4 Configuration
Installation manual
14
EHBH/X04~16CA
Daikin Altherma - Low Temperature Split
4P313771-1C – 2012.11
Digital I/O PCB
#
Code
Description
[A.2.2.6.1]
[C-02]
External backup heat source:
▪ 0 (No): None
▪ 1 (Bivalent): Gas, oil boiler
▪ 2: N/A
▪ 3: N/A
[A.2.2.6.2]
[D-07]
Solar pump station kit:
▪ 0 (No): NOT installed
▪ 1 (Yes): Installed
[A.2.2.6.3]
[C-09]
Alarm output on optional EKRP1HB
PCB:
▪ 0 (Normally open): The alarm output
will be powered when an alarm
occurs.
▪ 1 (Normally closed): The alarm
output will NOT be powered when an
alarm occurs. This installer setting
allows distinction between detection
of an alarm and detection of a power
failure to the unit.
See also table below (Alarm output
logic).
[A.2.2.6.4]
[F-04]
Bottom plate heater
▪ 0 (No): NOT installed
▪ 1 (Yes): Installed
Alarm output logic
[C-09]
Alarm
No alarm
No power
supply to unit
0 (default)
Closed output
Open output
Open output
1
Open output
Closed output
Demand PCB
#
Code
Description
[A.2.2.7]
[D-04]
Demand PCB
Only applicable for EHBH/X04+08 and
EHVH/X04+08. Indicates if the optional
demand PCB is installed.
▪ 0 (No): NOT installed
▪ 1 (Yes): Installed
Energy metering
#
Code
Description
[A.2.2.8]
[D-08]
Optional external kWh meter 1:
▪ 0 (No): NOT installed
▪ 1: Installed (0.1 pulse/kWh)
▪ 2: Installed (1 pulse/kWh)
▪ 3: Installed (10 pulse/kWh)
▪ 4: Installed (100 pulse/kWh)
▪ 5: Installed (1000 pulse/kWh)
[A.2.2.9]
[D-09]
Optional external kWh meter 2:
▪ 0 (No): NOT installed
▪ 1: Installed (0.1 pulse/kWh)
▪ 2: Installed (1 pulse/kWh)
▪ 3: Installed (10 pulse/kWh)
▪ 4: Installed (100 pulse/kWh)
▪ 5: Installed (1000 pulse/kWh)
4.2.4
Quick wizard: Capacities (energy
metering)
#
Code
Description
[A.2.3.1]
[6-02]
Booster heater capacity [kW]
[A.2.3.6]
[6-07]
Bottom plate heater capacity [W]
4.2.5
Space heating/cooling control
Leaving water temperature: Main zone
#
Code
Description
[A.3.1.1.1]
N/A
Set point mode:
▪ 0 (Absolute): Absolute
▪ 1
(Weather
dep.):
Weather
‑
dependent
▪ 2 (Abs + scheduled): Absolute +
scheduled (only for leaving water
temperature control)
▪ 3
(WD
+
scheduled):
Weather
‑
dependent + scheduled
(only for leaving water temperature
control)
[A.3.1.1.3]
[1-00]
[1-01]
[1-02]
[1-03]
Weather
‑
dependent curve (heating):
[1-03]
[1-02]
Ta
Tt
[1-00]
[1-01]
▪ T
t
: Target leaving water temperature
(main)
▪ T
a
: Outdoor temperature
[A.3.1.1.4]
[1-06]
[1-07]
[1
‑
08]
[1-09]
Weather
‑
dependent curve (cooling):
[1-09]
[1-08]
Ta
Tt
[1-06]
[1-07]
▪ T
t
: Target leaving water temperature
(main)
▪ T
a
: Outdoor temperature
Leaving water temperature: Additional zone
#
Code
Description
[A.3.1.2.1]
N/A
Set point mode:
▪ 0 (Absolute): Absolute
▪ 1
(Weather
dep.):
Weather
‑
dependent
▪ 2 (Abs + scheduled): Absolute +
scheduled (only for leaving water
temperature control)
▪ 3
(WD
+
scheduled):
Weather
‑
dependent + scheduled
(only for leaving water temperature
control)