background image

EKHBH/X016BB

Indoor unit and options for air to water heat pump system

4PW62573-1 – 10.2010

Operation manual

16

[9] Heating and cooling set point ranges

The purpose of this field setting is to prevent the user from selecting
a wrong (i.e., too hot or too cold) leaving water temperature. Thereto
the heating temperature set point range and the cooling temperature
set point range available to the user can be configured.

[9-00] Heating set point upper limit: maximum leaving water
temperature for heating operation.

[9-01] Heating set point lower limit: minimum leaving water
temperature for heating operation.

[9-02] Cooling set point upper limit: maximum leaving water
temperature for cooling operation.

[9-03] Cooling set point lower limit: minimum leaving water
temperature for cooling operation.

[9-05~9-08] Automatic setback function 

Setback function provides the possibility to lower the water
temperature during space heating. The setback function can for
instance be activated during the night because the temperature
demands during night and day are not the same.

[9-05] Status: defines whether the setback function is turned
ON (1) or OFF (0)

[9-06] Start time: time at which setback is started

[9-07] Stop time: time at which setback is stopped

[9-08] Leaving water setback value

A

Normal leaving water temperature set point or calculated 
weather depended set point

B

Calculated leaving water setback temperature set point

t

Time

T

Temperature

INFORMATION

Make sure the domestic water is only heated up to the
domestic hot water temperature you require.
Start with a low domestic hot water storage
temperature set point, and only increase if you feel
that the domestic hot water supply temperature is not
sufficient for your needs (this depends on your water
using pattern).

Make sure the domestic water is not heated
unnecessary. Start with activating automatic storage
during night (default setting). If it seems that the
domestic hot water night storage operation is not
sufficient for your needs, an additional scheduled
reheat during daytime can be set.

NOTICE

The setting [4-03] shall not be modified. The installer
selected the proper setting for your application.

INFORMATION

The status of this setting is only mentioned to indicate
which settings and functions are applicable for your
application.

[4-03]=4 is only for domestic hot water tank with built-in
electrical booster heater (EKHW*).

[4-03]=5 is only for domestic hot water tank without
electrical booster heater (EKHTS).

CAUTION

In case of a floor heating application, it is important to
limit the maximum leaving water temperature at
heating operation according to the specifications of
the floor heating installation.

In case of a floor cooling application, it is important to
limit the minimum leaving water temperature at
cooling operation (field setting of parameter [9-03]) to
16~18°C to prevent condensation on the floor.

INFORMATION

Remark that the 

b

 icon will be flashing during setback

operation. The calculated leaving water setback set
point is 

not

 shown during setback operation.

By default the setback function is disabled.

The setback function can be combined with the
automatic weather dependent set point operation.

Setback function is an automatic daily scheduled
function.

The setback function can be combined with the
schedule timer. When setback is active, the scheduled
space heating set point will be lowered with the [9-08]
leaving water setback value.

INFORMATION

Only applicable if [4-03]=4 or 5!

It is advised to set the start time of automatic storage
during night [6-04] on the moment that the setback function
starts [9-06].

INFORMATION

Pay attention not to set the setback value too low,
especially during colder periods (e.g. winter time). It is
possible that the room temperature can not be reached (or
it will take a much longer time) because of the big
temperature difference.

[9-06]

[9-07]

B

A

T

t

55

°

C

53

°

C

2

°

C [9-08]

Summary of Contents for EKHBH016BB3V3

Page 1: ...BB EKHBX016BB Indoor unit and options for air to water heat pump system EKHBH016BB3V3 EKHBH016BB6V3 EKHBH016BB6WN EKHBH016BB6T1 EKHBH016BB9WN EKHBH016BB9T1 EKHBX016BB3V3 EKHBX016BB6V3 EKHBX016BB6WN EK...

Page 2: ...this manual are classified according to their severity and probability of occurrence Some types of danger are represented by special symbols 1 2 Meaning of used terms Installation manual Instruction m...

Page 3: ...ent sizes 200 and 260 litre Solar kit for domestic hot water tank option For information concerning the EKSOLHW solar kit refer to the installation manual of that kit Room thermostat kit option An opt...

Page 4: ...ipate this gas safely it is recommended that a hot tap be turned on for several minutes at a sink basin or bath but not at a dishwasher clothes washer or other appliance During this procedure there mu...

Page 5: ...ATURE DISPLAY 9 The display shows the current space heating cooling set temperature of the installation 12 SETTING Not used For installation purposes only 13 NOT AVAILABLE n This icon is displayed whe...

Page 6: ...orage set point of the domestic hot water temperature only for 4 03 4 or 5 The buttons are not used when the domestic hot water tank is not installed 34 QUIET MODE BUTTON s This button enables or disa...

Page 7: ...int upon user request 2 Reheat Scheduled The unit will heat up the domestic water tank starting from a scheduled time and untill the reheat set point is reached Preferally this is done during the time...

Page 8: ...ng operation 1 Press v for 5 seconds to activate powerful domestic water heating operation For EKHW only Icons w and m start flashing 1 For EKHTS only Icons w and start flashing 2 Powerful domestic wa...

Page 9: ...iquid refrigerant temperature u The outdoor temperature w The domestic hot water temperature INFORMATION Only use the pr button to enable or disable the schedule timer The schedule timer overrules the...

Page 10: ...m at the very end of this manual This form can help you define the required actions for each day Keep in mind that In the space heating and domestic water heating program 4 actions can be programmed p...

Page 11: ...e programming mode 8 Use the button to select the action number you would like to program or to modify 9 Use the ba button to select For space heating x switch heating and the controller off 9 set the...

Page 12: ...select For space cooling x switch cooling and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation For quiet mode and booster heater...

Page 13: ...button The actual mode is blinking 2 Use the pi and pj buttons to select the mode you want to program The selected mode is blinking You can leave programming by pressing the pr button 3 Press the but...

Page 14: ...n 6 Repeat step 2 through 4 to change other field settings as required 7 When finished press the z button to exit FIELD SET MODE Detailed description 0 User permission level If required certain user i...

Page 15: ..._Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi2_A Note that the Hi2_Ti value should be lower than Lo2_Ti as for warmer out...

Page 16: ...nt hysteresis Example 1 Scheduled storage 6 03 1 scheduled reheat 6 05 1 disinfection function 2 01 1 activated A Scheduled storage operation activated at 6 04 heat up domestic hot water untill domest...

Page 17: ...ng automatic storage during night default setting If it seems that the domestic hot water night storage operation is not sufficient for your needs an additional scheduled reheat during daytime can be...

Page 18: ...it refer to the installation manual of that kit d Local shift value weather dependent Local shift value weather dependent The local shift value weather dependent field setting is only relevant in case...

Page 19: ...n All 01 Status 1 ON 0 1 02 Start time 23 00 0 00 23 00 1 00 hour 03 Set point only in combination with domestic hot water tank without electrical booster heater EKHTS 60 fixed 5 C 03 Set point only i...

Page 20: ...related setting 9 Heating and cooling set point ranges 00 Heating set point upper limit 55 37 55 1 C 01 Heating set point lower limit 25 15 37 1 C 02 Cooling set point upper limit 22 18 22 1 C 03 Coo...

Page 21: ...Unit information readout 00 Software version Read only 01 EEPROM version Read only 02 Unit model identification Do not change the default value depending on model 03 Liquid refrigerant temperature Re...

Page 22: ...nt of oil and other parts must be done by a qualified installer in accordance with the applicable legislation Units must be treated at a specialized treatment facility for re use recycling and recover...

Page 23: ......

Page 24: ...4PW62573 1 10 2010 Copyright 2010 Daikin...

Reviews: