8 Configuration
Installer reference guide
45
ERLQ004~0 EHVH/X04+0 EHVH/X08S26CA
Daikin Altherma - Low Temperature Split
4P313775-1C – 2012.11
#
Code
Description
Request is NOT available in leaving
water temperature control.
a
d
e
b
b
c
b
c
c
▪ a: Space heating/cooling control
(user interface)
▪ b: OFF
▪ c: On
▪ d: Heating demand (by ext RT or
RT)
▪ e: Pump operation
8.2.3
Quick wizard: Options
Domestic hot water settings
This chapter only applies to systems with a domestic hot water tank
installed:
▪ EHBH/X: an optional domestic hot water tank is available,
▪ EHVH/X: a domestic hot water tank is standard incorporated into
the indoor unit.
Following settings must be made accordingly.
#
Code
Description
[A.2.2.1]
[E-05]
DHW operation:
▪ 0 (No): NOT installed. Default for
EHBH/X.
▪ 1 (Yes): Installed. Default for EHVH/X.
Remark: For EHVH/X, the domestic
hot water tank is by default installed.
Do NOT change this setting.
[A.2.2.3]
[E-07]
During domestic hot water preparation,
the heat pump can be assisted by an
electrical heater to ensure the domestic
hot water preparation even for high
desired tank temperatures.
DHW tank heater:
▪ 0 (Horizontal BSH): Installed at side of
the tank. Default for EHBH/X.
▪ 1 (Backup heater): Default for
EHVH/X. The backup heater will also
be used in domestic hot water heating.
#
Code
Description
[A.2.2.A]
[D-02]
The indoor unit offers the possibility to
connect a field supplied domestic hot
water pump (On/OFF type). Depending
on the installation and configuration on
the user interface, we distinguish its
functionality.
DHW pump:
▪ 0 (No)(default): NOT installed.
▪ 1 (Secondary rtrn): Installed for instant
hot water when water is tapped. The
end-user sets the operation timing
(weekly schedule time) of the
domestic hot water pump when it
should run. Control of this pump is
possible through the indoor unit.
▪ 2
(Disinf.
shunt):
Installed
for
disinfection.
It
runs
when
the
disinfection function of the domestic
hot water tank is running. No further
settings are needed.
See also illustrations below.
Domestic hot water pump installed for…
Instant hot water
Disinfection
c
f
b
a
g
c
b
a
d
f
e
g
a
Indoor unit
b
Tank
c
Domestic hot water pump
d
Heater element
e
Non
‑
return valve
f
Shower
g
Cold water
Thermostats and external sensors
See "5 Application guidelines" on page 8.
#
Code
Description
[A.2.2.4]
[C-05]
Contact type main
In external room thermostat control, the
contact type of the optional room
thermostat or heat pump convector for
the main leaving water temperature zone
must be set. See "5 Application
guidelines" on page 8.
▪ 1 (Thermo ON/OFF): The connected
external room thermostat or heat
pump convector sends the heating or
cooling demand by the same signal as
it is connected to only 1 digital input
(preserved for the main leaving water
temperature zone) on the indoor unit
(X2M/1). Select this value in case of a
connection
to
the
heat
pump
convector (FWXV).
▪ 2
(C/H
request)(default):
The
connected external room thermostat
sends separate heating and cooling
demand and is therefore connected to
the 2 digital input (preserved for the
main leaving water temperature zone)
on the indoor unit (X2M/1 and 2).
Select this value in case of connection
with the wired (EKRTWA) or wireless
(EKRTR1) room thermostat.