8.2
Overall Wiring Diagram
8.3
Installation of the Breaker
In order to prevent power-supply-related accidents, be sure to use a no-fuse breaker conforming to
EN60947-2 in the power supply connection line. The rated capacity of the breaker should be as indicated in
the table below.
EHU15R07 : 10A
EHU15R10 : 10A
EHU30R07 : 15A
There are no inrush currents with EcoRich R.
Input power supply
3~ 200 -220 V 50/60 Hz
Control power supply input
1 ~ 200 -220 V 50/60 Hz
*On
ly when the “S: With separated
power supplies for power and
control lines” option is selected
(Power ON : Normal status)
*Only when communications option
selected
Communication port for
maintenance (Hybrid-Win
connection port)
Digital output
or
Ready to run
Positive common
Negative common
External power supply (DC+24V)
Max. current 50 mA
Digital input
Start/stop signal
Control/communications
line ground
or
Positive common
RS422 /RS485
communications
Located on the controller
’
s main power supply terminal block
Located on the
controller’s
signal line terminal block
Alarm contact output
Switching capacity 10mA to 1 A (DC30V max.)
RS232C
communications
power supply line ground
Analog input/output
function
Negative common
External power supply (DC+24V)
Input current 5 mA (when DC24V applied)
*Only when analog communications
option selected