SiAU18-715
List of Malfunction Code
Troubleshooting
319
3.
List of Malfunction Code
9
: Blink
8
: ON
7
: OFF
Malfunction
code
Malfunction contents
Page Referred
RA Indoor
Unit
SkyAir
Indoor Unit
BP Unit
Outdoor
Unit
Indoor
Unit
A0
Error of external protection device
—
—
—
—
A1
PC board defect, E
2
PROM defect
—
—
A3
Malfunction of drain level control system (33H)
—
—
—
A5
Freeze-up protection or high pressure control
—
—
—
A6
Fan motor (MF) lock, overload
—
—
A7
Malfunction of swing flap motor (MA)
—
—
—
A9
Malfunction of electronic expansion valve (20E)
—
—
—
AF
Drain pump error
—
—
—
AJ
Malfunction of capacity setting
—
—
—
C4
Malfunction of thermistor (R2T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
—
—
C5
Malfunction of thermistor (R3T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
—
—
—
C7
Shutter drive motor / shutter limit switch abnormality
—
—
—
—
C9
Malfunction of thermistor (R1T) for air inlet (loose
connection, disconnection, short circuit, failure)
—
—
CA
Malfunction of thermistor for air outlet (loose
connection, disconnection, short circuit, failure)
—
—
—
—
CJ
Malfunction of thermostat sensor in remote controller
—
—
—
Outdoor
Unit
E1
PC board defect, E
2
PROM defect
—
—
—
E2
Faulty BP unit PCB
—
—
—
E3
Actuation of high pressure switch
—
—
—
E4
Actuation of low pressure switch
—
—
—
E5
Compressor motor lock
—
—
—
E6
Standard compressor lock or over current
—
—
—
—
E7
Malfunction of outdoor unit fan motor
—
—
—
E9
Malfunction of moving part of electronic expansion
valve (Y1E~3E)
—
—
—
F3
Abnormal discharge pipe temperature
—
—
—
F6
Refrigerant overcharged
—
—
—
H3
Malfunction of high pressure switch
—
—
—
—
H4
Actuation of low pressure switch
—
—
—
—
H7
Abnormal outdoor fan motor signal
—
—
—
—
H9
Malfunction of thermistor (R1T) for outdoor air (loose
connection, disconnection, short circuit, failure)
—
—
—
J0
Faulty BP liquid or gas pipe thermistor
—
—
—
J2
Current sensor malfunction
—
—
—
—
J3
Malfunction of discharge pipe thermistor (R2T) (loose
connection, disconnection, short circuit, failure)
—
—
—
J5
Malfunction of thermistor (R3T, R5T) for suction pipe
(loose connection, disconnection, short circuit,
failure)
—
—
—
J6
Malfunction of thermistor (R4T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
—
—
—
J7
Malfunction of liquid thermistor (R7T)
—
—
—
J8
Malfunction of thermistor for oil equalizing pipe.
(loose connection, disconnection, short circuit,
failure)
—
—
—
—
J9
Malfunction of subcooling heat exchanger thermistor
(R6T)
—
—
—
JA
Malfunction of discharge pipe pressure sensor
—
—
—
JC
Malfunction of suction pipe pressure sensor
—
—
—
L0
Inverter system error
—
—
—
—
Summary of Contents for E Series
Page 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Page 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Page 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Page 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Page 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Page 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Page 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Page 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Page 449: ...SiAU18 715 vi Index ...