![Daikin BRC1E62 Installation Manual Download Page 18](http://html.mh-extra.com/html/daikin/brc1e62/brc1e62_installation-manual_501774018.webp)
17
7-6
Press ON/OFF button within about
10 seconds. The test operation starts.
Check operation condition for
3 minutes.
*
Note) In the case of above-men-
tioned procedures
7-5
and
7-6
in reverse order, test
operation can start as well.
7-7
Press Airflow Setting button.
7-8
Select airflow direction setting by
pressing the " " button on the setting
screen.
Use the "
" buttons to change the
airflow direction.
7-9
After the operation of airflow direction
is confirmed, press Menu/Enter button.
Basic screen returns.
7-10
Press and hold Cancel button for
4 seconds or longer in the Basic
screen.
Service Settings menu is displayed.
7-11
Select
Test Operation
in the Service
Settings menu, and press Menu/Enter
button. Basic screen returns and
normal operation is conducted.
*
Note) Test operation will automatically
finish in 30 minutes.
7-12
Check the functions according to the
operation manual.
7-13
When the decoration panel is not
installed, turn off the power after the
test operation finishes.
● If the interior finish work is not completed
when the test operation is finished, for
protection of the air conditioner ask the
customer not to operate the air conditioner
until the interior finish work is completed.
If the air conditioner is operated, the inside
of the indoor units may be polluted by
substances generated from the coating
and adhensives used for the interior finish
work and cause water splash and leakage.
7-6
Cool
Test Operation
Press ON/OFF button
(within 10 seconds).
7-7
Return
Setting
Return
Setting
Air volume/direction
Air Volume
Direction
Position 0
Low
Press Airflow Setting
button.
To select airflow direction
setting, press " " (Right)
button on the setting screen.
7-9
Return
Setting
Return
Setting
Air volume/direction
Air Volume
Direction
Low
Position 0
Change the airflow
direction by using
"
"
(Up/Down) button.
Press Menu/Enter button.
7-10
Cool
Test Operation
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
7-11
Return
Setting
Service Settings 1/3
Test Operation
Maintenance Contact
Field Settings
Min Setpoints Differential
Group Address
Indoor unit AirNet Address
Press Menu/Enter button.
<Basic screen>
Summary of Contents for BRC1E62