background image

iTM plus adaptor

Model

DCM601A72

Installation Manual

01_EN_3P291714-4.indd   1

3/26/2012   5:00:43 PM

Summary of Contents for DCM601A72

Page 1: ...iTM plus adaptor Model DCM601A72 Installation Manual ...

Page 2: ...ful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiv...

Page 3: ...ous injury CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury It may also be used to alert against unsafe practices NOTE Indicates situations that may result in equipment or prop erty damage accidents only WARNING Only qualified personnel must carry out the installation work Consult your Daikin dealer regarding relocation and reinstallat...

Page 4: ...kage c Near machinery emitting electromagnetic waves Electromagnetic waves may disturb the operation of the control system and cause the unit to malfunction d Where flammable gas may leak where there is carbon fiber or ignitable dust suspensions in the air or where volatile flammables such as thinner or gaso line are handled Operating the unit in such conditions can cause a fire e High temperature...

Page 5: ... conceptual connection diagram 16 2 2 2 Requirements that must be met 17 2 2 3 Precautions for using multiple centralized controllers 17 2 3 Connecting contact or pulse input equipment such as electric energy meters 18 2 3 1 Terminals location and conceptual connection diagram 19 2 3 2 Requirements that must be met 19 2 4 Connecting power supply 20 2 4 1 Terminals location and conceptual connectio...

Page 6: ...English 5 Outdoor Unit Address Setup 31 5 1 Procedure 31 6 Quick Operation Guide 32 6 1 Viewing target area and management point information in list format 32 6 2 Viewing target areas and management points 32 6 3 Starting stopping an area or management point 33 ...

Page 7: ...that an appropriate space for installing the iTM plus adaptor is available 1 1 Checking that all accessories are included Based on the following accessory list check that all accessories for the iTM plus adaptor are included Should there be any missing or defective parts contact your dealer Accessories included with iTM plus adaptor A B C D d 2 d 1 a 1 b 1 c 1 A a 1 iTM plus adaptor body 1 pc B b ...

Page 8: ...s on the unit and draw up an effi cient work plan For connection details including the cable type terminal size and wiring precautions refer to 2 Connection 1 3 1 Front face of iTM plus adaptor All the terminals used during installation are located on the front face of the iTM plus adaptor Note that only the power terminals are covered with a terminal cover for safety You can remove this cover by ...

Page 9: ...us adaptor set a unique number between 2 to 8 G TERM The switch used when multiple iTM plus adaptors are connected in parallel for enabling the termination resistor on the furthest iTM plus adaptor from the intelli gent Touch Manager H DIII MASTER The switch used when there are two or more DIII NET centralized controllers such as intelligent Touch Managers are connected for distinguishing between ...

Page 10: ...1 Installation place and mounting direction Note that the iTM plus adaptor must be installed in a place and in a mounting direction as described below Installation place Indoor inside control enclosure which must be lockable or designed to be opened only with a special tool Mounting direction Vertical only 1 4 2 Required space To install the iTM plus adaptor the following space is required Also no...

Page 11: ...91714 4 DCM601A72 iTM plus adaptor 11 English 1 4 3 Environmental conditions The installation environment must meet the following conditions Ambient temperature 14 to 122 F Ambient humidity 85 RH or less without condensation ...

Page 12: ...conditioning equipment 2 4 Connecting power supply Equipment spe cific procedures 2 3 Connecting contact or pulse input equipment such as electric energy meters WARNING Do not turn the power supply on until all connections are made Not doing so may cause an electric shock After completing connections check again that all wires are connected cor rectly before turning on the power supply All field s...

Page 13: ... ADP IF section on the rear face of your intel ligent Touch Manager Note that these terminals have polarity Be sure to connect the positive wire to the terminal and the negative wire to the terminal respectively In addition the intelligent Touch Manager must be connected as a terminal to the wiring Terminals location and conceptual connection diagram A intelligent Touch Manager Rear face B iTM plu...

Page 14: ...ble the termination resistor on the furthest iTM plus adaptor from the intelligent Touch Manager This termination resistor setting is done using the TERM switch located on the front face of the iTM plus adaptor plus ADP ADDRESS switch and TERM switch NOTE If the two LEDs CPU ALIVE and ALARM both light up during power on after installa tion there is a possibility of a problem with the address assig...

Page 15: ...ent Touch Manager can be connected with a maximum of seven iTM plus adaptors you can control a total of 512 groups of air conditioners at a maximum using a single intelligent Touch Manager WARNING Be sure to perform this procedure with the power supply turned off Not doing so may cause an electric shock The maximum length of adhered wiring of high current electrical line of power wires and weak cu...

Page 16: ...t power wires Inadvertently connecting power wires to these terminals results in a failure of the air conditioner or iTM plus adaptor Conceptual connection diagram with air conditioning equipment F2 F1 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 F1 F2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 F1 F2 E F A B C D D D D D A B C D D D D D A Outdoor unit B O...

Page 17: ...ss The total wire length must be limited to 6561 ft except when using a shielded cable whose total wire length must be kept to 4921 ft or less 2 2 3 Precautions for using multiple centralized controllers Equipment that controls multiple air conditioners is referred to as centralized controller DAIKIN s product portfolio includes a wide range of centralized controllers suited to differ ent applicat...

Page 18: ...ralized con trollers that cannot be installed in parallel with iTM plus adaptor CALCULATE UNIT intelligent Processing Unit Parallel Interface Intelligent Touch Controller DIII NET Plus Adapter Residential Central Remote Controller Schedule Timer Wiring Adaptor for Electrical Appendices 1 KRP2 2 3 Connecting contact or pulse input equipment such as elec tric energy meters The iTM plus adaptor can b...

Page 19: ...er of them However you can connect up to two wires simultaneously to each COM terminal Di1 Di2 COM Di3 Di4 COM 2 3 2 Requirements that must be met Cable type CPEV cable Core thickness AWG22 19 Cable length 656 ft or less Pulse width Pulse width 20 to 400 ms Pulse interval 100 ms or more A B A Pulse width 20 to 400 ms B Pulse interval 100 ms or more CAUTION The contact connected to the contact inpu...

Page 20: ...th a protective cover Remove this cover before you start connecting the power supply You can do so by loosening a single screw using a Phil lips screwdriver The terminal cover must be replaced where it was before when you finish connecting the power supply Next connect the power supply to the three terminals L Live N Neutral and ground in the POWER section Be sure to ground the ground terminal Rem...

Page 21: ...upply to the entire system must be installed When using an earth leakage breaker make sure to select one useful for to protection against overcurrent and short circuit When using an earth leakage breaker only for earth device make sure to use a wiring interrupter together The power supply requires earth leakage breaker installation and earth wire connection After installing an earth leakage breake...

Page 22: ...he following two ways Screw mounting to control enclosure DIN rail mounting 3 1 Screw mounting to control enclosure 3 1 1 Dimensions of iTM plus adaptor The figure below shows the dimensions of the iTM plus adaptor 5 7 8 4 23 32 5 11 32 2 11 16 2 21 32 2 1 16 6 5 16 2 13 32 2 13 32 in 1 4 1 4 5 32 5 32 1 4 5 32 1 4 5 1 2 5 32 ...

Page 23: ...trol enclosure using the supplied round head wood screws When done remove the blue protective film from the upper portion of the unit body Mounting to control enclosure 3 2 DIN rail mounting The iTM plus adaptor can be mounted to a 1 3 8 in DIN rail Mounting to DIN rail Do not use screws to secure the iTM plus adaptor onto the DIN rail ...

Page 24: ...hook 1 on the rear face is hooked and push it in direction 3 until the lower hook 2 snaps into the DIN rail When done remove the blue protective film from the upper portion of the unit body 3 3 2 2 1 1 3 2 1 Removal from DIN rail Pull down the lever at the lower portion of the iTM plus adaptor 1 and pull the unit body 2 out toward you 1 1 2 2 ...

Page 25: ...n ager and that both units are powered on Unless both are powered on you cannot perform DIII NET address assignment for your air conditioners For how to assign addresses for Ventilator Heat Reclaim Ventilator equipment and various adapters such as a universal adapter refer to the manual for each product 4 1 Remote controller buttons and areas The names of buttons and areas of a wired remote contro...

Page 26: ...splay Step 1 HH F 2 Using the Temperature Setting buttons change the value shown in the parameter num ber display area to 00 In the address display area the current address setting is displayed This area will show if no address is set Step 2 SETTING GROUP NOTE The parameter number cannot be changed to 00 when the intelligent Touch Manager is not powered on Power on the intelligent Touch Manager an...

Page 27: ...t the address you want to set Step 4 SETTING GROUP 5 Press the Timer ON OFF button to make the GROUP indicator stay lit The DIII NET address has been set Step 5 SETTING GROUP 6 Press the Inspection Test Operation button You are now brought back to the screen shown in Step 6 2 Step 6 1 SETTING GROUP Step 6 2 HH F ...

Page 28: ... The Group No setting menu is displayed Step 2 Test operation Register Service Contract Error record Return Setting Field setting Field setting list Indoor unit Airnet No set Group No setting 1 2 ON OFF NOTE The Group No setting menu is not displayed when the intelligent Touch Manager is not powered on Power on the intelligent Touch Manager and wait for a while before trying to operate the remote ...

Page 29: ...roup No setting Group 5 Using the Up Down buttons select the address you want to set Step 5 Group No Release 1 00 Return Change Group No setting Group 6 Press the Menu Enter button The DIII NET address has been set Step 6 Group No Set 1 03 Return Release Group No setting Group 7 Press the Cancel button three times You are now brought back to the screen shown in Step 7 2 Step 7 1 Group No Set 1 03 ...

Page 30: ...iTM plus adaptor English 4 1 3 Setting an unique address to each unit when power distribution is enabled When power distribution is enabled you need to set a unique address for each unit For how to set an address refer to the commissioning manual ...

Page 31: ...ator LED BS1 BS2 BS3 BS4 BS5 H2P H3P H4P H5P H6P H7P H8P Mode switch Microcomputer operation monitor 1 Press the BS1 button for 5 seconds or more The H1P LED lights up 2 Press the BS2 button 13 times This causes each LED on the printed circuit board to be in the following state which indicates that you are in the address setup mode H1P H2P H3P H4P H5P H6P H7P On Off 3 Press the BS3 button You can ...

Page 32: ...rget area and management point information in list format A B B A Touch the List button B The screen changes to the list view where the name operation mode set tempera ture and fan speed of all areas and indoor units are listed 6 2 Viewing target areas and management points A B A You can check the hierarchy level of the current area or indoor unit B Touch the Down button to go to the area being se...

Page 33: ... On the On Off combo box select Start or Stop to start or stop the area management point respectively The icon is green or red depending on the system setup when the area management point is started operating and gray when stopped C C C When Confirmation Dialog is set to Enabled in the system setup the corresponding message appears Select the Yes button to confirm the Start Stop operation ...

Page 34: ......

Page 35: ......

Page 36: ...3P291714 4 EM11A030 1203 HT ...

Reviews: