Belt Tensioning Instructions
Tensioning Forces
Belt Section
Force required to deflect belt 16mm per metre of span
Small Pulley Diameter
Kilogram Force
SPZ
56 - 95 mm
1.3 - 2.0 kg
100 - 140 mm
2.0 - 2.5 kg
SPA
80 - 132 mm
2.5 - 3.6 kg
140 - 200 mm
3.6 - 4.6 kg
SPB
112 - 224 mm
4.6 - 6.6 kg
236 - 315 mm
6.6 - 8.7 kg
SPC
224 - 355 mm
8.7 - 11.7 kg
375 - 560 mm
11.7 - 15.3 kg
Belt Tensioning Procedure Using a Belt Tension Indicator
- Calculate the deflection distance in millimetres on a basis of 16mm per metre of
centre distance.
- Set the lower marker ring at the deflection distance required in millimetres (mm) on
the lower scale.
- Set the upper marker ring against the bottom edge of the tube.