10 Commissioning

Installer reference guide

72

C08AA + EHYKOMB33A

Daikin hybrid for multi heat pump – heat pump module

4P471761-1A – 2017.10

During  a  heating  test  run,  the  unit  will  start  up  in  hybrid  operation.
The setpoint of the gas boiler during a heating test run is 40°C. Keep
in  mind  the  5°C  overshoot  that  is  possible  during  boiler  operation,
especially in combination with floor heating loops.

10.4.5

To perform an actuator test run

Purpose  of  the  actuator  test  run  is  to  confirm  the  operation  of  the
different actuators (e.g., when you select pump operation, a test run
of the pump will start).

Prerequisite: 

Make  sure  that  the  leaving  water  temperature  home

page, room temperature home page, and domestic hot water home
page are turned OFF.

1

Set the user permission level to Installer. See 

"To set the user

permission level to Installer" on page 46

.

2

Make  sure  the  room  temperature  control,  the  leaving  water
temperature  control  and  the  domestic  hot  water  control  are
turned OFF via the user interface.

3

Go  to  [A.7.4]: 

  >  Installer  settings  >  Commissioning  >

Actuator test run.

4

Select an actuator and press 

Example: 

Pump.

5

Select OK and press 

.

Result: 

The  actuator  test  run  starts.  It  automatically  stops  when

finished. To stop it manually, press 

, select OK and press 

.

Possible actuator test runs

▪ Pump test

INFORMATION

Make  sure  that  all  air  is  purged  before  executing  the  test
run. Also avoid disturbances in the water circuit during the
test run.

▪ Solar pump test

▪ Shut-off valve test

▪ 3-way valve test

▪ Alarm output test

▪ Heating signal test

▪ Quick heat-up test

▪ DHW pump test

▪ Gas boiler test

▪ Bypass valve test

INFORMATION

The setpoint during a boiler test run is 40°C. Keep in mind
the  5°C  overshoot  that  is  possible  during  boiler  operation,
especially in combination with floor heating loops.

10.4.6

Underfloor heating screed dryout

This  function  is  used  for  drying  out  the  screed  of  an  underfloor
heating  system  very  slowly  during  the  construction  of  a  house.  It
allows the installer to program and execute this program.

Make  sure  that  the  leaving  water  temperature  home  page,  room
temperature  home  page,  and  domestic  hot  water  home  page  are
turned OFF.

This  function  can  be  executed  without  finishing  the  outdoor
installation. In this case, the gas boiler will perform the screed dryout
and supply the leaving water without heat pump operation.

When no outdoor unit is installed yet, then connect the main power
supply  cable  to  the  indoor  unit  via  X2M/30  and  X2M/31.  See

"7.10.5  To  connect  the  main  power  supply  of  the  indoor  unit"  on
page 34

.

INFORMATION

▪ If Emergency is set to Manual ([A.6.C]=0), and the unit

is  triggered  to  start  emergency  operation,  the  user
interface  will  ask  confirmation  before  starting.  The
underfloor heating screed dryout function is active even
if the user does NOT confirm emergency operation.

▪ During  underfloor  heating  screed  dryout,  pump  speed

limitation [9‑0D] is NOT applicable.

NOTICE

The installer is responsible for:

▪ contacting  the  screed  manufacturer  for  the  initial

heating instructions to avoid cracking the screed,

▪ programming  the  underfloor  heating  screed  dryout

schedule  according  to  the  above  instruction  of  the
screed manufacturer,

▪ checking  the  proper  functioning  of  the  setup  on  a

regular basis,

▪ selecting  the  correct  program  complying  with  the  type

of the used screed of the floor.

NOTICE

To perform an underfloor heating screed dryout, room frost
protection needs to be disabled ([2‑06]=0). By default, it is
enabled  ([2‑06]=1).  However,  due  to  the  "installer-on-site"
mode  (see  "Checklist  before  commissioning"),  room  frost
protection  will  be  automatically  disabled  for  36  hours  after
the first power-on.

If  the  screed  dryout  still  needs  to  be  performed  after  the
first  36  hours  of  power-on,  manually  disable  room  frost
protection  by  setting  [2‑06]  to  "0",  and  KEEP  it  disabled
until the screed dryout has finished. Ignoring this notice will
result in cracking of the screed.

NOTICE

For the underfloor heating screed dryout to be able to start,
make sure the following settings are met:

▪ [4‑00]=1

▪ [C‑02]=0

▪ [D‑01]=0

▪ [4‑08]=0

▪ [4‑01]≠1

The installer can program up to 20 steps. For each step he needs to
enter:

1

the duration in hours, up to 72 hours,

2

the desired leaving water temperature.

Example:

t

T

A1

25°C (1)

35°C (2)

24h (1)

36h (2)

T

Desired leaving water temperature (15~55°C)

t

Duration (1~72 h)

(1)

Action step 1

(2)

Action step 2

Summary of Contents for CHYHBH05AA

Page 1: ...Installer reference guide Daikin hybrid for multi heat pump heat pump module English Installer reference guide Daikin hybrid for multi heat pump heat pump module CHYHBH05AA CHYHBH08AA EHYKOMB33A ...

Page 2: ... 2 To install the condensate trap 24 7 5 Condensate pipe work 25 7 5 1 Internal connections 25 7 5 2 External connections 26 7 6 Connecting the refrigerant piping 26 7 6 1 About connecting the refrigerant piping 26 7 6 2 Precautions when connecting the refrigerant piping 26 7 6 3 Guidelines when connecting the refrigerant piping 27 7 6 4 Pipe bending guidelines 27 7 6 5 To flare the pipe end 27 7 ...

Page 3: ...ing problems based on symptoms 78 13 3 1 Symptom The unit is NOT heating or cooling as expected 78 13 3 2 Symptom The compressor does NOT start space heating 78 13 3 3 Symptom The system is making gurgling noises after commissioning 78 13 3 4 Symptom The pump is making noise cavitation 78 13 3 5 Symptom The pressure relief valve opens 79 13 3 6 Symptom The water pressure relief valve leaks 79 13 3...

Page 4: ...SK OF BURNING Do NOT touch the refrigerant piping water piping or internal parts during and immediately after operation It could be too hot or too cold Give it time to return to normal temperature If you must touch it wear protective gloves Do NOT touch any accidental leaking refrigerant WARNING Provide adequate measures to prevent that the unit can be used as a shelter by small animals Small anim...

Page 5: ...ntilate the area immediately Possible risks Excessive refrigerant concentrations in a closed room can lead to oxygen deficiency Toxic gas may be produced if refrigerant gas comes into contact with fire DANGER RISK OF EXPLOSION Pump down Refrigerant leakage If you want to pump down the system and there is a leakage in the refrigerant circuit Do NOT use the unit s automatic pump down function with w...

Page 6: ...ies with the applicable legislation All field wiring MUST be performed in accordance with the wiring diagram supplied with the product NEVER squeeze bundled cables and make sure they do not come in contact with the piping and sharp edges Make sure no external pressure is applied to the terminal connections Make sure to install earth wiring Do NOT earth the unit to a utility pipe surge absorber or ...

Page 7: ... Standards Scotland Consolidated This appliance MUST be installed in accordance with the Gas Safety and Use Regulations current Building Regulations Building Standards Scotland I S 813 Installation of Gas Appliances Ireland IEE Wiring Regulations BS 7671 Health and Safety Document No 635 Electricity at Work Regulations and Local Water Authority Bye Laws UK Water Regulations and Bye Laws Health Saf...

Page 8: ...h All other languages are translations Technical engineering data A subset of the latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin extranet authentication required 3 2 Installer reference guide at a glance Chapter Description General safety precautions Safety instructions that you must read before...

Page 9: ...the gas boiler INFORMATION Do NOT throw away the upper cardboard cover On the outside of the cardboard cover the installation pattern is printed 4 2 2 To remove the accessories from the indoor unit The installation manual operation manual addendum book for optional equipment general safety precautions quick installation guide boiler communication cable and reducer accessory set are located in the ...

Page 10: ...nstallation manual and operation manual 5 About the units and options 5 1 Overview About the units and options This chapter contains information about Identifying the indoor unit Identifying the gas boiler Combining outdoor and indoor units Combining the indoor unit with options Combining the gas boiler with options 5 2 Identification NOTICE When installing or servicing several units at the same t...

Page 11: ...s English Swedish Norwegian Finnish EKRUCBL3 contains following languages English Spanish Greek Portuguese EKRUCBL4 contains following languages English Turkish Polish Romanian EKRUCBL5 contains following languages German Czech Slovenian Slovakian EKRUCBL6 contains following languages English Croatian Hungarian Estonian EKRUCBL7 contains following languages English German Russian Danish Languages ...

Page 12: ...00 l Use the appropriate connection kit for the tank EKEPHT3H as described in the addendum book for optional equipment Connection kit for the tank EKEPHT3H Use the connection kit to connect the domestic hot water tank to the indoor unit For installation instructions see the installation manual of the connection kit Mounting kit EKHYMNT1A EKHYMNT2A EKHYMNT3A Mounting fixture for easy installation o...

Page 13: ... PP GLV 60 100 EKFGP1293 Wall terminal kit low profile PP GLV 60 100 EKFGP1294 Plume management kit 60 UK only EKFGP1295 Flue deflector 60 UK only EKFGP1284 PMK elbow 60 90 UK only EKFGP1285 PMK elbow 60 45 2 pieces UK only EKFGP1286 PMK extension 60 L 1000 includes bracket UK only Accessories Part number Description EKFGW5333 Weather slate flat aluminium 80 125 EKFGW6359 Wall terminal kit PP GLV ...

Page 14: ...Ø130 EKFGS0250 Extension flex PP 130 L 130 m EKFGP6366 Connector flex flex PP 130 EKFGP1856 Flex kit PP Ø60 80 EKFGP4678 Chimney connection 60 100 Accessories Part number Description EKFGP2520 Flex kit PP Ø80 EKFGP4828 Chimney connection 80 125 EKFGP6340 Extension Flex PP 80 L 10 m EKFGP6344 Extension Flex PP 80 L 15 m EKFGP6341 Extension Flex PP 80 L 25 m EKFGP6342 Extension Flex PP 80 L 50 m EKF...

Page 15: ...dust is created the unit MUST be covered Choose an installation location with sufficient space for carrying the unit in and out of the site 6 2 1 Installation site requirements of the indoor unit INFORMATION Also read the precautions and requirements in the General safety precautions chapter Mind the measurement guidelines Maximum refrigerant piping length between indoor unit and outdoor unit 25 m...

Page 16: ...ening The area of the top opening must be larger than or equal to the bottom opening The bottom of the top opening must be situated at least 1 5 m above the top of the bottom opening Ventilation openings to the outside are NOT considered suitable ventilation openings the user can block them when it is cold For ventilation opening requirements see Ventilation opening requirements in the chapter Tec...

Page 17: ...ents INFORMATION Also read the precautions and requirements in the General safety precautions chapter Piping material Phosphoric acid deoxidised seamless copper Piping diameter CHYHBH05 08 Liquid piping Ø6 4 mm 1 4 Gas piping Ø15 9 mm 5 8 3MXM40 3MXM52 3MXM68 Liquid piping 3 Ø6 4 mm 1 4 Gas piping 1 Ø9 5 mm 3 8 2 Ø12 7 mm 1 2 4MXM68 Liquid piping 4 Ø6 4 mm 1 4 4MXM68 Gas piping 2 Ø9 5 mm 3 8 2 Ø12...

Page 18: ...ng station to prevent water that is too hot from entering the underfloor heating circuit Water temperature All installed piping and piping accessories valve connections MUST withstand the following temperatures INFORMATION The following illustration is an example and might NOT match your system layout M 89 C RAD1 RAD2 RAD3 95 C 65 C a b d e j k i c f g FCU1 FCU2 FCU3 h g l a Outdoor unit b Indoor ...

Page 19: ...ulation pump in between the hot water end point and the recirculation connection of the domestic hot water tank c d a b a Recirculation connection b Hot water connection c Shower d Recirculation pump 6 4 2 Formula to calculate the expansion vessel pre pressure The pre pressure Pg of the vessel depends on the installation height difference H Pg 0 3 H 10 bar 6 4 3 To check the water volume and flow ...

Page 20: ...ps is controlled by remotely controlled valves it is important that the minimum flow rate is guaranteed even if all valves are closed In case the minimum flow rate cannot be reached a flow error 7H will be generated no heating or operation Minimum required flow rate 05 08 models 9 l min See the recommended procedure as described in 10 4 Checklist during commissioning on page 70 6 4 4 Changing the ...

Page 21: ...able to indoor unit 3 Power supply for gas boiler 6 5 3 Overview of electrical connections for external and internal actuators The following illustration shows the required field wiring INFORMATION The following illustration is an example and might NOT match your system layout M 4 7 8 9 10 14 15 11 2 5 6 12 c a d b 13 3 1 a Outdoor unit b Indoor unit c Gas boiler d Domestic hot water tank Item Des...

Page 22: ...RMATION It is NOT possible to connect an indoor unit of 1 room only Be sure to connect indoor units of at least 2 rooms The Hybrid for Multi is considered as 1 room connection For the correct combination see the combination table and the installation manual of the Hybrid for Multi 7 2 Opening the units 7 2 1 About opening the units At certain times you have to open the unit Example When connecting...

Page 23: ...e indoor unit 7 3 1 About mounting the indoor unit When You have to mount the outdoor and indoor unit before you can connect the refrigerant and water piping Typical workflow Mounting the indoor unit typically consists of the following stages 1 Installing the indoor unit 7 3 2 Precautions when mounting the indoor unit INFORMATION Also read the precautions and requirements in the following chapters...

Page 24: ...er 4 Lift the boiler One person lifts the gas boiler on the left side left hand on the top and right hand on the bottom and another person lift the gas boiler on the right side left hand on the bottom and right hand on the top 5 Tilt the top of the unit at the position of the indoor unit mounting bracket 6 Slide the boiler downwards to fix the boiler bracket onto the indoor unit mounting bracket 7...

Page 25: ...ections If possible the condensate drain pipe should be routed and terminated so that the condensate drains away from the boiler under gravity to a suitable internal foul water discharge point such as an internal soil and vent stack A suitable permanent connection to the foul waste pipe should be used Ø22 mm a b c a Condensate discharge from boiler b Soil and vent stack c Minimum 450 mm and up to ...

Page 26: ...frigerant piping Keeping in mind the guidelines for Pipe bending Flaring pipe ends Brazing Using the stop valves 7 6 2 Precautions when connecting the refrigerant piping INFORMATION Also read the precautions and requirements in the following chapters General safety precautions Preparation DANGER RISK OF BURNING CAUTION Do NOT use mineral oil on flared part Do NOT reuse piping from previous install...

Page 27: ...wn so that the chips do not enter the pipe a b a Cut exactly at right angles b Remove burrs 3 Remove the flare nut from the stop valve and put the flare nut on the pipe 4 Flare the pipe Set exactly at the position as shown in the following illustration A 5 Check that the flaring is properly made a b c a Flare s inner surface must be flawless b The pipe end must be evenly flared in a perfect circle...

Page 28: ...m cap liquid side 13 5 16 5 Stem cap gas side 22 5 27 5 To handle the service cap Always use a charge hose equipped with a valve depressor pin since the service port is a Schrader type valve After handling the service port tighten the service port cap and check for refrigerant leaks Item Tightening torque N m Service port cap 10 8 14 7 7 6 8 Usage of reducers to connect the piping to the outdoor u...

Page 29: ...holesaler Do not use soap water which may cause cracking of flare nuts soap water may contain salt which absorbs moisture that will freeze when the piping gets cold and or lead to corrosion of flared joints soap water may contain ammonia which causes a corrosive effect between the brass flare nut and the copper flare 1 Charge the system with nitrogen gas up to a gauge pressure of at least 200 kPa ...

Page 30: ...he applicable legislation Formula to calculate the greenhouse gas emissions GWP value of the refrigerant Total refrigerant charge in kg 1000 Please contact your installer for more information WARNING FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable WARNING Do NOT pierce or burn refrigerant cycle parts Do NOT use cleaning materials or means to accelerate the defrosting proces...

Page 31: ... Connecting the water piping typically consists of the following stages 1 Connecting the water piping of the indoor unit 2 Connecting the water piping of the gas boiler 3 If necessary performing a wiring error check See 10 4 1 To perform a wiring error check on page 70 INFORMATION You only have to perform a wiring error check if you are not sure that the electrical wiring and piping is connected c...

Page 32: ...he correct operation of the field installed pressure relief valve If this is NOT working correctly overpressure will deform the tank and water leakage may occur To confirm good operation regular maintenance is required 7 9 4 Connecting the water piping of the gas boiler To connect the water piping for space heating Use the straight brass fitting connections accessory of the heat pump unit 1 The sp...

Page 33: ...opening a hot water tap 3 Leave the tap open until all air has disappeared from the system 4 Check all connections for leaks including internal connections 7 9 7 To fill the domestic hot water tank For installation instructions see the installation manual of the domestic hot water tank 7 9 8 To insulate the water piping The piping in the complete water circuit MUST be insulated to prevent reductio...

Page 34: ...nts during service Routing Possible cables depending on unit type and installed options a Interconnection cable between indoor and outdoor unit Heat pump convector option Room thermostat option 3 way valve option in case of tank Shut off valve field supply Domestic hot water pump field supply b Interconnection cable between indoor unit and gas boiler see boiler manual for connection instructions c...

Page 35: ...ROCUTION A fused spur or an unswitched socket MUST be located no more than 1 m from the appliance CAUTION For installation in damp rooms a fixed connection is obligatory When working on the electrical circuit ALWAYS isolate the electric supply 7 10 7 To connect the communication cable between gas boiler and indoor unit 1 Open the gas boiler 2 Open the switch box cover of the gas boiler 3 Remove on...

Page 36: ...t 1 user interface in the room used as room thermostat Action 1 Connect the user interface cable to the indoor unit Fix the cable with cable ties to the cable tie mountings X1M 1 2 X5M a b a Main user interface a b Optional user interface 2 Insert a screwdriver into the slots underneath the user interface and carefully separate the faceplate from the wallplate The PCB is mounted in the faceplate o...

Page 37: ...X5M NO NC M2S M2S 7 6 5 2 Fix the cable with cable ties to the cable tie mountings 7 10 10 To connect the domestic hot water pump 1 Connect the domestic hot water pump cable to the appropriate terminals as shown in the illustration below 35 34 X2M X1M X5M 1 M M2P 2 Fix the cable with cable ties to the cable tie mountings 7 10 11 To connect the alarm output 1 Connect the alarm output cable to the a...

Page 38: ...ivered with the domestic hot water tank the safety thermostat setpoint is at least 15 C greater than the maximum leaving water temperature setpoint INFORMATION After it is installed do NOT forget to configure the safety thermostat Without configuration the indoor unit will ignore the safety thermostat contact 7 11 Connecting the gas piping 7 11 1 To connect the gas pipe 1 Connect a gas valve to th...

Page 39: ...he integral sealing ring ensures an airtight connection 5 Check the connection of the internal flue pipe and the condensate collector Make sure it is properly connected 7 12 2 To change the 60 100 concentric connection to a dual pipe connection The concentric connection can be changed from Ø60 100 to a dual pipe connection 2 Ø80 by an adapter set 1 Remove the concentric pipe from the air supply an...

Page 40: ... pipe length for Ø80 Ø50 0 15 the permissible pipe length for Ø80 Contact the manufacturer to check the calculations for the resistance of the air supply and combustion gas flue pipe and the wall temperature at the end of the combustion gas flue pipe Sample calculation for dual pipe application L6 L4 L3 L1 L2 L5 Pipe Pipe length Total pipe length Flue pipe L1 L2 L3 2 2 m 13 m Air supply L4 L5 L6 2...

Page 41: ... 1 8 L1 11 8 Multi boiler installation INFORMATION All piping lengths in the tables below are maximum equivalent piping lengths L1 L1 C83 C43 C43 6 L2 5 C83 6 L1 C43 C43 5 5 5 L1 L2 L1 L1 L2 The horizontal flue MUST be installed under a 3 fall towards the boiler 50 mm per metre and MUST be supported with a minimum of 1 bracket at each meter length Best recommended position of the bracket is just b...

Page 42: ...rom the 3rd party All parts purchased from an external supplier MUST comply with EN14471 b NOT allowed 7 12 6 Flue pipe position See the local and national regulations Especially for UK Only use flue products approved by the boiler manufacturer which can be bought from the supplier of your boiler Refer to the field supplied accessories for all available accessories P S C B A M R D J Q G A Q Q N P ...

Page 43: ...RMATION Flexible flue gas lines may NOT be used in horizontal connection sections 7 12 9 Fitting a vertical flue system A vertical 60 100 mm flue kit is also available By using additional components available from your boiler supplier the kit can be extended up to a maximum length as specified in the table indicating the maximum pipe lengths excluding the initial boiler connection CAUTION Read the...

Page 44: ...ordance with the requirements of BS5440 Check if the condensate trap is filled with water and correctly connected to the boiler All flue joints are correctly made unstressed and adequately supported All parts of the flue can be visually inspected Ensure suitable access where flue is positioned within voids 7 13 Finishing the outdoor unit installation 7 13 1 To finish the outdoor unit installation ...

Page 45: ... and do with the user interface How You can configure the system using two different methods Method Description Configuring via the user interface First time Quick wizard When you turn ON the user interface for the first time via the indoor unit a quick wizard starts to help you configure the system Afterwards If necessary you can make changes to the configuration afterwards Configuring via the PC...

Page 46: ...en To modify an overview setting Example Modify 1 01 from 15 to 20 1 Go to A 8 Installer settings Overview settings 2 Go to the corresponding screen of the first part of the setting by using the and button INFORMATION An additional 0 digit is added to the first part of the setting when you access the codes in the overview settings Example 1 01 1 will result in 01 01 02 06 0a 0e 00 03 07 0b 0f 00 0...

Page 47: ...staller settings or the configuration of the unit on the main user interface If not it can take up to 5 minutes before these changes are visible in the menu structure 8 Your system is now set to be operated by the 2 user interfaces To copy the language set from the first to the second user interface See To copy the system settings from the first to the second user interface on page 46 Quick wizard...

Page 48: ...t unit this user interface is used to control the unit The other user interface is automatically set to In room In room default this user interface acts as room thermostat The other user interface is automatically set to At unit Code Description A 2 1 8 7 02 The system can supply leaving water to up to 2 water temperature zones During configuration the number of water zones must be set Number of L...

Page 49: ...ty to connect a field supplied domestic hot water pump On OFF type Depending on the installation and configuration on the user interface we distinguish its functionality Not applicable for Switzerland In case of E 06 0 0 No default NOT installed 1 Secondary rtrn Installed for instant hot water when hot water is tapped The end user sets the operation timing weekly schedule time of the domestic hot ...

Page 50: ...d on the indoor unit X2M 1a 2 H C request default See Contact type main Connected on the indoor unit X2M 1a and 2a Code Description A 2 2 B C 08 External sensor When an optional external ambient sensor is connected the type of the sensor must be set 0 No default NOT installed The thermistor in the user interface and in the outdoor unit are used for measurement 1 Outdoor sensor Installed The outdoo...

Page 51: ...eating control The basic required settings in order to configure the space heating of your system are described in this chapter The weather dependent installer settings define the parameters for the weather dependent operation of the unit When weather dependent operation is active the water temperature is determined automatically depending on the outdoor temperature Low outdoor temperatures will r...

Page 52: ...ure 40 C 5 C default 10 C 0 02 High outdoor ambient temperature 10 C 25 C default 15 C 0 01 Desired leaving water temperature when the outdoor temperature equals or drops below the low ambient temperature 9 05 C 9 06 C default 60 C Note This value should be higher than 0 00 as for low outdoor temperatures warmer water is required 0 00 Desired leaving water temperature when the outdoor temperature ...

Page 53: ... 10 C default 5 C Requires modulation to be enabled This is the value by which the desired leaving water temperature is increased or lowered INFORMATION When leaving water temperature modulation is enabled the weather dependent curve needs to be set to a higher position than 8 06 plus the minimum leaving water temperature setpoint required to reach a stable condition on the comfort setpoint for th...

Page 54: ...he value you ONLY have to do it in one place Depending on whether the desired leaving water temperature is weather dependent or NOT the desired shift values or the absolute desired leaving water temperature should be specified NOTICE The preset leaving water temperatures are ONLY applicable for the main zone as the schedule for the additional zone consists of On OFF actions NOTICE Select preset le...

Page 55: ...te desired LWT b Weather dependent desired LWT Code Description N A D 03 0 disabled default 1 enabled L 2 C R 4 C 2 C TA 2 C 2 enabled L 4 C R 4 C 2 C TA 2 C 3 enabled L 2 C R 8 C 4 C TA 4 C 4 enabled L 4 C R 8 C 4 C TA 4 C Leaving water temperature maximum modulation ONLY applicable in room thermostat control and when modulation is enabled The maximum modulation variance on the desired leaving wa...

Page 56: ...protection is guaranteed even if the room temperature home page is OFF on the user interface When room frost protection 2 06 is enabled and the room temperature drops below the room antifrost temperature 2 05 the unit will supply leaving water to the heat emitters to heat up the room again Code Description N A 2 06 Room frost protection 0 disabled default 1 enabled Code Description N A 2 05 Room a...

Page 57: ...3 1 4 02 14 C 35 C default 25 C Depending on 1 0A the actual outdoor temperature will be averaged over the selected time period Refer to System settings on page 60 4 02 25 C heat pump will be prohibited when the outdoor temperature reaches 4 02 This temperature can be different from the outdoor average temperature 4 02 25 C and 1 0A 0 heat pump will be prohibited when the outdoor temperature reach...

Page 58: ... Storage economic and reheat temperatures are NOT weather dependent In reheat mode the desired tank temperature is weather dependent Note When the displayed tank temperature is weather dependent it cannot be adjusted on the user interface Code Description A 4 7 0 0E 0 0D 0 0C 0 0B Weather dependent curve TDHW Ta 0 0C 0 0B 0 0E 0 0D TDHW The desired tank temperature Ta The averaged outdoor ambient ...

Page 59: ...ou do the following during disinfection Set the user permission level to Installer Go to the DHW tank temperature home page Tank Press to interrupt the disinfection Heat source settings Auto emergency When the heat pump fails to operate the gas boiler can serve as an emergency back up heater and either automatically or non automatically take over the entire heat load When auto emergency is set to ...

Page 60: ...aged over the selected time period Code Description A 6 4 1 0A Outdoor average timer 0 No averaging 1 12 hours default 2 24 hours 3 48 hours 4 72 hours Offset temperature external outdoor ambient sensor Only applicable in case of an external outdoor ambient sensor is installed and configured You can calibrate the external outdoor ambient temperature sensor It is possible to give an offset to the t...

Page 61: ...ssion level Actuators Operation modes Version Error information Error history Contact helpdesk number Version User interface Indoor unit Outdoor unit User settings Display Temperature lock Set schedules Preset values Unit of measurement Display Contrast Backlit LCD time User profile Available home pages Set schedules Room temp DHW temp Preset values Room temperature LWT main Tank temperature Quiet...

Page 62: ...thod Number of LWT zones Pump operation mode User interface location Options DHW operation DHW tank DHW tank type Contact type add Digital I O PCB Demand PCB External kWh meter DHW pump External sensor Leaving water Main Additional Room thermostat Room temp range Room temp offset Ext room sensor offset Operation range Space heating OFF temp Disinfection Disinfection Operation day Start time Temper...

Page 63: ... the domestic hot water comfort function can be turned off To reset the gas boiler Resetting is only possible when an error occurs Prerequisite Flashing LED above the button and an error code on the main display Prerequisite Check the meaning of the error code see Error codes of the gas boiler on page 83 and resolve the cause 1 Press to restart the gas boiler Maximum space heating supply temperatu...

Page 64: ...ible to set this parameter to 100 default setting We strongly recommend not modifying this setting Minimum supply temperature of the heat curve 10 C 25 C 15 C Do NOT modify this setting on the boiler Use the user interface instead Maximum supply temperature of the heat curve 30 C 90 C 90 C Do NOT modify this setting on the boiler Use the user interface instead Minimum outside temperature of the he...

Page 65: ...er to set the maximum fan rpm It is recommended not to modify this setting Set point space heating flow temperature during heating external domestic hot water tank 60 C 90 C 85 C Do NOT modify this setting on the boiler Use the user interface instead Comfort temperature 0 C 40 C 65 C 0 C Temperature used for eco comfort function When the value is 0 C the eco comfort temperature is the same as the ...

Page 66: ...ence 7 Open the gas tap 8 Check the gas connections before the gas valve for gastightness 9 Switch on the mains power 10 Check the gas connections after the gas valve for gastightness during operation 11 Now check the setting of the CO2 percentage at high setting in display and low setting in display 12 Put a sticker indicating the new gas type on the bottom of the gas boiler next to the nameplate...

Page 67: ...aximum value a Minimum value 8 4 7 4 9 4 9 4 a CO2 value at maximum power recorded at High setting 11 If the CO2 percentage at maximum and minimum power is within the range expressed in the tables above the CO2 setting of the boiler is correct If NOT adjust the CO2 setting according to the instructions in the chapter below 12 Switch off the appliance by pressing the button and put the sampling poi...

Page 68: ...r to the manual of the heat pump module 9 3 1 Flow resistance graph for appliance domestic hot water circuit Not applicable for Switzerland 0 2 0 1 3 5 7 9 11 13 15 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 bar l min The minimum flow for domestic hot water operation is 1 5 l min The minimum pressure is 0 1 bar A low flow 5 l min can reduce comfort Make sure to set the setpoint high enough 9 4 Operation ...

Page 69: ...irst running period of the unit the required power may be higher than stated on the nameplate of the unit This phenomenon is caused by the compressor that needs a continuous run time of 50 hours before reaching smooth operation and stable power consumption NOTICE NEVER operate the unit without thermistors and or pressure sensors switches Burning of the compressor might result 10 3 Checklist before...

Page 70: ...ge occurs 2 Proceed with the steps as described in the outdoor unit installation manual or outdoor unit installer reference guide to perform a wiring error check NOTICE Make sure that the minimum required water flow in the unit is guaranteed 10 4 2 To check the minimum flow rate 1 Confirm according to the hydraulic configuration which space heating loops can be closed due to mechanical electronic ...

Page 71: ...mp speed Result Low Result High 7 If applicable set the desired position of the 3 way valve space heating domestic hot water Use the and buttons to scroll to Circuit 8 Use the and buttons to set the desired position of the 3 way valve Result SHC or Tank 9 Set the desired position of the bypass valve Use the and buttons to scroll to Bypass 10 Use the and buttons to set the desired position of the b...

Page 72: ...e home page room temperature home page and domestic hot water home page are turned OFF This function can be executed without finishing the outdoor installation In this case the gas boiler will perform the screed dryout and supply the leaving water without heat pump operation When no outdoor unit is installed yet then connect the main power supply cable to the indoor unit via X2M 30 and X2M 31 See ...

Page 73: ... The current step of the program the total remaining time and the current desired leaving water temperature will be displayed INFORMATION There is limited access to the menu structure Only the following menus can be accessed Information Installer settings Commissioning UFH screed dryout To interrupt an underfloor heating screed dryout When the program is stopped by an error an operation switch off...

Page 74: ...vice agent We recommend performing maintenance at least once a year However applicable legislation might require shorter maintenance intervals 12 1 Overview Maintenance and service This chapter contains information about The yearly maintenance of the indoor unit Cleaning the gas boiler 12 2 Maintenance safety precautions DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING NOTICE Risk of electrosta...

Page 75: ...rt anymore flush and clean the complete tank including the piping between the relief valve and cold water inlet To make sure this water originates from the tank check after a tank heat up cycle It is recommended to do this maintenance more frequently Switch box Carry out a thorough visual inspection of the switch box and look for obvious defects such as loose connections or defective wiring WARNIN...

Page 76: ... heat exchanger and remove it 12 Remove the connector from the fan and the ignition unit from the gas valve 13 Unscrew the coupling below the gas valve 14 Unscrew the socket head screws from the front cover and remove the socket complete with gas valve and fan to the front NOTICE Make sure that the burner insulation plate gas valve gas supply and fan do NOT get damaged 12 6 To clean the inside of ...

Page 77: ...ap connection Make sure in doing this that the back of the condensate drain pan comes to rest on the lug of the back of the base tray 8 Fill the condensate trap with water and fit it to the connection below the condensate drain pan 9 Slide the flue pipe turning it counterclockwise with the top around the flue adapter into the top cover 10 Insert the bottom into the condensate drain pan and tighten...

Page 78: ...er In some cases it is normal that the unit decides to use a low water flow Possible causes Corrective action The water volume in the installation is too low Make sure that the water volume in the installation is above the minimum required value see 6 4 3 To check the water volume and flow rate on page 19 13 3 2 Symptom The compressor does NOT start space heating Possible causes Corrective action ...

Page 79: ...3 3 7 Symptom The space is NOT sufficiently heated at low outdoor temperatures Possible causes Corrective action Gas boiler operation is not activated Check and make sure that The gas boiler is switched On and is NOT in standby mode The communication cable between the gas boiler and the indoor unit is properly mounted There is no error code on the gas boiler display The gas boiler equilibrium temp...

Page 80: ...gnition electrode No spark Ignition unit on gas valve faulty Check the cabling Check the spark plug cap Replace the ignition unit Gas air adjustment NOT correctly set Check the adjustment See To check the carbon dioxide setting on page 66 Fan faulty Check the wiring Check the fuse If necessary replace the fan Fan dirty Clean the fan Possible causes Corrective action Gas valve faulty Replace the ga...

Page 81: ... low To guarantee comfort a minimum water flow of 5 l min is recommended Increase the domestic hot water setpoint on the domestic hot water homepage of the user interface 13 3 19 Symptom Hot water does NOT reach the temperature tank installed Possible causes Corrective action The gas boiler has an error code Check the display of the gas boiler for more information The indoor unit has an error code...

Page 82: ...rror Please contact your dealer U3 00 Under floor heating screed dryout function not completed correctly U4 00 Indoor outdoor unit communication problem U5 00 User interface communication problem U6 36 Boiler standby abnormality Check boiler Refer to boiler manual U8 01 Connection with adapter lost Please contact your dealer UA 00 Indoor unit outdoor unit matching problem Power reset required UA 5...

Page 83: ... and indicates them on the display by error codes If the LED is flashing the controller has detected a problem Once the problem is rectified the controller can be restarted by pressing the button Following table shows a list of error codes and the possible solutions Error code Cause Possible solution 10 11 12 13 14 Sensor fault S1 Check wiring Replace S1 Error code Cause Possible solution 20 21 22...

Page 84: ...eration will extract all refrigerant from the system into the outdoor unit 1 Remove the valve lid from the liquid stop valve and the gas stop valve 2 Carry out the forced cooling operation See 14 3 To start and stop forced cooling on page 84 3 After 5 to 10 minutes after only 1 or 2 minutes in case of very low ambient temperatures 10 C close the liquid stop valve with a hexagonal wrench 4 Check wi...

Page 85: ...s pipe 15 Domestic hot water hot water IN 16 R1T Plate heat exchanger outlet water thermistor 17 R2T Outlet water thermistor 18 R3T Heat exchanger liquid pipe thermistor 19 R4T Inlet water thermistor 20 Screw connection Screw connection Quick coupling Brazed connection Flare connection 15 2 Wiring diagram Indoor unit See the internal wiring diagram supplied with the unit on the inside of the indoo...

Page 86: ... floor heating domestic hot water tank M4S Bypass valve for gas boiler PHC1 Optocoupler input circuit PS Switching power supply Q DI Earth leakage circuit breaker R1T A1P Outlet water heat exchanger thermistor R1T A2P Ambient sensor user interface R1T A3P Ambient sensor On OFF thermostat R2T A1P Outlet gas boiler thermistor R2T A4P External sensor floor or ambient R3T A1P Refrigerant liquid side t...

Page 87: ...ar pump connection Solar pump connection Switch box Switch box Thermo On OFF output Thermo On OFF output 7 External room thermostats and heat pump convector 7 External room thermostats and heat pump convector English Translation Additional LWT zone Additional leaving water temperature zone Main LWT zone Main leaving water temperature zone Only for external sensor floor ambient Only for external se...

Page 88: ...in X2M 1 4 add X2M 1a 3 4 main X2M 1 3 4 add X2M 1a 4 main X2M 1 4 communication 2 core communication 2 core X2 2 4 earth unit power supply 230 V earth Gas boiler 3 core Gas boiler part Heat pump part 4 core In case user interface is relocated In case of signal cable keep minimum distance to power cables 5 cm Field supply Optional part External room thermostat Heat pump convector main and or addit...

Page 89: ...2 1 43 2 3 4 2 3 1 1 3 5 4 7 6 3 a Earth connections heat exchanger b Spark plug cover c Boiler controller d Earth connections boiler controller e Fuse 3 15 A T f Gas valve and ignition unit g Ionisation ignition probe h Main voltage i Fan S1 Flow sensor S2 Return sensor S3 Domestic hot water sensor not applicable for Switzerland S5 Flow switch S7 Space heating water pressure sensor X1 Gas valve a...

Page 90: ... 54 2 80 3 05 3 31 3 56 3 82 4 07 4 33 21 1 56 1 83 2 09 2 35 2 61 2 87 3 13 3 39 3 65 3 91 4 17 4 43 22 1 60 1 87 2 13 2 40 2 67 2 94 3 20 3 47 3 74 4 00 4 27 4 54 23 1 64 1 91 2 18 2 46 2 73 3 00 3 27 3 55 3 82 4 09 4 37 4 64 24 1 67 1 95 2 23 2 51 2 79 3 07 3 34 3 62 3 90 4 18 4 46 4 74 25 1 71 1 99 2 28 2 56 2 84 3 13 3 41 3 70 3 98 4 27 4 55 4 84 26 1 74 2 03 2 32 2 61 2 90 3 19 3 48 3 77 4 0...

Page 91: ...ues i e when H is between 2 H values from the table consider the value that corresponds to the lower H value from the table If H 950 mm consider the value that corresponds to H 900 mm In cases where H 600 mm h is always considered to be 600 mm as specified in IEC 60335 2 40 2013 A1 2016 clause GG2 For intermediate Aroom values i e when Aroom is between 2 Aroom values from the table consider the lo...

Page 92: ...22 76 17 42 13 77 11 15 9 22 7 74 6 60 5 91 5 52 5 17 4 87 2 00 34 32 25 22 19 31 15 25 12 36 10 21 8 58 7 31 6 30 5 81 5 45 5 13 2 10 37 84 27 80 21 29 16 82 13 62 11 26 9 46 8 06 6 95 6 10 5 72 5 38 2 20 41 53 30 51 23 36 18 46 14 95 12 36 10 38 8 85 7 63 6 64 5 99 5 64 2 30 45 39 33 35 25 53 20 17 16 34 13 50 11 35 9 67 8 34 7 26 6 38 5 90 2 40 49 42 36 31 27 80 21 97 17 79 14 70 12 36 10 53 9 ...

Page 93: ...0 145 0 40 224 192 168 150 135 122 115 111 107 103 100 97 0 20 119 102 89 80 72 65 60 56 54 52 50 49 0 00 2 2 1 98 805 746 698 658 624 595 570 547 527 510 493 479 1 76 716 663 620 585 555 529 506 487 469 453 439 426 1 54 627 580 543 512 485 463 443 426 410 396 384 372 1 32 548 497 465 439 416 397 380 365 352 340 329 319 1 10 510 437 388 366 347 331 317 304 293 283 274 266 0 88 447 383 336 298 278 ...

Page 94: ...6 558 541 1 92 960 823 720 640 605 577 552 531 511 494 478 464 1 60 895 767 671 597 537 488 460 442 426 412 399 387 1 28 784 672 588 523 471 428 392 362 341 330 319 310 0 96 635 545 477 424 381 347 318 294 273 254 239 232 0 64 453 388 340 302 272 247 227 209 194 181 170 160 0 32 240 206 180 160 144 131 120 111 103 96 90 85 0 00 5MXM90 3 3 2 97 1208 1118 1046 986 936 892 854 821 791 764 740 718 2 6...

Page 95: ...the minimum water flow rate is not reached 0 0 5 10 15 20 25 30 35 40 50 60 70 45 55 65 2 4 6 8 10 12 14 16 18 20 22 24 A kPa B l min 4D109043 C A External static pressure B Water flow rate C Minimum water flow rate Boiler bypassed Boiler not bypassed Note Selecting a flow outside the area of operation can cause damage or malfunction of the unit Water quality MUST be according to EN directive EC98...

Page 96: ...Aluminium Space heating water circuit Space heating piping connections Ø22 mm Piping material Cu Safety valve See indoor unit manual Manometer Yes Drain fill valve No Shut off valves No Air purge valve Yes Maximum pressure space heating circuit 3 bar Domestic hot water circuit not applicable for Switzerland Domestic hot water piping connections Ø15 mm Piping material Cu Gas connection Ø15 mm Flue ...

Page 97: ...o G25 After conversion to G31 Portugal II2H3 G20 20 mbar G31 37 mbar Greece II2H3 G20 20 mbar G31 37 mbar Cyprus II2H3 G20 20 mbar G31 37 mbar Poland II2H3P G20 20 mbar G31 37 mbar Ireland II2H3 G20 20 mbar G31 37 mbar Turkey II2H3 G20 20 mbar G31 37 mbar Switzerland II2H3 G20 20 mbar G31 37 mbar Malta I3P G31 30 mbar Lithuania II2H3P G20 20 mbar G31 30 mbar Latvia II2H3P G20 20 mbar G31 30 mbar a...

Page 98: ...oiler Fitted Not Required Fitted Not Required Fitted Not Required Fitted Not Required Provided Quantity litres No Yes No Yes ft3 hr Gas Inlet Pressure OR OR mbar m3 hr mbar OR OR m3 hr mbar C C Yes Yes Yes Yes Yes Yes ft3 hr Gas inlet Pressure at maximum rate mbar C Temperature C l min Condensing Boilers Only The Condensate drain has been installed in accordance with the manufacturer s instruction...

Page 99: ...mpany Name Telephone No Gas Safe Register No Comments Service 2 Date Signature Engineer Name Company Name Telephone No Gas Safe Register No Comments Service 3 Date Signature Engineer Name Company Name Telephone No Gas Safe Register No Comments Service 4 Date Signature Engineer Name Company Name Telephone No Gas Safe Register No Comments Service 5 Date Signature Engineer Name Company Name Telephone...

Page 100: ...ertain product or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance instructions Instruction manual specified for a certain product or application which explains if relevant how to install configure operate and or maintain the product or application Accessories ...

Page 101: ...1 6 Field settings table Applicable indoor units CHYHBH05AAV32 CHYHBH08AAV32 Notes 4P471775 1 2016 12 ...

Page 102: ...e for low ambient temp for LWT add zone heating WD curve R W 9 05 9 06 C step 1 C 60 C 7 7 2 1 0 02 Set weather dependent heating High ambient temp for LWT add zone heating WD curve R W 10 25 C step 1 C 15 C 7 7 2 1 0 03 Set weather dependent heating Low ambient temp for LWT add zone heating WD curve R W 40 5 C step 1 C 10 C Installer settings System layout Standard A 2 1 1 E 00 R O 0 5 3 Hybrid A...

Page 103: ...eheat only 1 Reheat sched 2 Scheduled only Disinfection A 4 4 1 2 01 R W 0 No 1 Yes A 4 4 2 2 00 R W 0 Each day 1 Monday 2 Tuesday 3 Wednesday 4 Thursday 5 Friday 6 Saturday 7 Sunday A 4 4 3 2 02 R W 0 23 hour step 1 hour 23 A 4 4 4 2 03 R W fixed value 60 C A 4 4 5 2 04 R W 40 60 min step 5 min 40 min Maximum setpoint A 4 5 6 0E R W E 06 1 E 07 6 40 75 C step 1 C 75 C E 07 6 40 60 C step 1 C 60 C...

Page 104: ...C A 8 4 03 3 A 8 4 04 1 A 8 4 05 0 A 8 4 06 0 1 A 8 4 07 1 A 8 4 08 0 A 8 4 09 1 A 8 4 0A 0 A 8 4 0B 1 A 8 4 0C 35 A 8 4 0D 3 A 8 4 0E Is the installer on site R W 0 No 1 Yes A 8 5 00 0 A 8 5 01 R W 15 35 C step 1 C 5 C A 8 5 02 0 What is the equilibrium temperature for the building Do not change this value Below which outdoor temperature is heating allowed What is the maximum desired room tempera...

Page 105: ... step 1 C 25 C A 8 9 02 22 A 8 9 03 5 A 8 9 04 1 A 8 9 05 R W 15 37 C step 1 C 25 C A 8 9 06 R W 37 80 C step 1 C 80 C A 8 9 07 5 A 8 9 08 22 A 8 9 09 5 A 8 9 0A 5 A 8 9 0B R W 0 Quick 1 Slow A 8 9 0C R W 1 6 C step 0 5 C 1 C A 8 9 0D R W 0 8 step 1 6 A 8 9 0E 0 8 step 1 6 A 8 A 00 0 A 8 A 01 0 A 8 A 02 0 A 8 A 03 0 A 8 A 04 0 A 8 B 00 0 A 8 B 01 0 A 8 B 02 0 A 8 B 03 0 What emitter type is connec...

Page 106: ...R O 0 A 8 E 05 R W 0 No 1 Yes A 8 E 06 R W 0 No 1 Yes A 8 E 07 R W 0 6 4 Type 5 6 Type 7 A 8 E 08 0 A 8 E 09 0 A 8 E 0A 0 A 8 E 0B 0 A 8 E 0C 0 A 8 F 00 0 A 8 F 02 3 A 8 F 03 5 A 8 F 04 0 A 8 F 05 0 A 8 F 06 0 A 8 F 09 0 A 8 F 0A 0 A 8 F 0B R W 0 No 1 Yes A 8 F 0C R W 1 A 8 F 0D R W 0 Continuous 1 Sample 2 Request Which type of unit is installed Which type of compressor is installed What is the pu...

Page 107: ......

Page 108: ...4P471761 1A 2017 10 Copyright 2016 Daikin ...

Reviews: