31
Mode
No.
(Note 1)
FIRST
CODE
NO.
Description
SECOND CODE NO.
(Note 2)
(Items in bold are factory default settings)
01
02
03
04
05
13 (23)
0
High ceiling setting (Setting
for when installed in ceiling
higher than 2.7 m).
* Height depends on the
connection model.
Refer to the installation
manual attached to the
indoor unit to be
connected for details.
≤2.7 m
*
2.7 m<,
≤3.0 m
*
3.0 m<,
≤3.5 m
*
—
—
1
Selection of airflow direction
(Setting for when a sealing
pad of air discharge outlet
has been installed).
4-way air
discharge
3-way air
discharge
2-way air
discharge
—
—
3
Selection of airflow function
(Setting for when using a
decoration panel for
outlet).
Equipped
Not
equipped
—
—
—
4
Airflow direction range
setting.
Upper
Normal
Lower
—
—
6
Setting the external static
pressure (Setting
according to the
connected duct resistance)
Normal
High static
pressure
Low
static
pressure
—
—
For FHYK
Normal
High ceiling
—
—
—
15 (25)
3
Drain pump operation with
humidifying.
Equipped
Not
equipped
—
—
—
1A
00 Pre Vent setting (Fresh-up)
Disabled
Enabled
—
—
—
1B
08
Daylight savings time
setting
Disabled
Change at
fixed time
Change on
individual
remote
controllers
(manually)
Change by
linkage
with
centralized
device
Change on
individual
remote
controllers
(automatically)
1C
01
Change room temperature
display
Inlet
temperature
Remote
controller
thermistor
—
—
—
12
External linkage adapter
B1 input setting
Unreferenced
Referenced
—
—
—
13
External linkage adapter
B2 input setting
Unreferenced
Referenced
—
—
—
14 Key card function
Disabled
Enabled
—
—
—
1E
02
Setback function
availability
OFF
Heating
only
Cooling
only
Both
heating
and
cooling
—
14
Mold Proof setting
(Streamer)
Disabled
Enabled
—
—
—