EDUS39-605
Control Devices
Controls
9
2.1.7
Field Setting Wired Remote Controller BRC1C71
Field Setting Contents and Code No.
If optional accessories are mounted on the indoor unit, its settings may have to be changed. Refer to the instruction manual
for each setting.
Procedure
1. When in the normal mode, press the
button for a minimum of four seconds, and the
FIELD SET MODE is entered.
2. Select the desired MODE NO. with the
button
O
.
3. During group control, when setting by each
indoor unit (mode No. 20, 21 and 23 have
been selected), push the
button (
P
) and
select the INDOOR UNIT NO to be set. This
operation is unnecessary when setting by
group.
4. Push the
upper button
Q
and select
FIRST CODE NO.
5. Push the
lower button
R
and select the
SECOND CODE NO.
6. Push the
button
S
once and the present
settings are SET.
7. Push the
button
T
for about one second
to return to the NORMAL MODE.
Example: If set for group setting and the time to clean air filter is set to:
FILTER CONTAMINATION-HEAVY
,
you should set
MODE NO. to [
10
], FIRST CODE NO. to [
0
] and SECOND CODE NO. [
02]
.
Mode No.
Note)1
FIRST
CODE No.
Description of Settings
SECOND CODE NO. Note)4
01
02
03
04
10(20)
0
Filter Contamination-Heavy/
Light: Setting for display time
to clean air filter. Time alert to
clean air filter is cut in half
when heavy filter
contamination.
UltraLong-Life
Type
Light
Approx.
10,000
hours
Heavy
Approx.
5,000
hours
—
—
Long-Life Type
Approx.
2,500
hours
Approx.
1,250
hours
Standard Type
Approx.
200 hours
Approx.
100 hours
1
Long-life or Standard filter type: Setting of filter
indication time. Change setting to Ultralong-life
filter if one is installed
Long-Life
Filter
Ultra-Long-
Life Filter
—
—
2
Thermostat Sensor in Remote Controller
Use
Not Use
—
—
3
Display Time to Clean Air Filter Calculation (Set
when filter sign is not to be displayed
Display
Do not
Display
—
—
12(22)
0
Optional accessories output selection field
selection of output for adaptor for wiring
Indoor Unit
Turned ON by
Thermostat
—
Operation
Output
Malfunction
Output
1
ON/OFF Input from Outside: Set when ON/OFF is
to be controlled from outside.
Forced Off
ON/OFF
Control
External
Protection
Device
—
2
Thermostat Differential Changeover: Set when
remote sensor is to be used.
FXFQ only
1°C
0.5°C
—
—
4
Automatic mode differential: Automatic
temperature differential setting for VRV system
heat recovery series cool/heat
01 : 0
02 : 1
03 : 2
04 : 3
05 : 4
06 : 5
07 : 6
08 : 7
5
Power failure automatic reset: Auto Restart
Not equipped
Equipped
—
—
13(23)
1
Selection of Air Flow Direction: Set when a blocking
pad kit has been installed FXFQ only
F
(4 directions)
T
(3 directions)
W
(2 directions)
—
4
Field set airflow position setting
Draft
Prevention
Standard
Ceiling Soiling
Prevention
—
5
Field set fan speed selection: Fan speed control by
air discharge outlet for phase control
Standard
Optional
Accessory 1
Optional
Accessory 2
—
TEST
SETTIING
Unit NO.
UNIT NO.
SECOND
CODE NO.
MODE NO.
FIELD
SET
MODE
FIRST
CODE NO.
2P068938
1 7
6
3
4
5
2
Summary of Contents for BRC1C71
Page 1: ......
Page 8: ...EDUS39 605 Control Devices Controls 7 2 1 6 Installation ...
Page 9: ...Control Devices EDUS39 605 8 Controls 18 2AWG ...
Page 70: ...EDUS39 605 Control Devices Controls 69 2 8 7 Electrical Wiring Connection ...
Page 71: ...Control Devices EDUS39 605 70 Controls ...
Page 72: ...EDUS39 605 Control Devices Controls 71 ...
Page 73: ...Control Devices EDUS39 605 72 Controls 1P167242A ...
Page 77: ...Adaptors EDUS39 605 76 Controls C 1PA63164D 2 ...
Page 78: ...EDUS39 605 Adaptors Controls 77 3 3 DTA109A51 DIII NET Expander Adaptor ...
Page 79: ...Adaptors EDUS39 605 78 Controls ...
Page 80: ...EDUS39 605 Adaptors Controls 79 ...
Page 81: ...Adaptors EDUS39 605 80 Controls 3 4 KRP1B71 72 73 Adaptor for wiring ...
Page 82: ...EDUS39 605 Adaptors Controls 81 C 2P164806 ...
Page 83: ...Adaptors EDUS39 605 82 Controls 3 5 KRP4A71 72 73 74 Wiring Adaptor for Electrical Appendices ...
Page 84: ...EDUS39 605 Adaptors Controls 83 1P161220 ...
Page 85: ...Adaptors EDUS39 605 84 Controls ...
Page 86: ...EDUS39 605 Adaptors Controls 85 ...