![background image](http://html1.mh-extra.com/html/daikin/dcg036xxx1dxxx/dcg036xxx1dxxx_technical-manual_4699391021.webp)
21
BLOWER PERFORMANCE DATA
DCG036-048XXX*HXXXA*
HIGH STATIC BELT DRIVE - 3 & 4 TON
NOTES:
Factory shipped at 2.5 turns open.
Tables represent dry coil without filter. To compensate for filter, add 0.08" to measured E.S.P.
SCFM correction for wet coil = 4%.
***
NOTE:
High static airflow requires installation of high static kit (HSKT*).
ESP
(IN W.C.)
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.6
1568
0.45
1266
0.32
0.8
1492
0.47
1194
0.34
922
0.23
1.0
1476
0.52
1163
0.37
856
0.24
1.2
1458
0.57
1146
0.41
802
0.25
1.4
1458
0.63
1139
0.46
782
0.30
1.6
1139
0.52
844
0.36
1.8
844
0.42
ESP
(IN W.C.)
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.6
1655
0.53
1389
0.39
1103
0.28
0.8
1640
0.57
1342
0.43
1035
0.29
775
0.19
1.0
1638
0.63
1326
0.47
1002
0.32
713
0.19
1.2
1638
0.69
1307
0.52
984
0.36
1.4
1307
0.58
1002
0.42
1.6
1002
0.48
717
0.32
1.8
717
0.38
ESP
(IN W.C.)
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.6
1894
0.66
1585
0.49
0.8
1839
0.71
1532
0.53
1223
0.37
1.0
1782
0.73
1477
0.55
1170
0.39
1.2
1786
0.80
1445
0.59
1115
0.40
1.4
1764
0.86
1426
0.64
1107
0.46
1.6
1446
0.72
1098
0.50
1.8
1099
0.56
ESP
(IN W.C.)
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.6
1989
0.77
1712
0.59
1433
0.44
0.8
1929
0.79
1662
0.63
1384
0.47
1106
0.33
1.0
1952
0.88
1622
0.67
1335
0.49
1056
0.34
1.2
1897
0.93
1611
0.73
1315
0.54
1008
0.36
1.4
1616
0.80
1298
0.59
1007
0.42
1.6
1316
0.66
1007
0.46
1.8
DCG048 HIGH STATIC BELT DRIVE HORIZONTAL FLOW
0 TURNS
1 TURN
2 TURNS
3 TURNS
4 TURNS
5 TURNS
DCG048 HIGH STATIC BELT DRIVE DOWNSHOT
0 TURNS
1 TURN
2 TURNS
3 TURNS
4 TURNS
5 TURNS
DCG036 HIGH STATIC BELT DRIVE DOWNSHOT
0 TURNS
1 TURN
2 TURNS
3 TURNS
4 TURNS
5 TURNS
DCG036 HIGH STATIC BELT DRIVE HORIZONTAL FLOW
0 TURNS
1 TURN
2 TURNS
3 TURNS
4 TURNS
5 TURNS