3 Operation

Operation manual

7

D2CND024A1/4AB + D2TND012~024A4AB
Wall-mounted condensing boiler
3P469438-3M – 2019.11

NOTICE

In  case  of  bad  or  inappropriate  central  heating  circuit
design,  which  causes  inadequate  heat  emission  to  the
living space, activating the ECO mode may cause capacity
shortage.

3.3.7

About the domestic hot water operation

This  unit  supplies  domestic  hot  water  by  way  of  a  plate  heat
exchanger  (instantaneous)  or  by  way  of  a  hot  water  storage  tank
according to model of the boiler.

If  the  boiler  is  instantaneous  type,  domestic  hot  water  operation  is
activated  when  water  is  being  tapped.  Water  flow  rate  must  be  at
least 2.5 l/min.

If  it  is  storage  tank  type,  domestic  hot  water  operation  is  activated
according to storage tank temperature value.

The   icon blinks when domestic hot water operation is active.

INFORMATION

Domestic  hot  water  operation  mode  must  be  enabled  for
the  boiler  to  be  able  to  produce  domestic  hot  water.  (i.e.
summer mode or winter mode).

DANGER

For storage tank type models, domestic water temperature
may increase to 70°C due to a protective function. Possible
measures are explained in installation manual.

3.3.8

About the domestic hot water comfort
mode

The domestic hot water comfort mode includes a domestic hot water
pre-heat function and a domestic hot water post-heat function. When
the comfort mode is enabled, both pre-heat and post-heat functions
are enabled.

The pre-heat function is a self-learning algorithm according to which
the  boiler  will  heat  up  the  domestic  hot  water,  before  the  tapping
demand. The algorithm is based on your personal use pattern of the
last 24 hours.

Note: 

Independent  of  personal  use  pattern,  comfort  mode

preheating  function  could  be  adjusted  to  operate  continuously  from
the user settings.

The  post-heat  function  heats  up  the  domestic  hot  water  heat
exchanger  after  tapping,  when  the  flow  temperature  of  the  boiler  is
below the domestic hot water temperature setpoint.

Comfort  mode  can  be  enabled  from  the  user  settings  menu  (see

"User settings menu: Parameters (short)"

 [

4

 9]).

INFORMATION

Domestic  hot  water  comfort  mode  is  only  valid  for
instantaneous type hot water supply types.

When the domestic hot water comfort mode is enabled, the   icon is
shown on the screen.

The   icon blinks when the burner is on for comfort mode.

3.3.9

About the boiler frost protection

Frost protection safety system:

 This function protects the unit and

heating installation from frost damages. This protection activates the
boiler  pump  when  the  water  temperature  drops  below  13°C  and  it
activates  the  burner  when  the  water  temperature  drops  below  8°C
(factory  setting).  The  unit  keeps  running  until  the  temperature
reaches 20°C. To enable this function, the unit must be connected to
the power supply and its main gas valve must be open. Any damage
caused  by  frost  is  not  covered  by  the  warranty.  Frost  Protection  is
enabled in all modes, including standby mode and full-off mode.

While frost protection is active, “Fr” and actual flow temperature are
displayed subsequently on the display.

WARNING

If  the  boiler  is  not  connected  to  the  power  supply,  frost
protection  is  not  active.  Consequently,  the  water  may
freeze  and  cause  cracks.  The  manufacturer  is  not
responsible for any damage that may occur this way.

NOTICE

When  not  using  the  boiler,  we  strongly  recommend  not  to
cut off the electric supply to the boiler.

3.3.10

About Energy Metering Function

INFORMATION

To  be  able  to  use  energy  metering  function,  the  units  has
to  be  equipped  with  the  LAN  adapter  and  the  function
should be activated by qualified persons.

This function provides user to read electricity and gas consumptions
for  central  heating  and  domestic  hot  water  operations,  in  monthly
and yearly basis. In case the unit is not connected to internet, UH-08
error is displayed after power on. To remove this error and activate
this function, actual date must be set from T parameters.

For detailed instructions to set actual date, see 

"3.5.3 User settings

menu"

 [

4

 9]

For  detailed  information  to  display  consumption  values,  see

"3.5.2 Info menu"

 [

4

 8]

3.4

Error handling

When an error occurs, the normal behaviour of the user interface is
interrupted,  and  the  status  of  the  status  indicator  is  affected.
However,  be  aware  that  not  all  errors  have  the  same  effect  on  the
user interface and the status indicator.

Error

type

Boiler operation

User interface and status

indicator

Warning Continue

The status indicator does not enter
error mode if the burner is on. It
turns to red when the burner is off.
The LCD screen stays active and
displays the error code.

Blocking Blocked, turns back

to operation if
cause disappears

The status indicator enters error
mode. The LCD screen stays active
and displays the error code.

Lockout

Blocked and a
reset is required

The status indicator enters error
mode. The LCD screen stays active
and displays the error code. Also,
the   icon starts blinking, indicating
that a reset is required

.

In case of a warning or a blocking error, the user interface will leave
error  mode  and  return  to  the  home  screen  when  the  cause  of  the
error disappears.

In  case  of  a  lockout  error,  the  boiler  needs  to  be  reset.  Press  the
"Reset" button to remove the error, if the cause of the error is gone.
If  the  cause  of  the  error  is  still  there,  the  user  interface  will  enter
error  mode  again.  When  the  error  is  solved,  the  user  interface
returns to the home screen.

If  you  turn  any  dial  or  press  any  button  (except  the  "Reset"  button)
during an error, the user interface will display the home screen. After
the  timeout  without  any  interaction,  instead  of  darkening,  the  user
interface will enter error mode.

Summary of Contents for D2CND024A1AB

Page 1: ...Operation manual Wall mounted condensing boiler English Operation manual Wall mounted condensing boiler D2CND024A1AB D2CND024A4AB D2TND012A4AB D2TND018A4AB D2TND024A4AB ...

Page 2: ...ndensing boiler that can supply heat to central heating systems as well as supply domestic hot water Depending on settings it is possible to use the unit solely for hot water or solely for central heating Hot water supply type can be instantaneous or by means of a hot water storage tank Heating only boilers do not supply domestic hot water The type of the boiler can be recognised from the model na...

Page 3: ...ever attempt to perform maintenance or repair yourself Call a qualified service agent CAUTION Do not use sprays solvents chlorinated cleaning agents paint and adhesives in the vicinity of the unit These substances can cause corrosion even in the flue system DANGER Do not damage or remove any seals on components Only qualified persons are allowed to alter sealed components Do not make any modificat...

Page 4: ...show the home screen of the active operation mode and the related setpoint depending on the system configuration see 3 3 3 Possible operation modes 45 Status icons Meaning of icons that appear on the LCD screen Icon Description Operation mode Standby mode Domestic hot water operation enabled Domestic hot water comfort mode is enabled Central heating operation enabled Room temperature Outdoor senso...

Page 5: ...mode c Summer mode d Winter mode e Full off mode 3 3 3 Possible operation modes Operation mode Description Central heating only mode Only central heating operation mode is enabled The central heating temperature setpoint which setpoint is shown depends on the system configuration see 3 3 5 Possible central heating operation modes 4 6 and the icon is shown on the home screen The icon blinks if cent...

Page 6: ...oom temperature is displayed The room temperature setpoint can be adjusted from the user interface by means of the left dial or from the Daikin room thermostat The icon is shown on the screen instead of the icon when central heating operation mode is enabled Boiler outdoor sensor Weather compensation The case that outdoor sensor is connected to the boiler In this case the central heating water tem...

Page 7: ...ion the unit must be connected to the power supply and its main gas valve must be open Any damage caused by frost is not covered by the warranty Frost Protection is enabled in all modes including standby mode and full off mode While frost protection is active Fr and actual flow temperature are displayed subsequently on the display WARNING If the boiler is not connected to the power supply frost pr...

Page 8: ...l energy consumption Central Heating Last month kWh Description short Unit F12 d Fuel energy consumption Central Heating Current month kWh F13 d Fuel energy consumption Central Heating Current Year kWh F21 d Electric energy consumption Central Heating Last month kWh F22 d Electric energy consumption Central Heating Current month kWh F23 d Electric energy consumption Central Heating Current Year kW...

Page 9: ...value same function that can be done via the right dial when domestic hot water mode is enabled U05 When On Off room thermostat and outdoor sensor are both connected this parameter value is the virtual room temperature setpoint when there is a heat demand U06 When On Off room thermostat and outdoor sensor are both connected this parameter value is the virtual room temperature setpoint when there i...

Page 10: ...Do not let your room become too hot Decreasing the room temperature during the day saves energy Have your combi boiler s maintenance performed at least annually Provide your building with sufficient heat insulation Thermostatic valves should be used Each room should be adjusted according to comfort conditions For reception rooms this is 20 C living rooms 22 C kitchens 18 C and bedrooms 18 C Preven...

Page 11: ...E1 73 Internal PCB error Perform reset if needed If problem repeats contact your service agent H9 01 Outside sensor fault Boiler continues operation but outside sensor is defective Contact your service agent HC 01 Domestic hot water temperature sensor fault Boiler continues operation but you must contact your service agent HJ 08 High system pressure Discharge water down to 0 8 bar You can bleed th...

Page 12: ...who commissioned the boiler as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference GAS BOILER SYSTEM COMMISSIONING CHECKLIST CONTROLS Programmable room thermostat Optimum start control Combination Boiler Fitted Fitted Fitted Automatic bypass to system Fitted Boiler interlock ALL SYSTEMS Yes Yes CENTRAL HEATING M...

Page 13: ...It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed Service Provider SERVICE RECORD SERVICE 01 AND Where Possible AND Signature SERVICE 02 AND Where Possible AND Signature SERVICE 03 AND Where Possible AND Signature SERVICE 04 AND Where Possible AND Signature SERVICE 05 AND Where Possible AND Signature SERVICE 06 AND Where ...

Page 14: ......

Page 15: ......

Page 16: ...STANBUL TÜRKİYE Tel 0216 453 27 00 Faks 0216 671 06 00 Çağrı Merkezi 444 999 0 Web www daikin com tr Gülsuyu Mahallesi Fevzi Çakmak Caddesi Burçak Sokak No 20 34848 Maltepe 3P469438 3M 2019 11 Copyright 2018 Daikin Verantwortung für Energie und Umwelt ...

Reviews: