Daikin EKCBH008BBV3 Operation Manual Download Page 9

EKCBX/H008BBV3

Unit for air to water heat pump system

4PW67442-1A – 12.2010

Operation manual

8

Displaying actual temperatures

1

Push the 

ba

 button for 5 seconds.

The 

b

 icon and the outgoing water temperature are displayed.

The icons 

l

 and 

=

 are flashing.

2

Use the 

pi

 and 

pj

 buttons to display:

If no button is pressed for 5 seconds, the controller leaves the
display mode.

Schedule timer operation

In schedule timer operation, the installation is controlled by the
schedule timer. The actions programmed in the schedule timer will be
executed automatically.

The schedule timer always follows the last command until a new
command is given. This means that the user can temporarily overrule
the last executed programmed command by manual operation (Refer
to 

"Manual operation" on page 7

). The schedule timer will regain

control over the installation as soon as the next programmed
command of the schedule timer occurs.

The schedule timer is enabled (

p

 icon displayed) or disabled (

p

 icon

not displayed), by pressing the 

pr

 button.

To set up the SCHEDULE TIMER refer to chapter 

"Programming and

consulting the schedule timer" on page 9

.

What can the schedule timer do?

The schedule timer allows the programming of:

1.

Space heating (refer to 

"Programming space heating or space

cooling" on page 10

)

Switch on the desired mode at a scheduled time, in combination
with a set point (weather dependent or manually set). 
Four actions per weekday can be programmed, totalling
28 actions.

2.

Space cooling (refer to 

"Programming quiet mode, booster

heating or domestic water heating" on page 11

).

Switch on the desired mode at a scheduled time, in combination
with a set point (weather dependent or manually set). Four
actions can be programmed. These actions are repeated daily.

3.

Quiet mode (refer to 

"Programming quiet mode, booster heating

or domestic water heating" on page 11

)

Switch the mode on or off at a scheduled time. Four actions can
be programmed per mode. These actions are repeated daily.

4.

Domestic water heating (refer to 

"Programming space heating or

space cooling" on page 10

)

[4-03]=0, 1, 2, or 3

Switch the mode on or off at a scheduled time. Four actions per
weekday can be programmed, totalling 28 actions.

[4-03]=4

Switch the mode on or off at a scheduled time. The switch set to
on means enabeling the programmed storage and reheat
operation.

Flashing icon(s)

Meaning

h

 or 

c

The entering water temperature

h

 or 

c

 and 

é

The outgoing water temperature after plate heat 
exchanger

h

 or 

c

 and 

)

The outgoing water temperature after backup 
heater (if installed)

ç

The liquid refrigerant temperature

u

The outdoor temperature

w

The domestic hot water temperature

INFORMATION

Only use the 

pr

 button to enable or disable the

schedule timer. The schedule timer overrules the 

y

button. The 

y

 button only overrules the schedule

timer until the next programmed action.

If the auto restart function is disabled, the schedule
timer will not be activated when power returns to the
unit after a power supply failure. Press the 

pr

 button

to enable the schedule timer again.

When power returns after a power supply failure, the
auto restart function reapplies the user interface
settings at the time of the power supply failure.

It is therefore recommended to leave the auto restart
function enabled.

The programmed schedule is time driven. Therefore, it
is essential to set the clock and the day of the week
correctly. Refer to 

"Setting the clock" on page 5

.

Manually adjust the clock for summertime and
wintertime. Refer to 

"Setting the clock" on page 5

.

A power failure exceeding 2 hours will reset the clock
and the day of the week. The schedule timer will
continue operation, but with a disordered clock. Refer
to 

"Setting the clock" on page 5

 to adjust the clock and

the day of the week.

The actions programmed in the schedule timer will not
be lost after a power failure so that reprogramming the
schedule timer is not required.

INFORMATION

When the unit is connected to an external room thermostat,
the schedule timer for space heating and space cooling is
overruled by the external room thermostat.

INFORMATION

The programmed actions are not stored according to
their timing but according to the time of programming.
This means that the action that was programmed first
gets action number 1, even though it is executed after
other programmed action numbers.

When the schedule timer switches space heating or
space cooling 

x

, the controller will also be

switched off. Note that this has no influence on
domestic water heating.

[4-03]=4In case no domestic water heating actions
are programmed, enabling or disabling the schedule
timer will only have influence on the space heating,
cooling and quite mode. In this way it is possible to
separate on one hand the space heating, cooling and
quite mode scheduled action as part of the schedule
timer and on the other hand the storage and reheat
operation of the domestic water heating.
In this way, it is easy to disable the space heating and
cooling by disabling the schedule timer with keeping
the storage and reheat domestic water heating
enabled (refer to 

"Scheduled domestic hot water

storage" on page 

15

 and 

"Scheduled/continuous

domestic hot water reheat" on page 16

).

NOTICE

The setting [4-03] shall not be modified. The installer
selected the proper setting for your application.

INFORMATION

The status of this setting is only mentioned to indicate
which settings and functions are applicable for your
application.

Summary of Contents for EKCBH008BBV3

Page 1: ...OPERATION MANUAL EKCBX008BBV3 EKCBH008BBV3 Unit for air to water heat pump system ...

Page 2: ... manual specified for a certain product or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance instructions Instruction manual specified for a certain product or application which explains if relevant how to install configure operate and or maintain the product or appl...

Page 3: ...er Refer to the operation manual of the indoor unit and to the installation manual of the digital I O PCB for more information Refer to the wiring diagram or connection diagram for connecting this PCB to the unit Bottom plate heater EKBPHT refer to the installation manual option Remote thermostat kit option An optional room thermostat EKRTW EKRTWA or EKRTR can be connected to the indoor unit Refer...

Page 4: ...t tap be turned on for several minutes at a sink basin or bath but not at a dishwasher clothes washer or other appliance During this procedure there must be no smoking open flame or any electrical appliance operating nearby If hydrogen is discharged through the tap it will probably make a sound as of air escaping 4 2 Operating the digital controller Operating the unit comes down to operating the di...

Page 5: ...9 OFF ICON x This icon indicates that the OFF action is selected when programming the schedule timer 10 INSPECTION REQUIRED k and l These icons indicate that inspection is required on the installation Consult your dealer 11 SET TEMPERATURE DISPLAY 9 The display shows the current space heating cooling set temperature of the installation 12 SETTING Not used For installation purposes only 13 NOT AVAI...

Page 6: ...ting the clock 33 DOMESTIC HOT WATER TEMPERATURE ADJUST BUTTONS wbi and wbj These buttons are used to adjust the current set point of the domestic hot water temperature only for 4 03 0 1 2 or 3 These buttons are used to adjust the current storage set point of the domestic hot water temperature only for 4 03 4 The buttons are not used when the domestic hot water tank is not installed 34 QUIET MODE ...

Page 7: ...e unit will immediately heat up the domestic water tank untill domestic hot water storage set point upon user request 2 Reheat Scheduled The unit will heat up the domestic water tank starting from a scheduled time and untill the reheat set point is reached Preferally this is done during the time of day when space heating demand is lowest Continuous The unit will continuously heat up the domestic w...

Page 8: ...disappears from the display Selecting powerful domestic water heating operation 1 Press v for 5 seconds to activate powerful domestic water heating operation Icons w and m start flashing Powerful domestic water heating is deactivated automatically when the set point for the domestic hot water is reached Selecting quiet mode operation s 1 Use the s button to activate quiet mode operation s Icon s ap...

Page 9: ... hot water temperature INFORMATION Only use the pr button to enable or disable the schedule timer The schedule timer overrules the y button The y button only overrules the schedule timer until the next programmed action If the auto restart function is disabled the schedule timer will not be activated when power returns to the unit after a power supply failure Press the pr button to enable the sche...

Page 10: ...he schedule timer remind Familiarise yourself with the icons and the buttons You will need them when programming Refer to Name and function of buttons and icons on page 4 Fill out the form at the very end of this manual This form can help you define the required actions for each day Keep in mind that In the space heating and domestic water heating program 4 actions can be programmed per weekday The...

Page 11: ...e 8 Use the button to select the action number you would like to program or to modify 9 Use the ba button to select For space heating x switch heating and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation For domestic water heating use the ba button to enable or disable the x action 10 Use the pi and pj buttons to set the corre...

Page 12: ...on time 8 Use the ba button to select For space cooling x switch cooling and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation For quiet mode and booster heater mode use the ba button to enable or disable the x action 9 Repeat steps 6 to 8 to program the other actions of the selected mode When all actions have been programmed m...

Page 13: ... the next day e g copy all programmed actions from 1 to 2 To copy programmed actions to the next day proceed as follows 1 Press the button The actual mode is blinking 2 Use the pi and pj buttons to select the mode you want to program The selected mode is blinking You can leave programming by pressing the pr button 3 Press the button to confirm the selected mode The actual day is blinking 4 Select t...

Page 14: ...LD SET MODE The icon 3 will be displayed The current selected field setting code is indicated 2 with the set value displayed to the right 1 2 Press the bgi button to select the appropriate field setting first code 3 Press the bgj button to select the appropriate field setting second code 4 Press the pfi button and pfj button to change the set value of the select field setting 5 Save the new value by pr...

Page 15: ...perature Lo_A Note that the Lo_Ti value should be higher than Hi_Ti as for low outdoor temperatures i e Lo_A warmer water is required 1 03 Set point at high ambient temperature Hi_Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi_A Note that the Hi_Ti value should be lower than Lo_Ti as for warmer outdoor temperatures i e Hi...

Page 16: ... Scheduled domestic hot water storage The storage set point can be accessed directly using the wi and wj buttons 6 03 Scheduled storage defines whether the scheduled domestic water heating storage during night is enabled 1 or not 0 6 04 Scheduled storage start time time of the night at which the domestic water should be heated CAUTION The disinfection function field settings must be configured by the...

Page 17: ...estic hot water user interface set point 9 Heating and cooling set point ranges The purpose of this field setting is to prevent the user from selecting a wrong i e too hot or too cold leaving water temperature Thereto the heating temperature set point range and the cooling temperature set point range available to the user can be configured 9 00 Heating set point upper limit maximum leaving water tem...

Page 18: ...ld settings of the weather dependent set point 1 E Unit information readout E 00 Readout of the software version example 23 E 01 Readout of the EEPROM version example 23 E 02 Readout of the unit model identification example 11 E 03 Readout of the liquid refrigerant temperature E 04 Readout of the inlet water temperature INFORMATION Remark that the b icon will be flashing during setback operation The...

Page 19: ...heating off temperature 00 Installation related setting 01 Installation related setting 02 Space heating off temperature 25 14 25 1 C 03 Installation related setting 04 Not applicable Do not change the default value 05 Not applicable Do not change the default value 06 Installation related setting 07 Installation related setting 5 Installation related setting 00 Installation related setting 01 Inst...

Page 20: ...elated setting 05 Not applicable Do not change the default setting d Local shift value weather dependent 00 Installation related setting 01 Installation related setting 02 Installation related setting 03 Local shift value weather dependent 0 OFF 0 1 2 3 4 1 04 Not applicable Do not change the default value 05 Installation related setting 06 Not applicable Do not change the default value E Unit inf...

Page 21: ...lified installer in accordance with relevant local and national legislation Units must be treated at a specialized treatment facility for re use recycling and recovery By ensuring this product is disposed off correctly you will help to prevent potential negative consequences for the environment and human health Please contact the installer or local authority for more information DANGER Do not touch...

Page 22: ...NOTES NOTES ...

Page 23: ......

Page 24: ...Copyright 2010 Daikin 4PW67442 1A 12 2010 ...

Reviews: