5 Unit installation

Installation manual

5

FTXJ35MV1BS/W6
Split system air conditioners
3P482320-15Z – 2021.10

Wall insulation

. When conditions in the wall exceed 30°C and a

relative  humidity  of  80%,  or  when  fresh  air  is  inducted  into  the
wall,  then  additional  insulation  is  required  (minimum  10  mm
thickness, polyethylene foam).

Wall  strength. 

Check  whether  the  wall  or  the  floor  is  strong

enough to support the weight of the unit. If there is a risk, reinforce
the wall or the floor before installing the unit.

Spacing. 

Install the unit at least 1.8 m from the floor and keep the

following  requirements  in  mind  for  distances  from  the  walls  and
the ceiling:

≥50

≥50

≥100

(mm)

Note: 

 Make sure that there are no obstacles within 500 mm under

the signal receiver. They may influence reception performance of the
user interface.

5.2

Mounting the indoor unit

5.2.1

To install the mounting plate

1

Install the mounting plate temporarily.

2

Level the mounting plate.

3

Mark  the  centres  of  the  drilling  points  on  the  wall  using  a  tape
measure. Position the end of tape measure at symbol " ".

4

Finish the installation by securing the mounting plate on the wall
using M4×25L screws (field supply).

INFORMATION

The removed pipe port cover can be kept in the mounting
plate pocket.

(mm)

998

357

135

142

348

160

151

φ

65

φ

65

49

100

200

124

303

49

50

203

234

67

a

f

b

c

d

e

h

g

a

Recommended mounting plate fixing spots

b

Pocket for the pipe port cover

c

Tabs for placing a spirit level

d

Through-the-wall hole Ø65 mm

e

Drain hose position

f

Position for the tape measure at symbol " "

g

Gas pipe end

h

Liquid pipe end

5.2.2

To drill a wall hole

CAUTION

For walls containing a metal frame or a metal board, use a
wall  embedded  pipe  and  wall  cover  in  the  feed-through
hole to prevent possible heat, electrical shock, or fire.

NOTICE

Be  sure  to  seal  the  gaps  around  the  pipes  with  sealing
material (field supply), in order to prevent water leakage.

1

Bore  a  65  mm  large  feed-through  hole  in  the  wall  with  a
downward slope towards the outside.

2

Insert a wall embedded pipe into the hole.

3

Insert a wall cover into the wall pipe.

a

c

a

b

φ 65

a

Wall embedded pipe

b

Putty

c

Wall hole cover

4

After  completing  wiring,  refrigerant  piping  and  drain  piping,  do
NOT forget to seal the gap with putty.

5.2.3

To remove the pipe port cover

INFORMATION

To  connect  the  piping  on  right-side,  right-bottom,  left-side
or left-bottom, the pipe port cover MUST be removed.

1

Cut  off  the  pipe  port  cover  from  inside  the  front  grille  using  a
coping saw.

Summary of Contents for Emura FTXJ-MW

Page 1: ...Installation manual Split system air conditioners English Installation manual Split system air conditioners FTXJ35MV1BW6 FTXJ35MV1BS6...

Page 2: ...al data 10 12 1 Wiring diagram 10 12 1 1 Unified wiring diagram legend 11 1 About the documentation 1 1 About this document INFORMATION Make sure that the user has the printed documentation and ask hi...

Page 3: ...N phase equipment might break down Establish proper earthing Do NOT earth the unit to a utility pipe surge absorber or telephone earth Incomplete earthing may cause electrical shock Install the requi...

Page 4: ...he latest version of this manual visit app daikineurope com INFORMATION Daikin Industries Czech Republic s r o declares that the radio equipment type inside of this unit is in compliance with Directiv...

Page 5: ...4 25L screws field supply INFORMATION The removed pipe port cover can be kept in the mounting plate pocket mm 998 357 135 142 348 160 151 65 6 5 49 100 200 124 303 49 50 203 234 67 a f b c d e h g a R...

Page 6: ...the piping on left side left back or left bottom INFORMATION The factory default is right side piping For left side piping remove the piping from the right side and install it on the left side 1 Remov...

Page 7: ...temperature is higher than 30 C and the humidity is higher than RH 80 the thickness of the insulation materials should be at least 20 mm to prevent condensation on the surface of the insulation 6 2 Co...

Page 8: ...t least 50 mm WARNING Provide adequate measures to prevent that the unit can be used as a shelter by small animals Small animals that make contact with electrical parts can cause malfunctions smoke or...

Page 9: ...bottom frame of the unit with both hands to set it on the bottom hooks of the mounting plate Make sure that the wires do NOT get squeezed anywhere Note Take care that the interconnection cable does N...

Page 10: ...ecified wires are used for the interconnection cable The indoor unit receives the signals of the user interface There are NO loose connections or damaged electrical components in the switch box The in...

Page 11: ...diode HAP Light emitting diode service monitor green HIGH VOLTAGE High voltage IES Intelligent eye sensor IPM Intelligent power module K R KCR KFR KHuR K M Magnetic relay L Live L Coil L R Reactor Sym...

Page 12: ...suyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe stanbul T RK YE Factory Kargal hanbaba OSB Mahallesi Organize Sanayi 1 Sokak No 28 54300 Hendek Sakarya T RK YE 3P482320 15Z 2021 10...

Reviews: