Daikin EKCBH008BBV3 Operation Manual Download Page 6

Operation manual

5

EKCBX/H008BBV3

Unit for air to water heat pump system

4PW67442-1A – 12.2010

25.

SPACE HEATING/COOLING BUTTON 

=

This button allows manual switching between heating or cooling
mode (provided the unit is not a heating only unit).

When the unit is connected with an external room thermostat,
this button is not operable and the icon 

e

 is shown.

26.

DOMESTIC WATER HEATING BUTTON 

v

This button enables or disables heating of the domestic water.

This button is not used when the domestic hot water tank is not
installed.

27.

WEATHER DEPENDENT SET POINT BUTTON 

ba

This button enables or disables the weather dependent set point
function which is available in space heating operation only.

If the controller is set in permission level 2 or 3 (refer to 

"Field

settings" on page 13

), the weather dependent set point button

will not be operable.

28.

INSPECTION/TEST OPERATION BUTTON 

z

This button is used for installation purposes and changing field
settings. Refer to 

"Field settings" on page 13

.

29.

PROGRAMMING BUTTON 

<

This multi-purpose button is used to program the controller. The
function of the button depends on the actual status of the
controller or on previous actions carried out by the operator.

30.

SCHEDULE TIMER BUTTON 

r

/

p

The main function of this multi-purpose button is to
enable/disable the schedule timer.

The button is also used to program the controller. The function of
the button depends on the actual status of the controller or on
previous actions carried out by the operator.

If the controller is set in permission level 3 (refer to 

"Field

settings" on page 13

), the schedule timer button will not be

operable.

31.

TIME ADJUST BUTTON 

pi

 and 

pj

These multi-purpose buttons are used to adjust the clock, to
toggle between temperatures (refer to 

"Displaying actual

temperatures" on page 8

) and in schedule timer programming

mode.

32.

TEMPERATURE ADJUST BUTTONS 

bi

 and 

bj

These multi-purpose buttons are used to adjust the current set
point in normal operation mode or in schedule timer
programming mode. In weather dependent set point mode the
buttons are used to adjust the shift value. Finally, the buttons are
also used to select the weekday while setting the clock.

33.

DOMESTIC HOT WATER TEMPERATURE ADJUST BUTTONS

wbi

 and 

wbj

These buttons are used to adjust the current set point of the
domestic hot water temperature (only for [4-03]=0, 1, 2, or 3).

These buttons are used to adjust the current storage set point of
the domestic hot water temperature (only for [4-03]=4).

The buttons are not used when the domestic hot water tank is
not installed.

34.

QUIET MODE BUTTON 

s

This button enables or disables quiet mode.

If the controller is set in permission level 2 or 3 (refer to 

"Field

settings" on page 13

), the quiet mode button will not be

operable.

35.

BIVALENT FUNCTION ACTIVE 

R

This icon indicates that the bivalent function permission signal is
active.

4.4.

Setting up the controller

After initial installation, the user can set the clock and day of the
week.

The controller is equipped with a schedule timer that enables the user
to schedule operations. Setting the clock and day of the week is
required to be able to use the schedule timer.

Setting the clock

1

Hold down the 

pr

 button for 5 seconds.

The clock read-out and the day of week indicator start flashing.

2

Use the 

pi

 and 

pj

 buttons to adjust the clock.

Each time the 

pi

 or 

pj

 button is pressed, the time will

increase/decrease by 1 minute. Keeping the 

pi

 or 

pj

button pressed will increase/decrease the time by 10 minutes.

3

Use the 

bi

 or 

bj

 button to adjust the day of the week.

Each time the 

bi

 or 

bj

 button is pressed the next or

previous day is displayed.

4

Press the 

<

 button to confirm the current set time and day of the

week.

To leave this procedure without saving, press the 

pr

 button.

If no button is pressed for 5 minutes the clock and day of the
week will return to their previous setting.

Setting the schedule timer

To set the schedule timer, refer to chapter 

"Programming and

consulting the schedule timer" on page 9

.

INFORMATION

Remark that pushing the 

y

 button has no influence

on the domestic water heating. Domestic water
heating is only switched on or off by means of the

v

 button.

NOTICE

The setting [4-03] shall not be modified. The installer
selected the proper setting for your application.

INFORMATION

The status of this setting is only mentioned to indicate
which settings and functions are applicable for your
application.

INFORMATION

The clock needs to be set manually. Adjust the setting
when switching from summertime to wintertime and vice
versa.

Summary of Contents for EKCBH008BBV3

Page 1: ...OPERATION MANUAL EKCBX008BBV3 EKCBH008BBV3 Unit for air to water heat pump system ...

Page 2: ... manual specified for a certain product or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance instructions Instruction manual specified for a certain product or application which explains if relevant how to install configure operate and or maintain the product or appl...

Page 3: ...er Refer to the operation manual of the indoor unit and to the installation manual of the digital I O PCB for more information Refer to the wiring diagram or connection diagram for connecting this PCB to the unit Bottom plate heater EKBPHT refer to the installation manual option Remote thermostat kit option An optional room thermostat EKRTW EKRTWA or EKRTR can be connected to the indoor unit Refer...

Page 4: ...t tap be turned on for several minutes at a sink basin or bath but not at a dishwasher clothes washer or other appliance During this procedure there must be no smoking open flame or any electrical appliance operating nearby If hydrogen is discharged through the tap it will probably make a sound as of air escaping 4 2 Operating the digital controller Operating the unit comes down to operating the di...

Page 5: ...9 OFF ICON x This icon indicates that the OFF action is selected when programming the schedule timer 10 INSPECTION REQUIRED k and l These icons indicate that inspection is required on the installation Consult your dealer 11 SET TEMPERATURE DISPLAY 9 The display shows the current space heating cooling set temperature of the installation 12 SETTING Not used For installation purposes only 13 NOT AVAI...

Page 6: ...ting the clock 33 DOMESTIC HOT WATER TEMPERATURE ADJUST BUTTONS wbi and wbj These buttons are used to adjust the current set point of the domestic hot water temperature only for 4 03 0 1 2 or 3 These buttons are used to adjust the current storage set point of the domestic hot water temperature only for 4 03 4 The buttons are not used when the domestic hot water tank is not installed 34 QUIET MODE ...

Page 7: ...e unit will immediately heat up the domestic water tank untill domestic hot water storage set point upon user request 2 Reheat Scheduled The unit will heat up the domestic water tank starting from a scheduled time and untill the reheat set point is reached Preferally this is done during the time of day when space heating demand is lowest Continuous The unit will continuously heat up the domestic w...

Page 8: ...disappears from the display Selecting powerful domestic water heating operation 1 Press v for 5 seconds to activate powerful domestic water heating operation Icons w and m start flashing Powerful domestic water heating is deactivated automatically when the set point for the domestic hot water is reached Selecting quiet mode operation s 1 Use the s button to activate quiet mode operation s Icon s ap...

Page 9: ... hot water temperature INFORMATION Only use the pr button to enable or disable the schedule timer The schedule timer overrules the y button The y button only overrules the schedule timer until the next programmed action If the auto restart function is disabled the schedule timer will not be activated when power returns to the unit after a power supply failure Press the pr button to enable the sche...

Page 10: ...he schedule timer remind Familiarise yourself with the icons and the buttons You will need them when programming Refer to Name and function of buttons and icons on page 4 Fill out the form at the very end of this manual This form can help you define the required actions for each day Keep in mind that In the space heating and domestic water heating program 4 actions can be programmed per weekday The...

Page 11: ...e 8 Use the button to select the action number you would like to program or to modify 9 Use the ba button to select For space heating x switch heating and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation For domestic water heating use the ba button to enable or disable the x action 10 Use the pi and pj buttons to set the corre...

Page 12: ...on time 8 Use the ba button to select For space cooling x switch cooling and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation For quiet mode and booster heater mode use the ba button to enable or disable the x action 9 Repeat steps 6 to 8 to program the other actions of the selected mode When all actions have been programmed m...

Page 13: ... the next day e g copy all programmed actions from 1 to 2 To copy programmed actions to the next day proceed as follows 1 Press the button The actual mode is blinking 2 Use the pi and pj buttons to select the mode you want to program The selected mode is blinking You can leave programming by pressing the pr button 3 Press the button to confirm the selected mode The actual day is blinking 4 Select t...

Page 14: ...LD SET MODE The icon 3 will be displayed The current selected field setting code is indicated 2 with the set value displayed to the right 1 2 Press the bgi button to select the appropriate field setting first code 3 Press the bgj button to select the appropriate field setting second code 4 Press the pfi button and pfj button to change the set value of the select field setting 5 Save the new value by pr...

Page 15: ...perature Lo_A Note that the Lo_Ti value should be higher than Hi_Ti as for low outdoor temperatures i e Lo_A warmer water is required 1 03 Set point at high ambient temperature Hi_Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi_A Note that the Hi_Ti value should be lower than Lo_Ti as for warmer outdoor temperatures i e Hi...

Page 16: ... Scheduled domestic hot water storage The storage set point can be accessed directly using the wi and wj buttons 6 03 Scheduled storage defines whether the scheduled domestic water heating storage during night is enabled 1 or not 0 6 04 Scheduled storage start time time of the night at which the domestic water should be heated CAUTION The disinfection function field settings must be configured by the...

Page 17: ...estic hot water user interface set point 9 Heating and cooling set point ranges The purpose of this field setting is to prevent the user from selecting a wrong i e too hot or too cold leaving water temperature Thereto the heating temperature set point range and the cooling temperature set point range available to the user can be configured 9 00 Heating set point upper limit maximum leaving water tem...

Page 18: ...ld settings of the weather dependent set point 1 E Unit information readout E 00 Readout of the software version example 23 E 01 Readout of the EEPROM version example 23 E 02 Readout of the unit model identification example 11 E 03 Readout of the liquid refrigerant temperature E 04 Readout of the inlet water temperature INFORMATION Remark that the b icon will be flashing during setback operation The...

Page 19: ...heating off temperature 00 Installation related setting 01 Installation related setting 02 Space heating off temperature 25 14 25 1 C 03 Installation related setting 04 Not applicable Do not change the default value 05 Not applicable Do not change the default value 06 Installation related setting 07 Installation related setting 5 Installation related setting 00 Installation related setting 01 Inst...

Page 20: ...elated setting 05 Not applicable Do not change the default setting d Local shift value weather dependent 00 Installation related setting 01 Installation related setting 02 Installation related setting 03 Local shift value weather dependent 0 OFF 0 1 2 3 4 1 04 Not applicable Do not change the default value 05 Installation related setting 06 Not applicable Do not change the default value E Unit inf...

Page 21: ...lified installer in accordance with relevant local and national legislation Units must be treated at a specialized treatment facility for re use recycling and recovery By ensuring this product is disposed off correctly you will help to prevent potential negative consequences for the environment and human health Please contact the installer or local authority for more information DANGER Do not touch...

Page 22: ...NOTES NOTES ...

Page 23: ......

Page 24: ...Copyright 2010 Daikin 4PW67442 1A 12 2010 ...

Reviews: