Installation Manual 3P291714-1
DCM601A51 intelligent Touch Manager
English
2.6
Connecting iTM plus adaptors
If you have many air conditioners, use iTM plus adaptors to connect them. It is a fact that
the number of indoor groups you can control using a single intelligent Touch Manager is
limited to 64. By using iTM plus adaptors, however, you can connect additional 64 groups
of indoor units per iTM plus adaptor. Moreover, considering that the intelligent Touch Man-
ager can be connected with a maximum of seven iTM plus adaptors, you can control a
total of 512 groups of indoor units at a maximum using a single intelligent Touch Manager.
WARNING
•
Be sure to perform this procedure with the power supply turned off. Doing so
may cause an electric shock.
•
Do not clamp the cables with high-current lines such as a power cable.
2.6.1
Terminals location and conceptual connection diagram
Connect an iTM plus adaptor to the plus ADP IF terminals located on the rear face. Be
sure to connect the positive wire the “+” terminal and the negative wire to the “–” terminal,
respectively, as these terminals have polarity.
<Terminals location and conceptual connection diagram>
A
intelligent Touch Manager (Rear face)
B iTM plus adaptor
C
plus ADP IF (intelligent Touch Manager)
D
plus ADP IF (iTM plus adaptor)
E iTM plus adaptor on which termination resistor must be enabled