Indoor unit and options for air to water heat pump system

4PW62573-1 – 10.2010

Operation manual

14

[1] Weather dependent set point

The weather dependent set point field settings define the parameters
for the weather dependent operation of the unit. When weather
dependent operation is active the water temperature is determined
automatically depending on the outdoor temperature: low outdoor
temperatures will result in warmer water and vice versa. During
weather dependent operation, the user has the possibility to shift up
or down the target water temperature by a maximum of 5°C.

Field settings for heating operation

[1-00] Low ambient temperature (Lo_A): low outdoor
temperature.

[1-01] High ambient temperature (Hi_A): high outdoor
temperature.

[1-02] Set point at low ambient temperature (Lo_Ti): the
target outgoing water temperature when the outdoor
temperature equals or drops below the low ambient
temperature (Lo_A). 
Note that the Lo_Ti value should be higher than Hi_Ti, as for
low outdoor temperatures (i.e. Lo_A) warmer water is
required.

[1-03] Set point at high ambient temperature (Hi_Ti): the
target outgoing water temperature when the outdoor
temperature equals or rises above the high ambient
temperature (Hi_A). 
Note that the Hi_Ti value should be lower than Lo_Ti, as for
warmer outdoor temperatures (i.e. Hi_A) less warm water
suffices.

Field settings for cooling operation

[1-05] Weather dependent for cooling function enable (1)/
disable (0)

[1-06] Low ambient temperature (Lo2_A): low outdoor
temperature.

[1-07] High ambient temperature (Hi2_A): high outdoor
temperature.

[1-08] Set point at low ambient temperature (Lo2_Ti): the
target outgoing water temperature when the outdoor
temperature equals or drops below the low ambient
temperature (Lo2_A).
Note that the Lo2_Ti value should be higher than Hi2_Ti, as
for low outdoor temperatures (i.e. Lo2_A) less cold water
suffices.

[1-09] Set point at high ambient temperature (Hi2_Ti): the
target outgoing water temperature when the outdoor
temperature equals or rises above the high ambient
temperature (Hi2_A). 
Note that the Hi2_Ti value should be lower than Lo2_Ti, as
for warmer outdoor temperatures (i.e. Hi2_A) colder water is
required.

T

t

Target water temperature

T

A

Ambient (outdoor) temperature

Shift value

Shift value

[2] Disinfection function

Applies only to installations with a domestic hot water tank.

The disinfection function disinfects the domestic hot water tank by
periodically heating the domestic hot water to a specific temperature.

[2-00] Operation interval: day(s) of the week at which the
domestic hot water should be heated.

[2-01] Status: defines whether the disinfection function is
turned on (1) or off (0).

[2-02] Start time: time of the day at which the domestic hot
water should be heated.

[2-03] Set point: high water temperature to be reached.

[2-04] Interval: time period defining how long the set point
temperature should be maintained.

T

DHW

Domestic hot water temperature

T

U

User set point temperature (as set on the user interface)

T

H

High set point temperature [2-03]

t

Time

Lo_Ti

Lo2_Ti

Lo_A

Lo2_A

Hi_A

Hi2_A

TA

Tt

+ 05

00

– 05

Hi_Ti

Hi2_Ti

Shift value

CAUTION

The disinfection function field settings must be configured
by the installer according to the applicable legislation.

WARNING

Be aware that the domestic hot water temperature at the
hot water tap will be equal to the value selected in field
setting [2-03] after a disinfection operation.

When the high domestic hot water temperature can be a
potential risk for human injuries, a mixing valve (field
supply) shall be installed at the hot water outlet connection
of the domestic hot water tank. This mixing valve shall
secure that the hot water temperature at the hot water tap
never rises above a set maximum value. This maximum
allowable hot water temperature shall be selected
according to the applicable legislation.

CAUTION

Make sure that the disinfection function start time [2-02]
with defined duration [2-04] is not interrupted by possible
domestic hot water demand.

00.00

22.00

24.00

01.00

23.00

t

T

DHW

T

H

T

U

[2-02]

[2-03]

[2-04]

Summary of Contents for EKHBH016BB3V3

Page 1: ...BB EKHBX016BB Indoor unit and options for air to water heat pump system EKHBH016BB3V3 EKHBH016BB6V3 EKHBH016BB6WN EKHBH016BB6T1 EKHBH016BB9WN EKHBH016BB9T1 EKHBX016BB3V3 EKHBX016BB6V3 EKHBX016BB6WN EK...

Page 2: ...this manual are classified according to their severity and probability of occurrence Some types of danger are represented by special symbols 1 2 Meaning of used terms Installation manual Instruction m...

Page 3: ...ent sizes 200 and 260 litre Solar kit for domestic hot water tank option For information concerning the EKSOLHW solar kit refer to the installation manual of that kit Room thermostat kit option An opt...

Page 4: ...ipate this gas safely it is recommended that a hot tap be turned on for several minutes at a sink basin or bath but not at a dishwasher clothes washer or other appliance During this procedure there mu...

Page 5: ...ATURE DISPLAY 9 The display shows the current space heating cooling set temperature of the installation 12 SETTING Not used For installation purposes only 13 NOT AVAILABLE n This icon is displayed whe...

Page 6: ...orage set point of the domestic hot water temperature only for 4 03 4 or 5 The buttons are not used when the domestic hot water tank is not installed 34 QUIET MODE BUTTON s This button enables or disa...

Page 7: ...int upon user request 2 Reheat Scheduled The unit will heat up the domestic water tank starting from a scheduled time and untill the reheat set point is reached Preferally this is done during the time...

Page 8: ...ng operation 1 Press v for 5 seconds to activate powerful domestic water heating operation For EKHW only Icons w and m start flashing 1 For EKHTS only Icons w and start flashing 2 Powerful domestic wa...

Page 9: ...iquid refrigerant temperature u The outdoor temperature w The domestic hot water temperature INFORMATION Only use the pr button to enable or disable the schedule timer The schedule timer overrules the...

Page 10: ...m at the very end of this manual This form can help you define the required actions for each day Keep in mind that In the space heating and domestic water heating program 4 actions can be programmed p...

Page 11: ...e programming mode 8 Use the button to select the action number you would like to program or to modify 9 Use the ba button to select For space heating x switch heating and the controller off 9 set the...

Page 12: ...select For space cooling x switch cooling and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation For quiet mode and booster heater...

Page 13: ...button The actual mode is blinking 2 Use the pi and pj buttons to select the mode you want to program The selected mode is blinking You can leave programming by pressing the pr button 3 Press the but...

Page 14: ...n 6 Repeat step 2 through 4 to change other field settings as required 7 When finished press the z button to exit FIELD SET MODE Detailed description 0 User permission level If required certain user i...

Page 15: ..._Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi2_A Note that the Hi2_Ti value should be lower than Lo2_Ti as for warmer out...

Page 16: ...nt hysteresis Example 1 Scheduled storage 6 03 1 scheduled reheat 6 05 1 disinfection function 2 01 1 activated A Scheduled storage operation activated at 6 04 heat up domestic hot water untill domest...

Page 17: ...ng automatic storage during night default setting If it seems that the domestic hot water night storage operation is not sufficient for your needs an additional scheduled reheat during daytime can be...

Page 18: ...it refer to the installation manual of that kit d Local shift value weather dependent Local shift value weather dependent The local shift value weather dependent field setting is only relevant in case...

Page 19: ...n All 01 Status 1 ON 0 1 02 Start time 23 00 0 00 23 00 1 00 hour 03 Set point only in combination with domestic hot water tank without electrical booster heater EKHTS 60 fixed 5 C 03 Set point only i...

Page 20: ...related setting 9 Heating and cooling set point ranges 00 Heating set point upper limit 55 37 55 1 C 01 Heating set point lower limit 25 15 37 1 C 02 Cooling set point upper limit 22 18 22 1 C 03 Coo...

Page 21: ...Unit information readout 00 Software version Read only 01 EEPROM version Read only 02 Unit model identification Do not change the default value depending on model 03 Liquid refrigerant temperature Re...

Page 22: ...nt of oil and other parts must be done by a qualified installer in accordance with the applicable legislation Units must be treated at a specialized treatment facility for re use recycling and recover...

Page 23: ......

Page 24: ...4PW62573 1 10 2010 Copyright 2010 Daikin...

Reviews: