Installation Manual 3P291714-1
DCM601A51 intelligent Touch Manager
23
English
2.6.2
Requirements that must be met
•
Cable type: CPEV or FCPEV cable
•
Core thickness: 0.65 - 0.9 mm²
•
Cable length: 50 meters or less
NOTE
Each air conditioner controlled via an iTM plus adaptor is also assigned a DIII address
between “1-00” to “4-15”. From the intelligent Touch Manager, it is recognized as “2:1-
00”, “3:1-02”, or the like, with the DIII-NET port number prefixed.
2.7
Connecting power supply
Connect the intelligent Touch Manager to an AC power supply.
WARNING
The following procedures must be carried out with the power supply shut off. Do
not turn the power supply on until all connections are made. Doing so may cause
an electric shock.
2.7.1
Terminals location and conceptual connection diagram
<Conceptual drawing of power sup-
ply connection>
Connect the power supply to the three terminals, L
(Live), N (Neutral), and ground in the POWER sec
-
tion.
A Earth
B Breaker
C Power supply 100-240VAC
50/60 Hz