2 .19 Energy Recovery

A. 

The rooftop unit shall be provided with an AHRI 

certified rotary wheel air-to-air heat exchanger in 

a cassette frame complete with seals, drive motor 

and drive belt. The energy recovery wheel shall 

be an integral part of the rooftop unit with unitary 

construction, power supply and controls and does 

not require field assembly. Bolt-on energy recovery 

units that require field assembly and section to 

section gasketing and sealing are not acceptable

B. 

The energy recovery wheels supplied must meet the 

scheduled capacity, and air pressure drop.

C. 

The wheel capacity, air pressure drop and 

effectiveness shall be AHRI certified per AHRI 

Standard 1060. Thermal performance shall be 

certified by the manufacturer in accordance with 

ASHRAE Standard 84, Method of Testing Air-to-Air 

Heat Exchangers and AHRI Standard 1060, Rating 

Air-to-Air Heat Exchangers For Energy Recovery 

Ventilation Equipment. 

D. 

The rooftop unit shall be designed with a track so 

the entire energy recovery wheel cassette can slide 

out from the rooftop unit to facilitate cleaning. 

E. 

The unit shall have 4" Merv 8 filters for the outdoor 

air before the wheel to help keep the wheel clean 

and reduce maintenance. A dirty filter switch and 

alarm shall be provided on the Energy wheel filter 

rack

F. 

The total energy recovery wheel shall have an 

aluminum substrate and a 3 angstrom desicant and 

shall have an adjustible purge for field balancing.

G. 

A VFD shall be provided an modualed for wheel 

capacity and frost prevention control by the unit 

contorller. 

H.  A electric preheat coil with SCR control shall be 

provided and modulated to prevent frost on the 

energy recovery device. Provide sizing equivalent to 

the schedule.

I. 

The rooftop unit with the energy recovery wheel 

shall incorporate the economizer operation. Units 

with economizers and energy recovery wheels shall 

have a bypass damper. When the unit is in the 

economizer mode of operation the energy recovery 

wheel shall stop and the bypass dampers shall be 

opened. The outdoor air shall be drawn through the 

bypass dampers to reduce the pressure drop of the 

outdoor airstream.

2 .20 Discharge and Return Plenum Options

A. 

A supply air discharge plenum shall be provided. 

The plenum section connection shall have a bottom, 

right, left, or top discharge opening consult the 

schedule and drawings for the final orientation.

2 .21 Condensing Section

A. 

All Units shall provide the Energy Efficiency 

specified EER and IEER per the schedule 

equipment or higher.

B. 

Condenser fans shall be direct drive, axial type 

designed for low tip speed and vertical air discharge. 

Fan blades shall be constructed of steel and riveted 

to a steel center hub. Condenser fan motors shall 

be heavy-duty, inherently protected, three-phase, 

non-reversing type with permanently lubricated ball 

bearing and integral rain shield.

C. 

Condenser coils shall be an all aluminum design, 

and mounted on polymer brackets, to minimize 

di-electric corrosion. The aluminum tube shall be a 

micro channel design with high efficiency aluminum 

fins. Fins shall be brazed to the tubing for a direct 

bond. Each condenser coil shall be factory leak 

tested with high-pressure air under water. 

D. 

Condenser coils shall be protected from incidental 

contact to coil fins by a coil guard. Coil guard shall 

be constructed of cross wire welded steel with PVC 

coating

E. 

Head Pressure Control

1. 

Units shall have at least one condenser fan per 

circuit to maintain positive head pressure and an 

ambient temperature based fan cycling control to 

provide mechancial cooling down to 50°F

2. 

Units shall have at least one condenser fan per 

circuit to maintain positive head pressure and 

a pressure transducer feedback per circuit to 

provide mechancial cooling down to 50°F

3. 

Units shall have at least one condenser fan per 

circuit to maintain positive head pressure and a 

VFD on each cirucit to modulate condenser fans 

to provide mechancial cooling down to 25°F

4. 

Units shall have at least one condenser fan per 

circuit to maintain positive head pressure and a 

VFD on each cirucit to modulate condenser fans 

to provide mechancial cooling down to -10°F

5. 

Units shall have at least one condenser fan 

controlled to maintain positive head pressure. 

SpeedTrol condenser fan speed control shall be 

added to the last fan OFF on each refrigeration 

circuit to provide cooling operation to ambient 

temperatures down to 0°F. Fan speed control 

shall be field adjustable. 

F. 

Each unit shall have multiple, heavy-duty scroll 

compressors. Each compressor shall be complete 

with gauge ports, crankcase heater, sight-glass, 

anti-slug protection, motor overload protection and a 

time delay to prevent short cycling and simultaneous 

starting of compressors following a power failure. 

Compressors shall be isolated with resilient rubber 

isolators to decrease noise transmission

Summary of Contents for DPSA

Page 1: ...Catalog 258 Rebel Applied Rooftop Systems Heating and Cooling Models DPSA DFSA 30 to 52 Tons R 410A Refrigerant...

Page 2: ...ir Quality 11 Outside Air Control 11 Filtration 11 Energy Recovery 12 Heating 13 Gas Heat 13 Electric Heat 13 Hot Water and Steam Heat 13 Fans 14 Supply Return and Exhaust Fan Array 14 EC Motor Techno...

Page 3: ...ide EER s over 11 0 and IEER s up to 17 2 Precision heating and cooling temperature and humidity control with modulating technologies that provide superior turndown Airflow measuring Filtration UV lig...

Page 4: ...icient thermal insulation and no exposed insulation for high indoor air quality Low Air Leakage Construction Air leakage occurs as infiltration or exfiltration Infiltration occurs when negative sectio...

Page 5: ...d has flexible filtration options to satisfy indoor air requirements from varying space types Pleated Filter Options MERV 8 or 13 Filtration efficiencies in 2 or 4 filters exceed the AHSRAE 62 minimum...

Page 6: ...to prevent failures and prolong equipment life Making Maintenance Easier Operating expenses go way beyond energy consumption To optimize the lifecycle cost of Rebel Applied rooftops we designed in fe...

Page 7: ...as heat exchanger warranty Separated high and low voltage control panels for safe access to human control interfaces 208V 230V 460V 575V Single point power block connection 10 KAIC SCCR Phase voltage...

Page 8: ...ransfer paths through the panel which prevents energy losses and exterior condensation Through metal provides a path for heat to enter the cabinet and lowers the effective R value of the insulation Fi...

Page 9: ...al conditioning above the building loads is required meaning additional operating load and additional operating expense Figure 6 shows the average annual operating cost to building operators due to th...

Page 10: ...o commission the equipment to provide the dehumidification each application requires No more no less The fully modulating hot gas reheat coil is controlled independent of the compressors to maintain c...

Page 11: ...d draw through filter section and an optional final filter section with dirty filter alarm An optional electronic pressure transducer measures dirty filter status and can be monitored through the unit...

Page 12: ...ls Defrost options for variable speed defrost control and electric preheat defrost 4 MERV 8 high capacity energy recovery filtration for high holding capacity to extend filter life in the outdoor air...

Page 13: ...ronment even during shoulder seasons and in demanding applications such as 100 make up air and VAV systems Solves the mixed air tempering requirements of VAV systems when meeting ASHRAE 62 1 ventilati...

Page 14: ...DC motor with an integral inverter The integral inverter eliminates variable frequency drives VFD saving energy losses and enhancing energy efficiency at part load ECM Fans provide the highest efficie...

Page 15: ...he base of the unit Wiring complies with NEC requirements and all applicable UL standards For ease of use wiring and electrical components are number coded and labeled according to the electrical diag...

Page 16: ...curbs Baserail curb pockets configurability makes direct replacement of multiple manufacturers legacy rooftops Daikin RoofPak and Trane IntelliPak can be replaced directly and others with minimal tra...

Page 17: ...installed ultraviolet lights are available on the downstream side of all cooling coils and above the unit drain pan All ultraviolet lights are pre engineered and factory installed for ease of use and...

Page 18: ...ounted BACnet or LonWorks communication module provides a network interface to the BAS Add optional field configurable I O modules to add additional sensors or points that are not standard on rooftop...

Page 19: ...dehumidification operation Building Pressure Control Units equiped with return or exhaust fans can be configured to control building pressure directly or via several indirect methods like fan trackin...

Page 20: ...1 kW 9 8 kW High Static Return Fans Type Direct dive ECM SWSI Plenum Fan Array Row Columns Qty 1 2 2 Diameter in 18 20 22 25 Motor Range kw hp 1 1 kW 6 0 kW Low Static Propeller Exhaust Type Direct d...

Page 21: ...ze 9 20 24 3 20 x 20 Cartridge Filters Thickness MERV 4 15 12 11 14 16 Carbon Area sqft 38 3 ft Qty Size 9 20 24 3 20 20 Cartridge Final Filters Thickness MERV 12 14 16 Area sqft 35 6 ft Qty Size 9 20...

Page 22: ...575V kW MBH kW MBH kW MBH kW MBH 4 stages SCR 30 102 0 20 62 4 20 62 7 25 170 6 45 153 0 40 124 7 40 125 0 45 60 204 0 55 187 1 55 188 0 75 255 0 75 249 4 75 250 2 70 255 9 90 306 0 90 311 8 90 313 4...

Page 23: ...Efficiency Standard Efficiency Highest Efficiency Condenser Ctrl Fantrol Speedtrol Coil Rows 4 Row 6 Row Compressor Type EER IEER EER IEER 31 Standard Staged 10 8 15 0 11 5 17 1 35 Standard Staged 10...

Page 24: ...0 100 Economizer with Propeller Fans 0 100 Economizer with High Static Exhaust Fans 0 100 Economizer with High Static Return Fans 0 100 Economizer with Energy Recovery Filter 2 Pleated Filter 8 32 2...

Page 25: ...1 2 ECM fan array 2 Merv 8 filters Office 2 50 ton Economizer with return fan Gas heat 2 2 ECM fan array 2 Merv 8 pre filters and 12 MERV 14 cartridge filters Outside Return Air Filter DX Coil Supply...

Page 26: ...Merv 8 filters 100 Outside Air 50 ton unit 100 Outside air damper 100 degree rise furnace 1 2 ECM fan array 2 MERV 8 filters Outside Return Air Filter DX Coil Supply Fan Gas Heat Condensing 81 0 40 0...

Page 27: ...Service Clearance www DaikinApplied com 27 CAT 258 REBEL APPLIED ROOFTOP Service Clearance Figure 24 Rebel Applied Service Clearance Top of unit needs unobstructed clearance...

Page 28: ...ble 9 Roof Curb Variable Dimensions 31 50 Tons A B C D Return End Configuration Out of Air Stream Vestibule AHU Length 8 Condenser Size Standard Return 2 93 48 Section 49 78 Configured 54 High Static...

Page 29: ...ur Daikin sales representative if available clearances do not meet minimum recommendations Operating Range Daikin Rebel Applied rooftop systems are designed to operate over an extensive operating rang...

Page 30: ...beneath the condensing section Apply for vibration isolation curb systems for sound transmission critical applications Account for low frequency duct breakout in system design Route the first 20 ft of...

Page 31: ...cs and connection requirements B Product data 1 Provide literature that indicates dimensions weights capacities ratings and electrical characteristics and connection requirements 2 Provide data on fil...

Page 32: ...shall be double wall with a solid stainless steel liner with a thermal break integral to the panel construction that provides a cleanable interior prevents conductive heat transfer through the panel...

Page 33: ...be lined with a perforated acoustic liner to enhance sound attenuation 2 05 Supply Return and Exhaust Fans A All supply return and exhaust fans shall be configured in an array with a minimum number f...

Page 34: ...re protection and prevent the motor from operation in the event of a loss of phase Motors shall be premium efficiency 3 Exhaust Fan configurations are not allowed as alternate 2 06 Electrical A Unit w...

Page 35: ...m wicking under the drain pan Fiberglass is not allowed 2 09 Corrosion Protection A All Indoor Heating and Cooling coils shall be provided with a corrosion protection coating rated for a minimum of 60...

Page 36: ...acterized Cv ball valves 2 12 Hot Water Heat Coils A A hot water heating coil shall be factory installed in the heat section The rooftop unit shall include a piping vestibule The coil connection shall...

Page 37: ...aft burner The burner shall be controlled for low fire start The burner shall be capable of continuous modulation between 10 and 100 10 1 control of rated capacity G The furnace will be supplied with...

Page 38: ...damper area at 1 differential pressure in according with testing defined in AMCA 500 Control of the dampers shall be by a factory installed direct coupled actuator D Unit shall be provided with an ou...

Page 39: ...t or top discharge opening consult the schedule and drawings for the final orientation 2 21 Condensing Section A All Units shall provide the Energy Efficiency specified EER and IEER per the schedule e...

Page 40: ...e a stand alone DDC controller not dependent on communications with any on site or remote PC or master control panel The microprocessor shall maintain existing set points and operate stand alone if th...

Page 41: ......

Page 42: ...uct Warranty Consult your local Daikin Applied Representative for warranty details To find your local Daikin Applied Representative go to www DaikinApplied com Aftermarket Services To find your local...

Reviews: