C
ontrols
IM 1049-9
18 www.DaikinApplied.com
Table 7: MicroTech III Controller Status LED's
Description
Type*
Yellow
Green
Red
Emergency Shutdown
Mode
OFF
Flash
OFF
Low Voltage Brownout
Fault
OFF
Flash
OFF
High Pressure (HP1)
Fault
OFF
OFF
Flash
Low Pressure (LP1)
Fault
OFF
OFF
ON
Low Suction Temp (LT1) Sensor Fail
Fault
Flash
Flash
ON
Low Suction Temp (LT1)
Fault
Flash
OFF
OFF
Room Temp Sensor Fail (with Room Sensor Control Only)
Fault
Flash
Flash
ON
Condensate Overflow (Cooling & Dehumidification Modes Only)
Fault
ON
OFF
OFF
Low Entering Water Temp (Heating Compressor Inhibit; No Display with Boilerless EH)
Fault
Flash
OFF
Flash
Serial EEPROM Corrupted
Fault
ON
ON
ON
Service Test Mode Enabled
Mode
Flash
Flash
Flash
Unoccupied Mode
Mode
ON
ON
OFF
Occupied, Bypass, Standby Modes
Mode
OFF
ON
OFF
* Mode / Faults are listed in order of priority.
Table 8: I/O Expansion Module Jumper Settings
I/O Expansion Description
Jumper(s)
Jumper Setting
Model
Compressor Options
JP1
JP1
Open
Single Compressor Model (factory default setting)
JP1
Shorted
Dual Compressor Model
Hot Gas/Water Reheat (HGR)
Dehumidification
JP2
JP2
Open
None (default)
JP2
Shorted
Hot Gas / Water Reheat (HGR)
Secondary Heating Options
JP3 & JP4
JP3
Open
None
JP4
Open
JP3
Shorted
Supplemental Electric Heat*
JP4
Open
JP3
Open
Boilerless Electric Heat*
JP4
Shorted
Fan Speed Selection
JP5 & JP6
JP5
Open
Single Speed Fan
JP6
Open
Not Used
JP7
JP7
Open
–
* I/O Expansion module supplied with Boilerless or Supplemental Electric Heat option.
Table 9: I/O Expansion Module LED & Fault Outputs
Description
Type
Yellow
Green
Red
Invalid Jumper Configuration
Fault
Flash
Flash
OFF
Baseboard Communication Fail
Fault
OFF
Flash
Flash
Entering Water Temp Sensor Fail (with Boilerless Electric Heating)
Fault
Flash
Flash
ON
Service Test Mode Enabled
Mode
Flash
Flash
Flash
Unoccupied Mode
Mode
ON
ON
OFF
Occupied, Bypass, Standby, or Tenant Override Modes
Mode
OFF
ON
OFF
Note:
Mode / Faults are listed in order of priority.
I/O Expansion module supplied with Boilerless or Supplemental Electric Heat option.