7. Test operation method (in the case of
SPLIT system)
*
In the case of VRV system, refer to the manual attached to the outdoor unit.
Also refer to installation manuals attached to the indoor unit and the
outdoor unit.
● Check that wiring work of the indoor unit and the outdoor unit is completed.
● Check that control box lid of the indoor unit and the outer panel and piping cover of the outdoor unit
are closed.
● After refrigerant piping, drain piping and electric wiring are completed, clean the inside of the indoor
unit and decoration panel.
● Perform the test operation according to following procedure.
7-1
To protect the compressor, turn on the
power to the outdoor unit at least 6
hours prior to test operation.
7-2
Confirm that stop valves of both liquid
side and gas side are opened.
<Make sure that outer panel and
piping cover are closed before
operation (danger of electric
shock). >
*
After air purge by vacuum pump,
refrigerant pressure may not rise
even though the stop valve is
opened. The reason is that refriger-
ant system of the outdoor unit is
blocked by electric expansion valve
or the like. Operation is no problem.
7-3
Press Mode Selector button to select
Cool mode.
7-4
Press and hold Cancel button for
4 seconds or longer. Service Settings
menu is displayed.
7-5
Select
Test Operation
in the Service
Settings menu, and press Menu/Enter
button. Basic screen returns and "Test
Operation" is displayed.
● The backlight will be lit for approximately
30 seconds by pressing any operation button.
● Operate the buttons during the backlight lit.
However, ON/OFF can be operated concur-
rently with the backlight lit.
Notes for backlight
<Basic screen>
7-3
7-4
Cool
Set to
Cool
28
°C
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
<Service Setting menu screen>
7-5
Return
Setting
Service Settings 1/3
Test Operation
Maintenance Contact
Field Settings
Min Setpoints Differential
Group Address
Indoor unit AirNet Address
Press Menu/Enter button.