background image

1

Gateway

Installation manual

READ THIS MANUAL ATTENTIVELY BEFORE
STARTING UP THE UNIT. DO NOT THROW IT AWAY.
KEEP IT IN YOUR FILES FOR FUTURE REFERENCE.

IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO EQUIPMENT. BE SURE ONLY TO
USE ACCESSORIES MADE BY DAIKIN THAT ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.

IF UNSURE OF INSTALLATION PROCEDURES OR
USE, ALWAYS CONTACT YOUR DAIKIN DEALER FOR
ADVICE AND INFORMATION.

I

NTRODUCTION

Thank you for purchasing the Gateway EKBMSMBA or
EKBMSBNA Kit. This Gateway will enable you to communicate
with your chiller or chillers through a Building Management
System (BMS) or other supervisory system. More specifically, it
functions as a translator between the BMS or supervisory system
and the address cards of the actual chiller or multiple chillers.

As such, the Gateway ensures the connection of all address cards
— and thus also of the chillers — with systems that can
communicate in Modbus or BACnet protocol.

Y

OUR

 

GATEWAY

 

KIT

The kit you have just purchased consists of:

1 Gateway

1 PC diskette with an MS-DOS-formatted program for the initial
configuration of the Gateway

a cable terminal (resistor)

G

ENERAL

 

OVERVIEW

 

OF

 

THE

 

SYSTEM

Different parts of the communication network

The communication network consists of two major players:

The Building Management System or supervisory system.

The chiller or multiple chillers.

The BMS or other supervisory system is able to communicate with
the chillers through two communication devices:

The Gateway, a separate device that functions as a translator
between the Modbus/BACnet signals of the BMS or
supervisory system and the protocol used by the chiller’s
address card.

The address card, a card placed on each PCB of the chiller or
a module placed inside the switchbox, depending on the range
of the chiller. It identifies the chiller. The Gateway can
communicate with up to 16 address cards using the Modbus-
Jbus protocol or up to 8 address cards using the BACnet
protocol. Mind that each PCB needs one address card!
(Refer to figure 1.)

D

ESCRIPTION

 

OF

 

THE

 

GATEWAY

Technical data

Intel 8032 microprocessor, 12 MHz

240Vac factory standard power supply (can be changed into
24Vac or 120Vac)

resident program, EPROM, 64 KB

A front view: Keys and LED’s

Key

Purpose

print out

No function

reset

Press this key to reset the Gateway. It will restart the internal
configuration and external inquiry process of the address cards

LED

Colour

Indication

line

yellow

Power supply on

alarm 1

red

Error in the configuration stored in the buffered RAM

alarm 2

red

Malfunction in the communication between thegateway and the
address card, probably due to an inconsistency with the initial
configuration

rx

green

Communication OK (blinking)

tx

green

Communication OK (blinking)

A rear view: Connectors

The rear panel of the gateway has the following series of
connectors:

Connector name

Connects to…

Type

modem

BMS/supervisory system with RS-232 standard

9 standard way male

RS-422/485

BMS/supervisory system with RS-485 standard

9 standard way female

config.

Configuration PC

9 standard way male

Carel Net.

Address cards with RS-485 standard

9 standard way female

fuse

line

print out

alarm 1alarm 2

rx

tx

reset

Gateway

config.

Carel Net.

relay

fuse

cod.

modem

rs422/485

EKBMSMBA
EKBMSBNA

Summary of Contents for EKBMSMBA

Page 1: ...INSTALLATION MANUAL Gateway EKBMSMBA EKBMSBNA ...

Page 2: ...1 Serial module µchiller compact line print out ala rm 1 ala rm 2 rx tx re set Gateway BMS ...

Page 3: ...communication devices The Gateway a separate device that functions as a translator between the Modbus BACnet signals of the BMS or supervisory system and the protocol used by the chiller s address card The address card a card placed on each PCB of the chiller or a module placed inside the switchbox depending on the range of the chiller It identifies the chiller The Gateway can communicate with up ...

Page 4: ...ire system could be damaged by the erroneous connection of a single wire Preferably insert the cables into the connectors with the Gateway switched off During the configuration phase strictly follow the instructions on the use of the relevant program Before installing the Gateway make sure you have installed the address cards correctly Follow the instructions in the installation manuals of the add...

Page 5: ...emale connector Make the connections as listed Supervisory system Gateway connector labelled modem 25 pole female 9 pole female 2 TX RX 2 3 RX RX 3 7 GND GND 5 Connections to make for a cable with two 9 pole female connectors Make the connections as listed Supervisory system Gateway connector labelled modem 9 pole female 9 pole female 3 TX RX 2 2 RX TX 3 5 GND GND 5 In any case refer to the specif...

Page 6: ...le shows the position of the jumper and the possibility in BACnet and Modbus Jbus Jumper Modbus BACnet C in 1 2 Yes Yes SOFTWARE CONFIGURATION MS DOS PROGRAM Installation of the configuration software for the Gateway System requirements for the PC to configure the Gateway 3 0 or higher DOS operating system RS 232 serial port Cable requirements for the PC to configure the Gateway cable termination ...

Page 7: ...a rdbaccnf enter digitise for Modbus Jbus a readmb0 enter The PC screen will display the configuration present in the Gateway with the parameter relevant to the software version If the Gateway is not connected or does not answer following message will be displayed ERROR READING GATEWAY CONFIGURATION If so check the cable connection the Gateway power supply yellow LED ON signalling LED state com ne...

Page 8: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWE08535 1 ...