8 Configuration
Installer reference guide
67
C08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1A – 2017.10
a
INFORMATION
Make sure the start-up procedure of the analyser is
completed before inserting the probe into the sampling
point.
INFORMATION
Allow the gas boiler to operate steadily. Connecting the
measuring probe before stable operation can give incorrect
readings. It is recommended to wait at least 30 minutes.
5
Switch on the gas boiler with the button and create a space
heating demand.
6
Select High setting by simultaneously pressing
and twice.
Capital will appear on the service display. The user interface
will display Busy. Do NOT test when lowercase is displayed. If
this is the case, press
and again.
7
Allow readings to stabilise. Wait for at least 3 minutes and
compare the CO
2
percentage with the values in the table below.
CO
2
value at
maximum power
Natural
gas G20
Natural
gas G25
(in
Belgium)
Propane P
G31
(30/50 mb
ar)
Propane P
G31
(37 mbar)
Maximum value
9.6
8.3
10.8
Minimum value
8.6
7.3
9.8
8
Note down the CO
2
percentage at maximum power. This is
important with regard to the next steps.
CAUTION
It is NOT possible to adjust the CO
2
percentage when test
program is running. When the CO
2
percentage deviates
from the values in the table above, please contact your
local service department.
9
Select Low setting by simultaneously pressing
and buttons
once. will appear on the service display. The user interface
will display Busy.
10
Allow readings to stabilise. Wait for at least 3 minutes and
compare the CO
2
percentage with the values in the table below.
CO
2
value at
minimum power
Natural
gas G20
Natural
gas G25
(in
Belgium)
Propane P
G31
(30/50 mb
ar)
Propane P
G31
(37 mbar)
Maximum value
(a)
Minimum value
8.4
7.4
9.4
9.4
(a)
CO
2
value at maximum power recorded at High setting.
11
If the CO
2
percentage at maximum and minimum power is
within the range expressed in the tables above, the CO
2
setting
of the boiler is correct. If NOT, adjust the CO
2
setting according
to the instructions in the chapter below.
12
Switch off the appliance by pressing the button and put the
sampling point back in its place. Make sure it is gastight.
13
Put the front panel back in its place.
CAUTION
Work on gas carrying parts may only be carried out by a
qualified competent person.
To adjust the carbon dioxide setting
INFORMATION
Only adjust the CO
2
setting when you have checked it first
and are sure adjustment is necessary. In Belgium, any
modifications to the gas valve MUST be performed by a
certified representative of the manufacturer. For more
information, contact your dealer.
1
Remove the cap that covers the adjustment screw. In the
illustration, the cover cap is already removed.
2
Turn the screw (a) to increase (clockwise) or decrease
(counterclockwise) the CO
2
percentage. See the table below for
the desired value.
a
a
Adjusting screw with cover
Measured value at
maximum power
Adjustment values CO
2
(%) at
minimum power (front cover opened)
Natural gas 2H
(G20, 20 mbar)
Propane 3P (G31,
30/50/37 mbar)
10.8
—
10.5±0.1
10.6
10.3±0.1
10.4
10.1±0.1
10.2
9.9±0.1
10.0
9.8±0.1
9.8
9.6±0.1
9.6
9.0±0.1
—
9.4
8.9±0.1
9.2
8.8±0.1
9.0
8.7±0.1
8.8
8.6±0.1
8.6
8.5±0.1
3
After measuring the CO
2
percentage and adjusting the setting,
put the cover cap and the sampling point back in their place.
Make sure they are gastight.
4
Select High setting by simultaneously pressing
and twice.
Capital will appear on the service display.
5
Measure the CO
2
percentage. If the CO
2
percentage still
deviates from the values in the table indicating the CO
2
percentage at maximum power, contact your local dealer.
6
Press and simultaneously to exit the test program.