EDUS39-605
Control Devices
Controls
53
4. Forced Reset Switch (SS1)
When changing the setting of the connector for individual use, the switch can be reset simply by setting it to the reset
side once and returning to the normal side. This procedure enables to reset without turning off the power. Set the
normal side at normal operation.
5. Setting for special function
When you want to have programmed operation for some functions of indoor units by using only the schedule timer,
cut off J1 and supply the power again.
You can have a programmed operation of the indoor units. Set the address for central control by local remote controller.
3. Transmission Wiring
In case of individual use of schedule timer, take the following action:
Connect terminals of the schedule timer (F1, F2) with terminals of the indoor unit (F1, F2). Connect terminals of the schedule
timer (D1, D2) and the connector on the indoor unit PC board, using the attached electric wire and crimp style terminals.
Prevent the connection part of crimp style terminal from hanging outside the electric parts box.
In case of combined
use with other optional controllers for centralized control, take the following action:
Connect terminals of the schedule timer (F1, F2, D1, D2) and the terminals of the central remote controller or unified
ON/OFF controller.
Wiring Specifications
NOTES:
1. Electrical box and transmission wiring are not attached.
2. Do not touch the PC board with your hand.
3. Keep transmission wiring at least 2 inches away from power supply wiring to prevent malfunctions.
F1, F2
D1, D2
Wiring
2-conductor, stranded, non-shielded copper cable /
PVC or vinyl jacket
2-conductor, stranded, non-shielded copper cable /
PVC or vinyl jacket
Gauge
AWG18
AWG18
Length
Max. 3280 ft. (1000 m)
Max. 492 ft. (150 m)
Summary of Contents for BRC1C71
Page 1: ......
Page 8: ...EDUS39 605 Control Devices Controls 7 2 1 6 Installation ...
Page 9: ...Control Devices EDUS39 605 8 Controls 18 2AWG ...
Page 70: ...EDUS39 605 Control Devices Controls 69 2 8 7 Electrical Wiring Connection ...
Page 71: ...Control Devices EDUS39 605 70 Controls ...
Page 72: ...EDUS39 605 Control Devices Controls 71 ...
Page 73: ...Control Devices EDUS39 605 72 Controls 1P167242A ...
Page 77: ...Adaptors EDUS39 605 76 Controls C 1PA63164D 2 ...
Page 78: ...EDUS39 605 Adaptors Controls 77 3 3 DTA109A51 DIII NET Expander Adaptor ...
Page 79: ...Adaptors EDUS39 605 78 Controls ...
Page 80: ...EDUS39 605 Adaptors Controls 79 ...
Page 81: ...Adaptors EDUS39 605 80 Controls 3 4 KRP1B71 72 73 Adaptor for wiring ...
Page 82: ...EDUS39 605 Adaptors Controls 81 C 2P164806 ...
Page 83: ...Adaptors EDUS39 605 82 Controls 3 5 KRP4A71 72 73 74 Wiring Adaptor for Electrical Appendices ...
Page 84: ...EDUS39 605 Adaptors Controls 83 1P161220 ...
Page 85: ...Adaptors EDUS39 605 84 Controls ...
Page 86: ...EDUS39 605 Adaptors Controls 85 ...