IM 1049-9
Filter Access
Each unit is shipped with a filter bracket for side filter
removal. For bottom removal push the filter up into top
bracket to gain clearance of bottom bracket and remove
the filter. Also, a sheet metal duct filter retainer can be
fabricated when return air duct work is used.
Air Discharge Conversion
Unit sizes 007 thru 060 are stocked as straight
discharge. A straight discharge unit may be converted to
an end discharge by doing the following:
Note:
The information covered in this section of the
blower assembly orientation is typical of Daikin
units. Regardless, if you are changing end to
straight or straight to end the blower assembly
has to turn 90 degrees and simultaneously rotate
180 degrees to achieve the proper orientation.
Not all Daikin units will have the same air dis-
charge location but will have the same general
results when following the instructions.
DANGER
Hazardous Voltage!
Disconnect all electric power including remote
disconnects before servicing. Failure to disconnect
power before servicing can cause severe personal
injury or death.
CAUTION
Sharp edges can cause personal injury. Avoid contact with them.
Use care and wear protective clothing, safety glasses and gloves
when handling parts and servicing heat pumps.
1 .
Turn off power to the unit at the breaker box.
2 .
Remove the top panel by removing the screws
around the perimeter of the top securing it to the
lower cabinet (
Figure 4
).
Note:
Retain all screws for reinstalling.
3 .
Remove the access panel to the fan motor by
loosening the two (2) screws at the bottom holding
the panel (
Figure 4
). Remove the piece of insulation
at the bottom on the side of the bottom panel.
4 .
If the unit being converted is installed and has been
operating, discharge the capacitor. Release the
wire clip shown in
Figure 3
to provide slack in the
wires. If necessary remove the wire tie to provide
additional free wire length (
Figure 3
).
Figure 3: Discharge capacitor and release wire clip
Release wire clip to
provide slack in wiring
Discharge
Capacitor
Capacitor
5 .
Remove the screws securing the fan discharge
panel assembly (
Figure 4
).
Figure 4: Remove top and access panel to fan motor
Remove screws around
the perimeter of top
Loosen two (2) screws at
bottom of access panel to
fan motor
Remove Top
Remove Access
Panel to Fan
Motor Assembly
Fan Discharge Panel Assembly
(Bottom-Horizontal Orientation)