CAT 258 • REBEL APPLIED ROOFTOP
Features and Options
Summary
Standard Features
•
Double-wall foam-injected panel with thermal resistance
of R-13
•
Integral thermal break in all walls, doors, floors and roof
panels
•
Low air leakage: <0.5% air leakage at +/- 5 in w.c. of
static pressure; CL6 @ 6 in w.c. per ASHRAE Std 111
•
Pre-paint exterior surfaces withstand a minimum 1000 hr
salt spray test per ASTM B117
•
Access doors are mounted with durable full length
stainless steel piano style hinge.
•
A single, lockable handle and latch mechanism plus door
holders on each access door.
•
Dual refrigeration circuits with fully interlaced evaporator
coils
•
Minimum operating ambient down to 50°F mechanical
cooling
•
A minimum of four stages of compressor capacity control
for stable discharge air temperature and humidity control
•
A minimum of (2) direct-drive ECM supply fans to offer
redundancy, reduced maintenance, and higher efficiency
•
2" MERV 8 filtration with dirty filter monitoring
•
Multi-stage gas heat with 439 stainless steel heat
exchanger
•
Multi-staged electric heat
•
Hot water or steam heat
•
Standard 1 year parts, labor and compressor warranty
•
Standard 10 year gas heat exchanger warranty
•
Separated high and low voltage control panels for safe
access to human control interfaces
•
208V/230V/460V/575V
•
Single point power block connection
•
10 KAIC SCCR
•
Phase voltage monitor
•
MicroTech
®
4 controls
Customizable Features
•
100% or 0–30% outisde air damper or 0-100%
economizer damper
•
Low static exhaust or high static exhaust or return fans
•
Energy efficiency (coil face area, 6 row coils)
•
Modulating hot gas reheat for dehumidification
•
Low ambient mechanical cooling
•
Quiet condensing and compressor sound blankets
•
Speedtrol
®
, modulating head pressure control
•
Outdoor and Fan Airflow Measuring
•
Refrigerant system monitoring (liquid, suction, and
condensing refrigerant pressure/temperature sensors)
•
Modulating gas heat control between 5:1 and 100:1
turndown
•
Modulating hot water and steam control valves
•
ECM supply fan array with backdraft dampers for
redundancy
•
Extended 5 year parts, labor and compressor warranty
•
Extended 20 year heat exchanger warranty
•
2"/4" filter rack with Merv 8 or 13 filters
•
2" Merv 8 pre-filter with 12" rigid cartridge Merv 11, 14,16,
or carbon filters
•
Final filters – 12" rigid cartridge MERV 14, 16, HEPA
•
Non-fused, unit mounted disconnect switch
•
Dual point power for back-up power systems
•
115V service outlet
•
65 KAIC electrical rating
•
Line reactor, power factor correction
•
MicroTech 4 controls with BAS integration and power
measuring