background image

E(D/B)(H/L)Q011~016BB

Unit and options for air to water heat pump system

4PW67905-1A – 2013.02

Operation manual

8

Selecting weather dependent set point operation

1

Press the 

ba

 button to select weather dependent set point

operation.

Icon 

a

 appears on the display as well as the calculated water

temperature set point based on the outdoor temperature.

2

Use the 

bi

 or 

bj

 button to display the actual shift value

and subsequently, to set the correct value.

The shift value only appears on the display after pressing one of
the buttons 

bi

 or 

bj

. If no button is pressed for 5

seconds, the shift value will automatically disappear from the
display again.
Range for the shift value: –5°C to +5°C

Displaying actual temperatures

1

Push the 

ba

 button for 5 seconds.

The 

b

 icon and the entering water temperature are displayed.

The icons 

l

 and 

=

 are flashing.

2

Use the 

pi

 and 

pj

 buttons to display:

If no button is pressed for 5 seconds, the controller leaves the
display mode.

Schedule timer operation

In schedule timer operation, the installation is controlled by the
schedule timer. The actions programmed in the schedule timer will be
executed automatically.

The schedule timer always follows the last command until a new
command is given. This means that the user can temporarily overrule
the last executed programmed command by manual operation (Refer
to 

"Manual operation" on page 7

). The schedule timer will regain

control over the installation as soon as the next programmed
command of the schedule timer occurs.

The schedule timer is enabled (

p

 icon displayed) or disabled (

p

 icon

not displayed), by pressing the 

pr

 button.

To set up the SCHEDULE TIMER refer to chapter 

"4.7. Programming

and consulting the schedule timer" on page 9

.

What can the schedule timer do?

The schedule timer allows the programming of:

1.

Space heating (refer to 

"Programming space heating or

domestic water heating" on page 10

)

Switch on the desired mode at a scheduled time, in combination
with a set point (weather dependent or manually set). 
Four actions per weekday can be programmed, totalling
28 actions.

2.

Space cooling (refer to 

"Programming space cooling, quiet

mode, or booster heater mode" on page 11

).

Switch on the desired mode at a scheduled time, in combination
with a set point (weather dependent or manually set). Four
actions can be programmed. These actions are repeated daily.

3.

Quiet mode (refer to 

"Programming space cooling, quiet mode,

or booster heater mode" on page 11

)

Switch the mode on or off at a scheduled time. Four actions can
be programmed per mode. These actions are repeated daily.

4.

Domestic water heating (refer to 

"Programming space heating or

domestic water heating" on page 10

)

[4-03]=0, 1, 2, or 3

Switch the mode on or off at a scheduled time. Four actions per
weekday can be programmed, totalling 28 actions.

[4-03]=4 or 5

Switch the mode on or off at a scheduled time. The switch set to
on means enabeling the programmed storage and reheat
operation.

Flashing icon(s)

Meaning

h

 or 

c

The entering water temperature

h

 or 

c

 and 

é

The outgoing water temperature after plate heat 
exchanger

h

 or 

c

 and 

)

The outgoing water temperature after backup 
heater

ç

The liquid refrigerant temperature

u

The outdoor temperature

w

The domestic hot water temperature

INFORMATION

Only use the 

pr

 button to enable or disable the

schedule timer. The schedule timer overrules the 

y

button. The 

y

 button only overrules the schedule

timer until the next programmed action.

If the auto restart function is disabled, the schedule
timer will not be activated when power returns to the
unit after a power supply failure. Press the 

pr

 button

to enable the schedule timer again.

When power returns after a power supply failure, the
auto restart function reapplies the user interface
settings at the time of the power supply failure.
It is therefore recommended to leave the auto restart
function enabled.

The programmed schedule is time driven. Therefore, it
is essential to set the clock and the day of the week
correctly. Refer to 

"Setting the clock" on page 5

.

Manually adjust the clock for summertime and
wintertime. Refer to 

"Setting the clock" on page 5

.

A power failure exceeding 2 hours will reset the clock
and the day of the week. The schedule timer will
continue operation, but with a disordered clock. Refer
to 

"Setting the clock" on page 5

 to adjust the clock and

the day of the week.

The actions programmed in the schedule timer will not
be lost after a power failure so that reprogramming the
schedule timer is not required.

INFORMATION

When the unit is connected to an external room
thermostat, the schedule timer for space heating and
space cooling is overruled by the external room
thermostat.

Summary of Contents for EBHQ011BB6V3

Page 1: ...BB6W1 EDLQ011BB6V3 EDLQ014BB6V3 EDLQ016BB6V3 EDLQ011BB6W1 EDLQ014BB6W1 EDLQ016BB6W1 EBHQ011BB6V3 EBHQ014BB6V3 EBHQ016BB6V3 EBHQ011BB6W1 EBHQ014BB6W1 EBHQ016BB6W1 EBLQ011BB6V3 EBLQ014BB6V3 EBLQ016BB6V3 EBLQ011BB6W1 EBLQ014BB6W1 EBLQ016BB6W1 Unit and options for air to water heat pump system ...

Page 2: ...ified according to their severity and probability of occurrence Some types of danger are represented by special symbols 1 2 Meaning of used terms Installation manual Instruction manual specified for a certain product or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintena...

Page 3: ...er EKHTS in 2 different sizes 200 and 260 litre Solar kit for domestic hot water tank option For information concerning the EKSOLHW solar kit refer to the installation manual of that kit Room thermostat kit option An optional room thermostat EKRTW EKRTWA or EKRTR can be connected to the unit Refer to the operation manual of the room thermostat for more information 3 2 Scope of this manual This man...

Page 4: ...To dissipate this gas safely it is recommended that a hot tap be turned on for several minutes at a sink basin or bath but not at a dishwasher clothes washer or other appliance During this procedure there must be no smoking open flame or any electrical appliance operating nearby If hydrogen is discharged through the tap it will probably make a sound as of air escaping 4 2 Operating the digital cont...

Page 5: ...ler 11 SET TEMPERATURE DISPLAY 9 The display shows the current space heating cooling set temperature of the installation 12 SETTING Not used For installation purposes only 13 NOT AVAILABLE n This icon is displayed whenever a non installed option is addressed or a function is not available 14 DEFROST STARTUP MODE ICON d This icon indicates that the defrost startup mode is active 15 COMPRESSOR ICON ...

Page 6: ... storage set point of the domestic hot water temperature only for 4 03 4 or 5 The buttons are not used when the domestic hot water tank is not installed 34 QUIET MODE BUTTON s This button enables or disables quiet mode If the controller is set in permission level 2 or 3 refer to 5 Field settings on page 13 the quiet mode button will not be operable 35 BIVALENT FUNCTION OR EXTERNAL BACKUP HEATER AC...

Page 7: ...nt upon user request 2 Reheat Scheduled The unit will heat up the domestic water tank starting from a scheduled time and untill the reheat set point is reached Preferally this is done during the time of day when space heating demand is lowest Continuous The unit will continuously heat up the domestic water tank untill the reheat set point is reached In this case a balance with the space heating de...

Page 8: ...The actual temperature set point only appears on the display after pressing one of the buttons wi or wj If no button is pressed for 5 seconds the temperature set point will automatically disappear from the display again Temperature range for domestic water heating For EKHW only 30 C to 78 C For EKHTS only 30 C to 60 C 3 Press the v button to deactivate domestic water heating w Icon w disappears fr...

Page 9: ...on with a set point weather dependent or manually set Four actions can be programmed These actions are repeated daily 3 Quiet mode refer to Programming space cooling quiet mode or booster heater mode on page 11 Switch the mode on or off at a scheduled time Four actions can be programmed per mode These actions are repeated daily 4 Domestic water heating refer to Programming space heating or domesti...

Page 10: ...ot a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day and at the same time only the action with the highest action number will be executed You can always alter add or remove the programmed actions later INFORMATION The programmed actions are not stored according to their timing but according to the time of programming This m...

Page 11: ...he programming mode 8 Use the button to select the action number you would like to program or to modify 9 Use the ba button to select For space heating x switch heating and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation For domestic water heating use the ba button to enable or disable the x action 10 Use the pi and pj button...

Page 12: ...o select For space cooling x switch cooling and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation For quiet mode and booster heater mode 1 use the ba button to enable or disable the x action 9 Repeat steps 6 to 8 to program the other actions of the selected mode When all actions have been programmed make sure that the display s...

Page 13: ...utton The actual mode is blinking 2 Use the pi and pj buttons to select the mode you want to program The selected mode is blinking You can leave programming by pressing the pr button 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to copy to the next day by means of the pi and pj buttons The selected day is blinking You can return to step 2...

Page 14: ...t step 2 through 4 to change other field settings as required 7 When finished press the z button to exit FIELD SET MODE Detailed description 0 User permission level If required certain user interface buttons can be made unavailable for the user Three permission levels are defined see the table below Switching between level 1 and level 2 3 is done by simultaneously pressing buttons pfi and pfj immedia...

Page 15: ... Hi2_Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi2_A Note that the Hi2_Ti value should be lower than Lo2_Ti as for warmer outdoor temperatures i e Hi2_A colder water is required Tt Target water temperature TA Ambient outdoor temperature Shift value Shift value 2 Disinfection function Applies only to installations with a...

Page 16: ...steresis Example 1 Scheduled storage 6 03 1 scheduled reheat 6 05 1 disinfection function 2 01 1 activated A Scheduled storage operation activated at 6 04 heat up domestic hot water untill domestic hot water user interface set point TDHW e g 55 C is reached B Scheduled reheat operation activated at 6 06 heat up domestic hot water untill domestic hot water reheat set point 6 07 e g 45 C is reached ...

Page 17: ...vating automatic storage during night default setting If it seems that the domestic hot water night storage operation is not sufficient for your needs an additional scheduled reheat during daytime can be set NOTICE The setting 4 03 shall not be modified The installer selected the proper setting for your application INFORMATION The status of this setting is only mentioned to indicate which settings a...

Page 18: ...efer to the installation manual of that kit d Local shift value weather dependent Local shift value weather dependent The local shift value weather dependent field setting is only relevant in case weather dependent set point see field setting 1 Weather dependent set point on page 14 is selected d 03 Local shift value weather dependent determines the shift value of the weather dependent set point aro...

Page 19: ... Fri Mon Sun All 01 Status 1 ON 0 1 02 Start time 23 00 0 00 23 00 1 00 hour 03 Set point only in combination with domestic hot water tank without electrical booster heater EKHTS 60 fixed 5 C 03 Set point only in combination with domestic hot water tank with built in electrical booster heater EKHW 70 55 80 5 C 04 Interval only in combination with domestic hot water tank without electrical booster h...

Page 20: ...stallation related setting 9 Heating and cooling set point ranges 00 Heating set point upper limit 55 37 55 1 C 01 Heating set point lower limit 25 15 37 1 C 02 Cooling set point upper limit 22 18 22 1 C 03 Cooling set point lower limit 5 5 18 1 C 04 Installation related setting Automatic set back function 05 Set back operation 0 OFF 0 1 1 06 Set back operation start time 23 00 0 00 23 00 1 00 hou...

Page 21: ...6 Not applicable Do not change the default value E Unit information readout 00 Software version Read only 01 EEPROM version Read only 02 Unit model identification Do not change the default value depending on model 03 Liquid refrigerant temperature Read only 1 C 04 Inlet water temperature Read only 1 C F Installation related setting 00 Installation related setting 01 Installation related setting 02 ...

Page 22: ... avoid injury give the piping time to return to normal temperature or be sure to wear proper gloves Do not touch any switch with wet fingers Touching a switch with wet fingers can cause electrical shock WARNING Do not touch the refrigerant pipes during and immediately after operation as the refrigerant pipes may be hot or cold depending on the condition of the refrigerant flowing through the refriger...

Page 23: ...s shall not be mixed with unsorted household waste Do not try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil and other parts must be done by a qualified installer in accordance with the applicable legislation Units must be treated at a specialized treatment facility for re use recycling and recovery By ensuring this product is disposed off correct...

Page 24: ......

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...4PW67905 1A 2013 02 Copyright 2011 Daikin 4PW67905 1 A 0000000T ...

Reviews: