SAFETY PRECAUTIONS

!

 WARNING

!

 CAUTION

•  Installation and maintenance should be performed by 

qualified persons who are familiar with local code and 
regulation, and experienced with this type of appliance.

•  All field wiring must be installed in accordance with the 

national wiring regulation.

•  Ensure that the rated voltage of the unit corresponds to that 

of the name plate before commencing wiring work according 
to the wiring diagram.

•  The unit must be GROUNDED to prevent possible hazard 

due to insulation failure.

•  All electrical wiring must not touch the water piping or any 

moving parts of the fan motors.

•  Confirm that the unit has been switched OFF before 

installing or servicing the unit.

•  Risk of electric shock, can cause injury or death. Disconnect 

all remain electric power supplies before servicing.

•  DO NOT pull out the power cord when the power is ON. 

This may cause serious electrical shocks which may result 
in the fire hazards.

•  Keep the indoor and outdoor units, power cable and 

transmission wiring, at least 1m from TVs and radios, to 
prevent distorted pictures and static. {Depending on the type 
and source of the electrical waves, static may be heard even 
when more than 1m away}.

Please take note of the following important points when 
installing.
•  Ensure that the drainage piping is connected properly.

  If the drainage piping is not connected properly, it may 

cause water leakage which will dampen the furniture.

•  Ensure that the unit’s panel is closed after service or 

installation.

  Unsecured panels will cause the unit to operate 

noisily.

•  Sharp edges and coil surfaces are potential locations which 

may cause injury hazards. Avoid from being in contact with 
these places.

•  Before turning off the power supply set the remote 

controller’s ON/OFF switch to the “OFF” position to 
prevent the nuisance tripping of the unit. 

If this is not done, 

the unit’s fans will start turning automatically when power 
resumes, posing a hazard to service personnel or the user.

•  Do not install the units at or near doorway.
•  Do not install the units at area like hot spring or oil refinery 

plant where sulphide gas exists.

•  Do not operate any heating apparatus too close to the air 

conditioner unit or use in room where mineral oil, oil vapour 
or oil steam exist, this may cause platic part to melt or 
deform as a result of excessive heat or chemical reaction.

•  When the unit is used in kitchen, keep flour away from going 

into suction of the unit.

•  This unit is not suitable for factory used where cutting oil 

mist or iron powder exist or voltage fluctuates greatly.

•  Ensure the color of wires of the outdoor unit and the 

terminal markings are same to the indoors respectively.

•  IMPORTANT : DO NOT INSTALL OR USE THE AIR 

CONDITIONER UNIT IN A LAUNDRY ROOM.

•  Don’t use joined and twisted wires for incoming power 

supply.

• 

 The equipment is not intended for use in a potentially 
explosive atmosphere.

INSTALLATION MANUAL

This manual provides the procedures of installation to ensure a safe and good standard of operation for the air 
conditioner unit.
Special adjustment may be necessary to suit local requirement.
Before using your air conditioner, please read this instruction manual carefully and keep it for future reference.
This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for 
commercial use by lay persons.
This appliance is not intended for use by persons, including children, with reduced physical, sensory or mental 
capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning 
use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.

NOTICE

Disposal requirement

Your air conditioning product is marked with this symbol. This means that electrical and electronic products shall 
not be mixed with unsorted household waste.
Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of the 
refrigerant, of oil and of other parts must be done by a quali

fi

 ed installer in accordance with relevant local and 

national legislation.
Air conditioners must be treated at a specialized treatment facility for re-use, recycling and recovery. By ensuring 
this product is disposed of correctly, you will help to prevent potential negative consequences for the environment 
and human health. Please contact the installer or local authority for more information.
Batteries must be removed from the remote controller and disposed of separately in accordance with relevant 
local and national legislation.

IM-CCCW 0308(5)DK(asean)-EN.indd5   5

IM-CCCW 0308(5)DK(asean)-EN.indd5   5

11/29/13   8:37:30 AM

11/29/13   8:37:30 AM

Summary of Contents for C-Series

Page 1: ...D CHILLED WATER FAN COIL UNIT C Series INSTALLATION MANUAL IM CCCW 0308 5 DAIKIN ASEAN Part No R08019031562E CVR IM CCCW 0308 5 DK asean ind1 1 CVR IM CCCW 0308 5 DK asean ind1 1 11 29 13 8 34 18 AM 11 29 13 8 34 18 AM ...

Page 2: ...CVR IM CCCW 0308 5 DK asean ind2 2 CVR IM CCCW 0308 5 DK asean ind2 2 11 29 13 8 34 19 AM 11 29 13 8 34 19 AM ...

Page 3: ... M L K G D 150 31 10 51 10 150 31 E A B C F 131 P 40 36 40 20 10 N O Q 178 133 39 131 40 10 63 WATEROUTLET All dimensions are in mm I J I H LEFT PIPING WATERINLET All dimensions are in mm 10 D H 31 150 51 31 150 10 I J I K L M F C B A E P 131 40 40 20 36 10 N O 63 10 40 131 40 133 178 Q G RIGHT PIPING WATEROUTLET WATERINLET IM CCCW 0308 5 DK asean EN indd1 1 IM CCCW 0308 5 DK asean EN indd1 1 11 2...

Page 4: ...A FOR FWPMM4 121 179 133 84 60 M L K D H 31 51 10 10 31 R G I J I Q 131 40 40 40 131 40 P N O 10 10 36 E C B A F R LEFT PIPING WATEROUTLET WATERINLET WATEROUTLET WATERINLET WATEROUTLET WATERINLET All dimensions are in mm 31 10 SEE DETAILA FOR FWPMM4 SEE DETAIL B FOR FWPMM6 7 DETAIL B FOR FWPMM6 7 DETAIL A FOR FWPMM4 I J I 10 R G M L K D H R 31 51 F C B A P 40 131 40 10 N O 40 131 40 Q 36 10 60 133...

Page 5: ... 31 FWPMM11AV1 97 638 559 186 233 563 156 148 97 149 51 All dimensions are in mm 25 W 160 22 V U T C O 15 15 S 15 P M L E B A F K D G 371 40 15 16 50 25 R H Q N I J I LEFT PIPING WATEROUTLET WATERINLET 16 50 W 15 25 R H K L M G D 371 40 F C B A E P S 15 15 15 N O 25 U T V 22 160 Q I J I All dimensions are in mm RIGHT PIPING WATEROUTLET WATERINLET IM CCCW 0308 5 DK asean EN indd3 3 IM CCCW 0308 5 D...

Page 6: ...59 159 109 196 FWPMM12AV1 173 541 462 173 307 467 359 159 109 196 FWPMM14AV1 173 541 462 173 307 594 359 156 106 196 FWPMM16AV1 183 541 462 173 307 694 359 154 104 196 Q 15 59 188 60 U T N O 15 40 93 40 P E C B A F G R 40 I J I H D 25 50 15 M L K S All dimensions are in mm LEFT PIPING WATEROUTLET WATERINLET I D H 25 J I 50 40 S G K L M R F C B A E P 40 93 40 15 N O 60 188 59 Q V T U 15 15 All dime...

Page 7: ...atic part to melt or deform as a result of excessive heat or chemical reaction Whentheunitisusedinkitchen keepflourawayfromgoing into suction of the unit This unit is not suitable for factory used where cutting oil mist or iron powder exist or voltage fluctuates greatly Ensure the color of wires of the outdoor unit and the terminal markings are same to the indoors respectively IMPORTANT DO NOT INS...

Page 8: ...n in the diagram INSTALLATION DIAGRAM INSTALLATION OF THE INDOOR UNIT CAUTION Do not install the unit at altitude over 2000m for both indoor and outdoor CC FWPMM3A Z V1 FWPMM4A Z V1 FWPMM6A Z V1 FWPMM7A Z V1 FWPMM8A Z V1 A mm 741 881 1041 1176 959 L mm 225 225 225 225 339 CC FWPMM9A Z V1 FWPMM11A Z V1 FWPMM12A Z V1 FWPMM14A Z V1 FWPMM16A Z V1 A mm 956 1264 1076 1326 1526 L mm 266 401 266 266 266 3...

Page 9: ...lve Gate Valve Gate Valve FCU Two Way Valve Good Controlling Bad Controlling Gate Valve Gate Valve FCU Worst Controlling WATER PIPING CONNECTION 100 100 The drain pipe must be installed as shown in the diagram see diagram above to avoid damage caused by leaks and condensation For the best result keep the piping as short as possible Slant the piping at an angle to improve the flow Ensure the drain ...

Page 10: ...z or 208 230V 1ø 60Hz TH FSC FSC FL FM FH L N FL FM FH L N L N L N L N FL Fan Low FM Fan Medium FH Fan High L Live N Neutral FSC Fan Speed Controller X1 X2 X3 Relay 220 240V 10A TH Thermostat FCU 1 FCU 2 FCU 3 FSC X2 X1 Chiller SH H M L N TH 220 240V 1ø 50Hz or 208 230V 1ø 60Hz TH X3 220 240V 1ø 50Hz or 208 230V 1ø 60Hz 220 240V 1ø 50Hz or 208 230V 1ø 60Hz TH FSC FSC SH H M L N SH H M L N L N L N ...

Page 11: ...Hz or 208 230V 1ø 60Hz L N 3WV 3 way valve Field supply X1 X2 X3 Relay 220 240V 10A FCU 1 FCU 2 FCU 3 Note This is a proposed wiring connection It may change subject to the chiller unit and must comply with the local and national code and regulations Model Indoor FWPMM3A Z V1 FWPMM4A Z V1 FWPMM6A Z V1 FWPMM7A Z V1 FWPMM8A Z V1 Voltage Range Indoor 220V 240V 1Ph 50Hz or 208V 230V 1Ph 60Hz Power Sup...

Page 12: ... C F Minimum indoor temperature 19 0 66 2 14 0 57 2 Maximum indoor temperature 32 0 89 6 23 0 73 4 All wires must be firmly connected Make sure all the wire do not touch the refrigerant pipings compressor or any moving parts The connecting wire between the indoor unit and the outdoor unit must be clamped by using provided cord anchorage The power supply cord must be equivalent to H07RN F which is ...

Page 13: ... or chemicals to clean the indoor unit 1 2 At least once every 2 weeks More frequently if necessary Indoor Fan Check for any abnormal noise 1 When necessary For any enquiries on spare part please contact your authorized dealer When any malfunction of the air conditioner unit is noted immediately switch off the power supply to the unit Check the following fault conditions and causes for some simple...

Page 14: ...MEMO IM CCCW 0308 5 DK asean EN indd12 12 IM CCCW 0308 5 DK asean EN indd12 12 11 29 13 8 37 32 AM 11 29 13 8 37 32 AM ...

Page 15: ...CVR IM CCCW 0308 5 DK asean ind3 3 CVR IM CCCW 0308 5 DK asean ind3 3 11 29 13 8 34 19 AM 11 29 13 8 34 19 AM ...

Page 16: ...0 B 8400 Oostende Belgium Importer for Turkey Hürriyet Mahallesi Yakacık D 100 Kuzey Yanyol Caddesi No 49 1 2 Kartal İstanbul Head office Umeda Center Bldg 2 4 12 Nakazaki Nishi Kita ku Osaka 530 8323 Japan Tokyo office JR Shinagawa East Bldg 2 18 1 Konan Minato ku Tokyo 108 0075 Japan http www daikin com global CVR IM CCCW 0308 5 DK asean ind4 4 CVR IM CCCW 0308 5 DK asean ind4 4 11 29 13 8 34 19...