15
Mode
No.
Note) 1
FIRST
CODE
NO.
Description of setting
SECOND CODE NO. Note) 2
01
02
03
04
12 (22)
1
ON/OFF input from outside (Setting
for when forced ON/OFF is to be
operated from outside).
Forced OFF
ON/OFF
operation
—
—
2
Thermostat differential changeover
(Setting for when using remote
sensor).
1°C
0.5°C
—
—
13 (23)
0
High ceilling setting (Setting for
when installed in ceilling higher than
2.7m).
*
Height depends on the connection
model.
Refer to the installation manual
attached to the indoor unit to be
connected for details.
≤
2.7m
*
2.7m<,
≤
3.0m
*
3.0m<,
≤
3.5m
*
—
1
Selection of airflow direction (Setting
for when a sealing pad of air
discharge outlet has been installed).
4-way air
discharge
3-way air
discharge
2-way air
discharge
—
3
Selection of airflow function (Setting
for when using a decoration panel
for outlet).
Equipped
Not equipped
—
—
4
Airflow direction range setting.
Upper
Normal
Lower
—
6
Setting the external static pressure
(Setting according to the connected
duct resistance)
Normal
High static
pressure
Low static
pressure
—
For FHYK
Normal
High ceiling
—
—
15 (25)
3
Drain pump operation with
humidifying.
Equipped
Not equipped
—
—
1c
1
Thermostat sensor in remote
controller (For Auto mode and
Setback function only)
Not use
Use
—
—
1e
2
Setback function
Not use
Heating only
Cooling
only
Cooling
and
Heating
Notes)
1. Though setting is performed totally in the group, set Mode No. in the parenthesis when
individual setting per indoor unit or checking after the setting should be performed.
2. SECOND CODE NO. at factory shipment is set to "01".
However for the following cases it is not "01".
● Airflow direction range setting (except Round flow cassette)
…
"02"
● Thermostat sensor in remote controller (SPLIT system only)
…
"02"
● Thermostat sensor in remote controller for auto mode and Setback function
only
…
"02"
● Setback function
…
"04"
3. Any function which the indoor unit does not have is not displayed.