• Heating • Daikin Altherma low temperature split

3

• Daikin Altherma low temperature split • ERLQ-CV3

2

Specifications

 Notes

 (1) Condition 1: cooling Ta 35ºC - LWE 18ºC (DT = 5ºC); heating Ta DB/WB 7ºC/6ºC - LWC 35ºC (DT = 5ºC)
 (2) Condition 2: cooling Ta 35ºC - LWE 7ºC ( DT = 5ºC); heating Ta DB/WB 7ºC/6ºC - LWC 45ºC ( DT = 5ºC )
 (3) DB/WB 7ºC/6ºC - LWC 35ºC (DT=5ºC)
 (4) DB/WB 7ºC/6ºC - LWC 45ºC (Dt=5ºC)
 (5) Condition 3: heating Ta DB -7ºC (RH85%) - LWC 35ºC
 (6) Condition 4: heating Ta DB -7ºC (RH85%) - LWC 45ºC

2-1 Nominal Capacity And Nominal Input

EHBH04C3V/

ERLQ004CV3

EHBH08C3V/

ERLQ006CV3

EHBH08C9W/
ERLQ006CV3

EHBH08C3V/

ERLQ008CV3

EHBH08C9W/
ERLQ008CV3

Heating capacity Min.

kW

1.80 (1) / 1.80 (2)

1.80 (1) / 1.80 (2)

1.80 (1) / 1.80 (2)

1.80 (1) / 1.80 (2)

1.80 (1) / 1.80 (2)

Nom.

kW

4.40 (1) / 4.03 (2)

6.00 (1) / 5.67 (2)

6.00 (1) / 5.67 (2)

7.40 (1) / 6.89 (2)

7.40 (1) / 6.89 (2)

Max.

kW

5.12 (1) / 4.90 (2)

8.35 (1) / 7.95 (2)

8.35 (1) / 7.95 (2)

10.02 (1) / 9.35 (2)

10.02 (1) / 9.35 (2)

Power input

Heating

Nom.

kW

0.87 (1) / 1.13 (2)

1.27 (1) / 1.59 (2)

1.27 (1) / 1.59 (2)

1.66 (1) / 2.01 (2)

1.66 (1) / 2.01 (2)

Max.

kW

-

COP

5.04 (1) / 3.58 (2)

4.74 (1) / 3.56 (2)

4.74 (1) / 3.56 (2)

4.45 (1) / 3.42 (2)

4.45 (1) / 3.42 (2)

Pump

Nominal ESP unit

Heating

kPa

55 (3) / 59 (4)

48 (3) / 51 (4)

48 (3) / 51 (4)

37 (3) / 41 (4)

37 (3) / 41 (4)

Water side Heat 
exchanger

Water flow rate

Heating Nom

.

l/min

12.6 (3) / 11.6 (4)

17.2 (3) / 16.3 (4)

17.2 (3) / 16.3 (4)

21.2 (3) / 19.8 (4)

21.2 (3) / 19.8 (4)

2-2 Nominal Capacity And Nominal Input

EHBH16C3V/

ERLQ011CV3

EHBH16C9W/
ERLQ011CV3

EHBH16C3V/

ERLQ014CV3

EHBH16C9W/
ERLQ014CV3

EHBH16C3V/

ERLQ016CV3

EHBH16C9W/
ERLQ016CV3

Heating 
capacity

Min.

kW

-

-

Nom.

kW

11.20 (1) / 10.98 

(2)

11.20 (1) / 10.98 (2)

14.50 (1) / 13.60 (2)

14.50 (1) / 13.60 (2)

16.00 (1) / 15.20 (2)

16.00 (1) / 15.20 (2)

Max.

kW

8.81 (3) / 8.16 (4)

8.81 (3) / 8.16 (4)

11.65 (3) / 10.96 (4)

11.65 (3) / 10.96 (4)

12.30 (3) / 11.35 (4)

12.30 (3) / 11.35 (4)

Power input

Heating

Nom.

kW

2.56 (1) / 3.19 (2)

2.56 (1) / 3.19 (2)

3.42 (1) / 4.13 (2)

3.42 (1) / 4.13 (2)

3.81 (1) / 4.66 (2)

3.81 (1) / 4.66 (2)

Max.

kW

3.52 (3) / 4.14 (4)

3.52 (3) / 4.14 (4)

4.95 (3) / 5.66 (4)

4.95 (3) / 5.66 (4)

5.49 (3) / 6.43 (4)

5.49 (3) / 6.43 (4)

COP

4.38 (1) / 2.50 (3) 

/ 3.44 (2) / 1.97 

(4)

4.38 (1) / 2.50 (3) / 

3.44 (2) / 1.97 (4)

4.24 (1) / 2.35 (3) / 

3.29 (2) / 1.94 (4)

4.24 (1) / 2.35 (3) / 

3.29 (2) / 1.94 (4)

4.20 (1) / 2.24 (3) / 

3.26 (2) / 1.79 (4)

4.20 (1) / 2.24 (3) / 

3.26 (2) / 1.79 (4)

Pump

Nominal ESP 
unit

Heating

kPa

86 (1) / 88 (2)

86 (1) / 88 (2)

47 (1) / 59 (2)

47 (1) / 59 (2)

26 (1) / 38 (2)

26 (1) / 38 (2)

Water side Heat 
exchanger

Water flow rate Heating Nom. l/min

32.1 (1) / 31.5 (2)

32.1 (1) / 31.5 (2)

41.6 (1) / 39 (2)

41.6 (1) / 39 (2)

45.9 (1) / 43.6 (2)

45.9 (1) / 43.6 (2)

2-3 Nominal Capacity And Nominal Input

EHBX04C3V/

ERLQ004CV3

EHBX08C3V/

ERLQ006CV3

EHBX08C9W/
ERLQ006CV3

EHBX08C3V/

ERLQ008CV3

EHBX08C9W/
ERLQ008CV3

Heating capacity

Min.

kW

1.80 (1) / 1.80 (2)

1.80 (1) / 1.80 (2)

1.80 (1) / 1.80 (2)

1.80 (1) / 1.80 (2)

1.80 (1) / 1.80 (2)

Nom.

kW

4.40 (1) / 4.03 (2)

6.00 (1) / 5.67 (2)

6.00 (1) / 5.67 (2)

7.40 (1) / 6.89 (2)

7.40 (1) / 6.89 (2)

Max.

kW

5.12 (1) / 4.90 (2)

8.35 (1) / 7.95 (2)

8.35 (1) / 7.95 (2)

10.02 (1) / 9.53 (2)

10.02 (1) / 9.53 (2)

Cooling capacity

Min.

kW

2.00 (1) / 2.00 (2)

2.50 (1) / 2.50 (2)

2.50 (1) / 2.50 (2)

2.50 (1) / 2.50 (2)

2.50 (1) / 2.50 (2)

Nom.

kW

5.00 (1) / 4.17 (2)

6.76 (1) / 4.84 (2)

6.76 (1) / 4.84 (2)

6.86 (1) / 5.3 (2)

6.86 (1) / 5.3 (2)

Power input

Heating

Nom.

kW

0.87 (1) / 1.13 (2)

1.27 (1) / 1.59 (2)

1.27 (1) / 1.59 (2)

1.66 (1) / 2.01 (2)

1.66 (1) / 2.01 (2)

Max.

kW

-

Cooling

Nom.

kW

1.48 (1) / 1.80 (2)

1.96 (1) / 2.07 (2)

1.96 (1) / 2.07 (2)

2.01 (1) / 2.34 (2)

2.01 (1) / 2.34 (2)

COP

5.04 (1) / 3.58 (2)

4.74 (1) / 3.56 (2)

4.74 (1) / 3.56 (2)

4.45 (1) / 3.42 (2)

4.45 (1) / 3.42 (2)

EER

3.37 (1) / 2.32 (2)

3.45 (1) / 2.34 (2)

3.45 (1) / 2.34 (2)

3.42 (1) / 2.29 (2)

3.42 (1) / 2.29 (2)

Pump

Nominal ESP 
unit

Cooling

kPa

57 (3) / 47 (4)

58 (3) / 42 (4)

58 (3) / 42 (4)

54 (3) / 41 (4)

54 (3) / 41 (4)

Heating

kPa

55 (5) / 59 (6)

48 (5) / 51 (6)

48 (5) / 51 (6)

37 (5) / 41 (6)

37 (5) / 41 (6)

Water side Heat 
exchanger

Water flow rate

Cooling

Nom.

l/min

12.0 (3) / 14.3 (4)

13.9 (3) / 19.4 (4)

13.9 (3) / 19.4 (4)

15.4 (3) / 19.7 (4)

15.4 (3) / 19.7 (4)

Heating

Nom.

l/min

12.6 (5) / 11.6 (6)

17.2 (5) / 16.3 (6)

17.2 (5) / 16.3 (6)

21.2 (5) / 19.8 (6)

21.2 (5) / 19.8 (6)

Summary of Contents for ERLQ-CV3

Page 1: ...Heating Technical Data Daikin Altherma low temperature split EEDEN12 725 ERLQ CV3...

Page 2: ......

Page 3: ...les 9 Cooling Capacity Tables 12 Certification Programs 14 4 Dimensional drawings 16 Dimensional Drawings 16 5 Centre of gravity 17 Centre of Gravity 17 6 Piping diagrams 18 Piping Diagrams 18 7 Wirin...

Page 4: ...ture split ERLQ CV3 1 1 Heating Daikin Altherma low temperature split 2 1 Features H e a t i n g E R L Q C V 3 D a i k i n A l t h Outdoor unit extracts heat from the outdoor air even at 25 C Inverter...

Page 5: ...Nom kW 2 56 1 3 19 2 2 56 1 3 19 2 3 42 1 4 13 2 3 42 1 4 13 2 3 81 1 4 66 2 3 81 1 4 66 2 Max kW 3 52 3 4 14 4 3 52 3 4 14 4 4 95 3 5 66 4 4 95 3 5 66 4 5 49 3 6 43 4 5 49 3 6 43 4 COP 4 38 1 2 50 3...

Page 6: ...3 1 1 33 6 2 43 1 1 36 0 2 46 0 1 36 0 2 46 0 1 37 6 2 48 0 1 37 6 2 48 0 1 Heating Nom l min 32 1 1 31 5 2 32 1 1 31 5 2 41 6 1 39 0 2 41 6 1 39 0 2 45 9 1 43 6 2 45 9 1 43 6 2 2 5 Nominal Capacity A...

Page 7: ...29 2 3 42 1 2 29 2 Pump Nominal ESP unit Cooling kPa 54 3 45 4 57 3 42 4 57 3 42 4 54 3 41 4 54 3 41 4 Heating kPa 52 5 55 6 49 5 51 6 49 5 51 6 37 5 41 6 37 5 41 6 Water side Heat exchanger Water fl...

Page 8: ...Quantity 7 Face area m 1 131 Stages Quantity 32 60 Empty tubeplate hole Quantity 0 Tube type 8 Hi XA 8 Hi XSS Fin Type WF fin Treatment Anti corrosion treatment PE Fan Type Propeller fan Quantity 1 2...

Page 9: ...em Equivalent m 70 Chargeless m 10 Additional refrigerant charge kg m See installation manual Level difference IU OU Max m 20 30 Heat insulation Both liquid and gas pipes Sound power level Heating Nom...

Page 10: ...n range 10 In accordance with EN IEC 61000 3 11 respectively EN IEC 61000 3 12 it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supp...

Page 11: ...Daikin Altherma low temperature split ERLQ CV3 1 3 Heating Daikin Altherma low temperature split 9 3 Capacity tables 3 1 Heating Capacity Tables...

Page 12: ...3 1 3 Heating Daikin Altherma low temperature split 10 Daikin Altherma low temperature split ERLQ CV3 3 Capacity tables 3 1 Heating Capacity Tables...

Page 13: ...g Daikin Altherma low temperature split 11 3 Capacity tables 3 1 Heating Capacity Tables ERLQ011 016C 3TW60332 5A Capacity in function of eld piping length for inverter Field piping length m Cooling H...

Page 14: ...3 1 3 Heating Daikin Altherma low temperature split 12 Daikin Altherma low temperature split ERLQ CV3 3 Capacity tables 3 2 Cooling Capacity Tables...

Page 15: ...Daikin Altherma low temperature split ERLQ CV3 1 3 Heating Daikin Altherma low temperature split 13 3 Capacity tables 3 2 Cooling Capacity Tables...

Page 16: ...3 1 3 Heating Daikin Altherma low temperature split 14 Daikin Altherma low temperature split ERLQ CV3 3 Capacity tables 3 3 Certification Programs...

Page 17: ...Daikin Altherma low temperature split ERLQ CV3 1 3 Heating Daikin Altherma low temperature split 15 3 Capacity tables 3 3 Certification Programs...

Page 18: ...onal Drawings ERLQ011 016CV3 3TW60334 2 Hole for anchor 1 Gas pipe connection 15 9 are 2 Liquid connection pipe 9 5 flare 3 Service port in the unit 4 Electronic connection and grounding terminal M5 i...

Page 19: ...Daikin Altherma low temperature split ERLQ CV3 1 5 Heating Daikin Altherma low temperature split 17 5 Centre of gravity 5 1 Centre of Gravity ERLQ011 016CV3 4TW31729 4...

Page 20: ...3 1 6 Heating Daikin Altherma low temperature split 18 Daikin Altherma low temperature split ERLQ CV3 6 Piping diagrams 6 1 Piping Diagrams...

Page 21: ...Daikin Altherma low temperature split ERLQ CV3 1 7 Heating Daikin Altherma low temperature split 19 7 Wiring diagrams 7 1 Wiring Diagrams Single Phase...

Page 22: ...tronic expansion valve main H1P 7P A2P Light emit diode serv monitor orange H2P Pepare test ickering Malfunction detection light up R2 Resistor Y3E Electronic expansion valve inj R1T Thermistor air Y1...

Page 23: ...re level dB Sound pressure level dB Sound pressure level dB Heating Octave band center frequency Hz Octave band center frequency Hz Octave band center frequency Hz 3TW60337 4 NOTES 1 Data is valid at...

Page 24: ...3 1 8 Heating Daikin Altherma low temperature split 22 Daikin Altherma low temperature split ERLQ CV3 8 Sound data 8 2 Sound Pressure Spectrum Heating...

Page 25: ...scale according to IEC 3 Reference acoustic pressure 0dB 20 Pa 4 If the sound is measured under actual installation conditions the measured value will be higher due to environmental noise and sound r...

Page 26: ...3 1 8 Heating Daikin Altherma low temperature split 24 Daikin Altherma low temperature split ERLQ CV3 8 Sound data 8 3 Sound Pressure Spectrum Cooling...

Page 27: ...scale according to IEC 3 Reference acoustic pressure 0dB 20 Pa 4 If the sound is measured under actual installation conditions the measured value will be higher due to environmental noise and sound r...

Page 28: ...3 3 3 L1 L2 L1 H 350 500 750 1000 0 L1 1 2H 2 1000 0 L1 1 2H H L1 L1 H L2 L1 L2 H 200 1000 500 1000 0 L2 1 2H 300 1 2H L2 H H L2 L2 H NOTES Legend Unit mm Suction side obstacle Discharge side obstacle...

Page 29: ...may still occur even if installed more than 3 m away Do not install in the following locations Locations where sulphurous acids and other corrosive gases may be present in the atmosphere Locations whe...

Page 30: ...3 1 10 Heating Daikin Altherma low temperature split 28 Daikin Altherma low temperature split ERLQ CV3 10 Operation range 10 1 Operation Range...

Page 31: ...Daikin Altherma low temperature split ERLQ CV3 1 10 Heating Daikin Altherma low temperature split 29 10 Operation range 10 1 Operation Range...

Page 32: ...5 The present leaflet is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N V Daikin Europe N V has compiled the content of this leaflet to the best of i...

Reviews: