Troubleshooting for Outdoor Unit
SiAU18-715
366
Troubleshooting
7.7
Abnormal Discharge Pipe Temperature
Remote
Controller
Display
F3
Applicable
Models
AII outdoor unit models
Method of
Malfunction
Detection
Abnormality is detected according to the temperature detected by the discharge pipe
temperature sensor.
Malfunction
Decision
Conditions
When the discharge pipe temperature rises to an abnormally high level
When the discharge pipe temperature rises suddenly
Supposed
Causes
Faulty discharge pipe temperature sensor
Faulty connection of discharge pipe temperature sensor
Faulty outdoor unit PCB
Troubleshooting
∗
Refer to “Thermistor Resistance / Temperature Characteristics” table on P405.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Pull out the discharge pipe
thermistor from the outdoor
PCB, and then make
measurement of resistance
using a multiple meter.
Discharge pipe
temperature is 120˚C or
higher when the unit stop
by malfunction.
Are the
characteristics
of the discharge pipe
thermistor normal?
(3.5~400K
Ω
)
∗
Replace outdoor unit PC
board (A1P).
(Q0556)
Refrigerant shortage,
compression defect, etc.
Defect of the refrigerant
system.
YES
Replace the discharge
pipe thermistor.
NO
NO
YES
Summary of Contents for E Series
Page 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Page 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Page 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Page 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Page 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Page 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Page 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Page 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Page 449: ...SiAU18 715 vi Index ...