Troubleshooting for Outdoor Unit
Troubleshooting
367
7.8
Refrigerant Overcharged
Remote
Controller
Display
F6
Applicable
Models
All outdoor unit models
Method of
Malfunction
Detection
Excessive charging of refrigerant is detected by using the heat exchanging deicer temperature
during a check operation.
Malfunction
Decision
Conditions
When the amount of refrigerant, which is calculated by using the heat exchanging deicer
temperature during a check run, exceeds the standard.
Supposed
Causes
Refrigerant overcharge
Misalignment of the thermistor for heat exchanger
Defect of the thermistor for heat exchanger
Troubleshooting
∗
Refer to “Thermistor Resistance / Temperature Characteristics” table on P405.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Remove the heat
exchanging deicer
thermister from the outdoor
PCB and measure
resistance with a tester.
Check the mounting
condition of the temperature
sensors of the heat
exchanging deicer
thermistor in the piping.
Are the
above thermistor
installed on pipes
correctly?
Is the
characteristic of the
above thermistor
normal?
Refrigerant overcharged.
(Q0557)
Install thermistor correctly.
NO
Replace thermistor.
NO
YES
YES
Summary of Contents for E Series
Page 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Page 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Page 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Page 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Page 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Page 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Page 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Page 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Page 449: ...SiAU18 715 vi Index ...