• Heating • Daikin Altherma low temperature split

7

• Daikin Altherma low temperature split • ERLQ-CV3

2

Specifications

 Notes

 (1) Operation range heating (outdoor unit): range increase by support back-up heater
 (2) See operation range drawing: range increase by support booster heater or backup heater
 (3) The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to 
sound spectrum drawing for more information.
 (4) Minimum Ssc value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents produced by equipment 
connected to public low-voltage systems with input current \>16A and 

 75A per phase

 (5) PED unit category: excluded from scope of PED due to article 1, item 3.6 of 97/23/EC

Piping connections

Liquid

Quantity

-

1

Type

Flare connection

OD

mm

6.35

9.52

Gas

Quantity

-

1

Type

Flare connection

OD

mm

15.9

Drain

Quantity

2

3

Type

Hole

OD

mm

1x ø15 + 1x ø20

26

Drain 2

Quantity

-

1

Type

-

Hole

OD

mm

-

18

Piping length

OU - IU

Max.

m

30

50

System

Equivalent

m

-

70

Chargeless

m

-

10

Additional refrigerant charge

kg/m

-

See installation manual

Level difference

IU - OU

Max.

m

20

30

Heat insulation

-

Both liquid and gas pipes

Sound power level

Heating

Nom.

dBA

61

62

64

66

Cooling

Nom.

dBA

63

64

66

69

Sound pressure level

Heating

Nom.

dBA

48 (3)

49 (3)

51

52

Cooling

Nom.

dBA

48 (3)

49 (3)

50 (3)

50

52

54

Night quiet mode

Heating

dBA

-

42

43

Cooling

dBA

-

45

46

Defrost method

Reversed cycle

Pressure equalising

Defrost control

Sensor for outdoor heat exchanger temperature

Safety devices

Item

01

-

High pressure switch

02

-

Fan motor thermal protection

03

-

Fuse

PED

Category

Category I

-

2-10 Electrical Specifications

ERLQ004CV3

ERLQ006CV3

ERLQ008CV3

ERLQ011CV3

ERLQ014CV3

ERLQ016CV3

Power supply

Name

V3

Phase

1~

Frequency

Hz

50

Voltage

V

230

Voltage range

Min.

%

10

-10

Max.

%

10

Current

Zmax

Text

-

0.22

Minimum Ssc value

kVa

-

525

Starting current

Heating

A

18

-

Cooling

A

18

-

Maximum running 
current

Heating

A

-

34.2

Cooling

A

-

34.2

Recommended fuses

A

20

40

Wiring connections

For power supply

Quantity

3

-

Remark

-

See installation manual outdoor unit

For connection with 
indoor

Quantity

3

-

Remark

No earth wiring

See installation manual outdoor unit

Power supply intake

-

Outdoor unit only

2-9 Technical Specifications

ERLQ004CV3

ERLQ006CV3

ERLQ008CV3

ERLQ011CV3

ERLQ014CV3

ERLQ016CV3

Summary of Contents for ERLQ-CV3

Page 1: ...Heating Technical Data Daikin Altherma low temperature split EEDEN12 725 ERLQ CV3...

Page 2: ......

Page 3: ...les 9 Cooling Capacity Tables 12 Certification Programs 14 4 Dimensional drawings 16 Dimensional Drawings 16 5 Centre of gravity 17 Centre of Gravity 17 6 Piping diagrams 18 Piping Diagrams 18 7 Wirin...

Page 4: ...ture split ERLQ CV3 1 1 Heating Daikin Altherma low temperature split 2 1 Features H e a t i n g E R L Q C V 3 D a i k i n A l t h Outdoor unit extracts heat from the outdoor air even at 25 C Inverter...

Page 5: ...Nom kW 2 56 1 3 19 2 2 56 1 3 19 2 3 42 1 4 13 2 3 42 1 4 13 2 3 81 1 4 66 2 3 81 1 4 66 2 Max kW 3 52 3 4 14 4 3 52 3 4 14 4 4 95 3 5 66 4 4 95 3 5 66 4 5 49 3 6 43 4 5 49 3 6 43 4 COP 4 38 1 2 50 3...

Page 6: ...3 1 1 33 6 2 43 1 1 36 0 2 46 0 1 36 0 2 46 0 1 37 6 2 48 0 1 37 6 2 48 0 1 Heating Nom l min 32 1 1 31 5 2 32 1 1 31 5 2 41 6 1 39 0 2 41 6 1 39 0 2 45 9 1 43 6 2 45 9 1 43 6 2 2 5 Nominal Capacity A...

Page 7: ...29 2 3 42 1 2 29 2 Pump Nominal ESP unit Cooling kPa 54 3 45 4 57 3 42 4 57 3 42 4 54 3 41 4 54 3 41 4 Heating kPa 52 5 55 6 49 5 51 6 49 5 51 6 37 5 41 6 37 5 41 6 Water side Heat exchanger Water fl...

Page 8: ...Quantity 7 Face area m 1 131 Stages Quantity 32 60 Empty tubeplate hole Quantity 0 Tube type 8 Hi XA 8 Hi XSS Fin Type WF fin Treatment Anti corrosion treatment PE Fan Type Propeller fan Quantity 1 2...

Page 9: ...em Equivalent m 70 Chargeless m 10 Additional refrigerant charge kg m See installation manual Level difference IU OU Max m 20 30 Heat insulation Both liquid and gas pipes Sound power level Heating Nom...

Page 10: ...n range 10 In accordance with EN IEC 61000 3 11 respectively EN IEC 61000 3 12 it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supp...

Page 11: ...Daikin Altherma low temperature split ERLQ CV3 1 3 Heating Daikin Altherma low temperature split 9 3 Capacity tables 3 1 Heating Capacity Tables...

Page 12: ...3 1 3 Heating Daikin Altherma low temperature split 10 Daikin Altherma low temperature split ERLQ CV3 3 Capacity tables 3 1 Heating Capacity Tables...

Page 13: ...g Daikin Altherma low temperature split 11 3 Capacity tables 3 1 Heating Capacity Tables ERLQ011 016C 3TW60332 5A Capacity in function of eld piping length for inverter Field piping length m Cooling H...

Page 14: ...3 1 3 Heating Daikin Altherma low temperature split 12 Daikin Altherma low temperature split ERLQ CV3 3 Capacity tables 3 2 Cooling Capacity Tables...

Page 15: ...Daikin Altherma low temperature split ERLQ CV3 1 3 Heating Daikin Altherma low temperature split 13 3 Capacity tables 3 2 Cooling Capacity Tables...

Page 16: ...3 1 3 Heating Daikin Altherma low temperature split 14 Daikin Altherma low temperature split ERLQ CV3 3 Capacity tables 3 3 Certification Programs...

Page 17: ...Daikin Altherma low temperature split ERLQ CV3 1 3 Heating Daikin Altherma low temperature split 15 3 Capacity tables 3 3 Certification Programs...

Page 18: ...onal Drawings ERLQ011 016CV3 3TW60334 2 Hole for anchor 1 Gas pipe connection 15 9 are 2 Liquid connection pipe 9 5 flare 3 Service port in the unit 4 Electronic connection and grounding terminal M5 i...

Page 19: ...Daikin Altherma low temperature split ERLQ CV3 1 5 Heating Daikin Altherma low temperature split 17 5 Centre of gravity 5 1 Centre of Gravity ERLQ011 016CV3 4TW31729 4...

Page 20: ...3 1 6 Heating Daikin Altherma low temperature split 18 Daikin Altherma low temperature split ERLQ CV3 6 Piping diagrams 6 1 Piping Diagrams...

Page 21: ...Daikin Altherma low temperature split ERLQ CV3 1 7 Heating Daikin Altherma low temperature split 19 7 Wiring diagrams 7 1 Wiring Diagrams Single Phase...

Page 22: ...tronic expansion valve main H1P 7P A2P Light emit diode serv monitor orange H2P Pepare test ickering Malfunction detection light up R2 Resistor Y3E Electronic expansion valve inj R1T Thermistor air Y1...

Page 23: ...re level dB Sound pressure level dB Sound pressure level dB Heating Octave band center frequency Hz Octave band center frequency Hz Octave band center frequency Hz 3TW60337 4 NOTES 1 Data is valid at...

Page 24: ...3 1 8 Heating Daikin Altherma low temperature split 22 Daikin Altherma low temperature split ERLQ CV3 8 Sound data 8 2 Sound Pressure Spectrum Heating...

Page 25: ...scale according to IEC 3 Reference acoustic pressure 0dB 20 Pa 4 If the sound is measured under actual installation conditions the measured value will be higher due to environmental noise and sound r...

Page 26: ...3 1 8 Heating Daikin Altherma low temperature split 24 Daikin Altherma low temperature split ERLQ CV3 8 Sound data 8 3 Sound Pressure Spectrum Cooling...

Page 27: ...scale according to IEC 3 Reference acoustic pressure 0dB 20 Pa 4 If the sound is measured under actual installation conditions the measured value will be higher due to environmental noise and sound r...

Page 28: ...3 3 3 L1 L2 L1 H 350 500 750 1000 0 L1 1 2H 2 1000 0 L1 1 2H H L1 L1 H L2 L1 L2 H 200 1000 500 1000 0 L2 1 2H 300 1 2H L2 H H L2 L2 H NOTES Legend Unit mm Suction side obstacle Discharge side obstacle...

Page 29: ...may still occur even if installed more than 3 m away Do not install in the following locations Locations where sulphurous acids and other corrosive gases may be present in the atmosphere Locations whe...

Page 30: ...3 1 10 Heating Daikin Altherma low temperature split 28 Daikin Altherma low temperature split ERLQ CV3 10 Operation range 10 1 Operation Range...

Page 31: ...Daikin Altherma low temperature split ERLQ CV3 1 10 Heating Daikin Altherma low temperature split 29 10 Operation range 10 1 Operation Range...

Page 32: ...5 The present leaflet is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N V Daikin Europe N V has compiled the content of this leaflet to the best of i...

Reviews: