SiAU18-715
Troubleshooting for SkyAir Indoor Unit
Troubleshooting
343
5.10
Malfunction of Suction Air Thermistor
Remote
Controller
Display
C9
Applicable
Models
FFQ, FCQ, FBQ, FHQ
Method of
Malfunction
Detection
Malfunction detection is carried out by temperature detected by suction air temperature sensor.
Malfunction
Decision
Conditions
When the suction air temperature sensor’s thermistor becomes disconnected or shorted while
the unit is running.
Supposed
Causes
Failure of the sensor itself
Broken or disconnected wire
Failure of indoor unit PCB
Failure of connector contact
Troubleshooting
Check No.02
Refer to P.349
Connect correctly.
Suction air temperature
sensor replacement.
If contact is OK,
replace outdoor unit
PCB.
NO
NO
YES
YES
(Q0540)
Disconnect the sunction air
temperature sensor (R1T) from
X19A on the indoor unit PCB
and measure the resistance.
Is the
thermistor normal?
(See note)
Is it normal?
Check contact of connector
+
See
Check No. 02
for “Thermistor temperature and resistance characteristics”.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for E Series
Page 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Page 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Page 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Page 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Page 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Page 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Page 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Page 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Page 449: ...SiAU18 715 vi Index ...