background image

s

tart

-

uP

IM 1049-9 

14 www.DaikinApplied.com

Start-up

1 . 

Open all valves to full open position and turn on 

power to the conditioner.

2 . 

Set thermostat for “Fan Only” operation by selecting 

“Off” at the system switch and “On” at the fan switch. 

If “Auto” fan operation is selected, the fan will cycle 

with the compressor. Check for proper air delivery.

3 . 

For those units that have two-speed motors, 

reconnect for low speed operation if necessary.

4 . 

Set thermostat to “Cool.” If the thermostat is an 

automatic changeover type, simply set the cooling 

temperature to the coolest position. On manual 

changeover types additionally select “Cool” at the 

system switch. 

Again, many conditioners have time delays which 

protect the compressor(s) against short cycling. 

After a few minutes of operation, check the 

discharge grilles for cool air delivery. Measure 

the temperature difference between entering and 

leaving water. It should be approximately 1½ 

times greater than the heating mode temperature 

difference. For example, if the cooling temperature 

difference is 15°F (8°C), the heating temperature 

difference should have been 10°F (5°C). 

Without automatic flow control valves, target a 

cooling temperature difference of 10°F to 14°F (5°C 

to 8°C). Adjust the combination shutoff/balancing 

valve in the return line to a water flow rate which will 

result in the 10˚F to 14°F (5°C to 8°C) difference.

5 . 

Set thermostat to “Heat.” If the thermostat is the 

automatic changeover type, set system switch to the 

“Auto” position and depress the heat setting to the 

warmest selection. Some conditioners have built-

in time delays which prevent the compressor from 

immediately starting. With most control schemes, 

the fan will start immediately. After a few minutes of 

compressor operation, check for warm air delivery 

at discharge grille. If this is a “cold building” start- 

up, leave unit running until return air to the unit is at 

least 65°F (18°C). 

Measure the temperature difference between 

entering and leaving air and entering and leaving 

water. With entering water of 60°F to 80°F (16°C to 

27°C), leaving water should be 6°F to 12°F (3.3°C to 

6.6°C) cooler, and the air temperature rise through 

the machine should not exceed 35°F (19°C). If 

the air temperature exceeds 35°F (19°C), then the 

water flow rate is inadequate.

6 . 

Check the elevation and cleanliness of the 

condensate line. If the air is too dry for sufficient 

dehumidification, slowly pour enough water into the 

condensate pan to ensure proper drainage.

7 . 

If the conditioner does not operate, check the 

following points:

 

a.  Is supply voltage to the machine compatible?

 

b.  Is thermostat type appropriate?

 

c.  Is thermostat wiring correct?

8 . 

If the conditioner operates but stops after a brief period:

 

a.  Is there proper airflow? Check for dirty filter,  

 

  incorrect fan rotation (3-phase fan motors only),   

  or incorrect ductwork.

 

b.  Is there proper water flow rate within    

 

  temperature limits? Check water balancing;  

 

  backflush unit if dirt-clogged.

9 . 

Check for vibrating refrigerant piping, fan wheels, etc.

10 . 

Do not lubricate the fan motor during the first year of 

operation as it is prelubricated at the factory.

11 . 

Field supplied relays installed on the input terminals 

W1, W2, Y1, Y2 or G may introduce electrical noise. 

Never install relay coils in series with the inputs.

Summary of Contents for Enfinity CCW

Page 1: ...Installation and Maintenance Manual IM 1049 9 Group WSHP Part Number 910258820 Date December 2018 Daikin Enfinity Horizontal Water Source Heat Pumps R 410A Refrigerant Model CCH CCW Unit Sizes 007 070...

Page 2: ......

Page 3: ...rt up 23 Changing PSC Fan Motor Speed 23 Optional EC Motor 25 Start up 26 Typical Wiring Diagrams 27 Thermostats Wall Sensors 32 Typical Connections For Thermostats Temperature Sensors 32 Additional A...

Page 4: ...ht Discharge Air 09 13 E End Discharge S Straight Discharge Blower Motor 10 14 15 01 Standard PSC 03 Low Static 04 ECM Construction Type 12 18 A Standard 1 2 inch FG insulation 1 filter rack B Standar...

Page 5: ...spection by the carrier s agent within fifteen 15 days of the delivery date and file a claim with the carrier CAUTION The installer must determine and follow all applicable codes and regulations This...

Page 6: ...ts 5 Each unit is furnished with a hanger kit The kit is shipped unassembled and includes hanger brackets rubber isolators washers bolts and lock washers Lay out the threaded rods per the dimension in...

Page 7: ...personal injury or death CAUTION Sharp edges can cause personal injury Avoid contact with them Use care and wear protective clothing safety glasses and gloves when handling parts and servicing heat pu...

Page 8: ...Fan Motor Reinstall Top Completed End Discharge Assembly IM 1049 9 8 www DaikinApplied com 6 Lift the fan assembly out rotating it 180 degrees and position it within the opening at the end of the unit...

Page 9: ...ace a straight length of duct 5 to 10 times the duct width before the next fitting to smooth out airflow Diffusers that are located in the bottom of a trunk duct can also produce noise For this same r...

Page 10: ...gure 9 Standard 1 25mm Filter rack return air duct collar Standard 2 51mm Figure 10 Optional 2 51mm Filter rack return air duct collar Tool less Filter Removal Ventilation Air Ventilation may require...

Page 11: ...Volt Operation All 208 230 volt single phase and three phase units are factory wired for 208 volt operation For 230 phase operation the line voltage tap on the 24 volt transformer must be changed Dis...

Page 12: ...tape to assure a tight seal Figure 11 Sizes 007 through 060 shown Ball Valves Supply Riser Return Riser Condensate Riser Supply Air Hanger Kits 4 Flex Hoses Electrical Access Panel Note Do not over t...

Page 13: ...an drain water 3 Shut off supplemental heater and circulator pump and open all drains and vents to completely drain down the system Short circuited supply and return runouts should now be connected to...

Page 14: ...selection Some conditioners have built in time delays which prevent the compressor from immediately starting With most control schemes the fan will start immediately After a few minutes of compressor...

Page 15: ...not for continuous duty Operating Mode Entering Air F Entering Water F Minimum Maximum Standard Range Extended Range DB WB DB WB Minimum Maximum Minimum Maximum Cooling 50 40 105 87 45 120 30 120 Amb...

Page 16: ...al output to indicate an alarm condition exists Remote Reset of Automatic Lockouts The Remote Reset feature provides the means to remotely reset some lockouts There are 3 means to reset an automatic l...

Page 17: ...larm Output TB2 3 W2 Thermostat Heat Stage 2 Input TB2 4 W1 Thermostat Heat Stage 1 Input TB2 5 Y2 Thermostat Cool Stage 2 Input TB2 6 Y1 Thermostat Cool Stage 1 Input TB2 7 G Thermostat Fan Input TB2...

Page 18: ...s Jumper Setting Model Compressor Options JP1 JP1 Open Single Compressor Model factory default setting JP1 Shorted Dual Compressor Model Hot Gas Water Reheat HGR Dehumidification JP2 JP2 Open None def...

Page 19: ...rned on This signal is detected by a pump restart relay providing a N O or N C set of contacts for heat pump loop circulation pump or motorized valve control When used with a system control by others...

Page 20: ...apability of substituting the wall sensor with a duct mounted return air sensor Each unit controller orchestrates the following unit operations Enable heating and cooling to maintain setpoint based on...

Page 21: ...ed that the MAC address dip switches on the communication module be set prior to installing the unit in the ceiling Access to the dip switches may be limited when the unit is installed Reference IM 92...

Page 22: ...IM 1049 9 22 www DaikinApplied com Controls Figure 18 LonWorks Communication Module Placement on MicroTech III Unit Controller...

Page 23: ...GRN RD LOW BLK HIGH Factory Wired WHT CAPACITOR LINE BRN FAN MOTOR Unit Sizes 015 and 024 all available voltages Fan motors on unit sizes 015 and 024 in all available voltages have a four position ter...

Page 24: ...0 60 1 and 208 230 60 3 factory wired for low speed 1 YEL 2 BRN 3 BLK 4 RED LOW FACTORY WIRED LINE HIGH GR YE CAPACITOR FAN MOTOR Unit Size 048 380 50 3 460 60 3 575 60 3 The fan motor on unit size 04...

Page 25: ...NE HIGH FACTORY WIRED GR YE CAPACITOR FAN MOTOR Unit Size 070 460 60 3 575 60 3 The fan motor on unit size 070 for voltages 460 60 3 and 575 60 3 Figure 32 have a five position terminal block and are...

Page 26: ...g After a few minutes of operation check the discharge grilles for cool air delivery Measure the temperature difference between entering and leaving water It should be approximately 1 1 2 times greate...

Page 27: ...sensor is included with ECM and or Secondary Electric Heat Legend Item Description C1 Capacitor Compressor C2 Capacitor Fan CC Compressor Contactor CM Compressor Motor COS Condensate Overflow Sensor...

Page 28: ...EWT sensor is included with ECM and or Secondary Electric Heat Legend Item Description C1 Capacitor Compressor C2 Capacitor Fan CC Compressor Contactor CM Compressor Motor COS Condensate Overflow Sen...

Page 29: ...itch SLTS Suction Line Temp Sensor LWT Leaving Water Temp Sensor MIII MicroTech III Main Board RAT Return Air Temp Sensor RV Reversing Valve Solenoid X1 Transformer _____ Standard Unit Wiring _ _ _ _...

Page 30: ...LED Annunciator Harness LP Low Pressure Switch SLTS Suction Line Temp Sensor LWT Leaving Water Temp Sensor MIII MicroTech III Main Board R1 Relay Fan Motor RAT Return Air Temp Sensor RV Reversing Val...

Page 31: ...mp Sensor LWT Leaving Water Temp Sensor MIII MicroTech III Main Board RAT Return Air Temp Sensor RV Reversing Valve Solenoid X1 Transformer _____ Standard Unit Wiring _ _ _ _ Optional Wiring by others...

Page 32: ...Y2 G C RH RC W2 A I O Expansion Module TB1 MicroTech III Controller Terminal TB2 Programmable Touch Screen Y1 1 Notes Includes thermostat and wall plate Refer to IO manual 910193127 Figure 41 Program...

Page 33: ...132 910193133 910193134 P N 667720401 Sensors used with MicroTech III control Building Automated System Operation Figure 46 Digitally Adjustable Display Sensor 6 button P N 910121754 1 R 2 4 E U 6 5 3...

Page 34: ...10121753 3 2 5 1 4 Figure 51 Adjustable Cool Warm with Occupancy Switch P N 910121753 NOTICE For 50Hz units it may be necessary to install a Ferrite Core Noise Suppresor on the thermostat cord cable w...

Page 35: ...ssory used when up to 3 units are controlled from a single thermostat Typically the control panel and board is centrally mounted between the units and thermostat A maximum of 2 boards may be used toge...

Page 36: ...a water source heat pump operates under a wide range of water and air temperatures the values printed below are to be taken as suggested pressure and temperatures All Daikin water source heat pumps a...

Page 37: ...sure switch Unit is low on charge Table 14 Compressor Suction Temp Fail Room Temp Sensor Fail Leaving Water Temp Sensor Fail Description Type Yellow Green Red Compressor Suction Temp Sensor Fail Fault...

Page 38: ...have a control signal or ready to operate when a control signal is active I O Expansion Module LED Faults For units with optional boilerless electric heat Table 22 Invalid Jumper Configuration Descrip...

Page 39: ...Pressure Circuit 2 Description Type Yellow Green Red Low Pressure Circuit 2 Fault OFF OFF ON Loose wire connection on low pressure circuit Failed low pressure switch Unit is low on charge Table 28 Low...

Page 40: ...Pressure Low Low Air Flow Heating High High High High Low High Low High Pressure Normal Low Air Flow Cooling Low Low Low Low High High Low Low Temp Normal Low Water Flow Heating Low Low Low Low High...

Page 41: ...defective wiring or loose connection Check for faulty compressor capacitor Insufficient cooling or heating Check for lock rotor amp draw Check for defective compressor internal windings with ohm meter...

Page 42: ...n flows as a low pressure gas through the reversing valve and back to the suction side of the compressor to complete the cycle Figure 59 Heating Mode Single Circuit Only Shown Return Air Thermal Expan...

Page 43: ...roTech III unit controller s control or thermostat inputs However only one drive terminal R or C can be connected to any individual input terminal or damage may result Some control inputs are not acce...

Page 44: ...of Air ____________________________________________________________________ Filters Clean _____________________________________________________________________________ Condensate Traps Installed _____...

Page 45: ...be converted to GPM by looking in the equipment specificaton catalog Caution P GPM Note A conversion table must be used to find GPM from Delta P measurements Loop Fluid Temperature Rise Drop through...

Page 46: ...page Model Serial H P EWT 3 LWT 4 EWP 1 LWP 2 EAT 5 LAT 6 Volts Amps Cool ing Check Air Filter and Coil Comments more comments on next sheet 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23...

Page 47: ...Notes Comments Form WS CTS 00 01 Rev 4 14 www DaikinApplied com 47 IM 1049 9...

Page 48: ...ndard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details Refer to Form 933 430285Y To find your local Daikin Applied...

Reviews: