Control Devices
EDUS39-605
36
Controls
4. Forced reset switch
When changing the setting of the connector for the main controller, you can reset simply by setting it to the reset side
once and returning to the normal side, without turning the power OFF.
For normal operation, set the switch to the normal OFF side.
5. Special Function Settings
Special functions on the central control system can be changed while in FIELD SETTING mode.
Setting Procedure
1.
=
Press and hold the
TEST
button for four seconds or more to set the system to FIELD SETTING mode.
2.
=
Use the
ZONE No.
button to select a desired temperature.
Press
to increase the Mode No. Press
to decrease the Mode No.
3.
=
Press the
CODE No.
button for control mode to select a
Switch Setting No
.
4.
=
Press the
SET
button to determine the content of the changed setting. The blinking display then reads
Switch
Setting No
.
5.
=
Press the
TEST
button to return the system to NORMAL mode. In this case, you do not need to turn cycle the power
again.
Example: If no restricted items from the sub-central remote controller while in double-central control, set Mode No. to
[
02]
and the Switch Setting No. to [
0]
.
6. Refreshed operation
Refreshed operation is the default setting from the factory and enables setting of TEMPERATURE CONTROL and
TEMPERATURE SETTING automatically when turning on the unit from DCS302C71.
7. Factory default setting
OUTDOOR SYSTEMS
INDOOR UNITS
Cooling Mode
Cooling 82°F
C
4
2
1.5
3
SET
Mode No.
No. of Switch Setting
Summary of Contents for BRC1C71
Page 1: ......
Page 8: ...EDUS39 605 Control Devices Controls 7 2 1 6 Installation ...
Page 9: ...Control Devices EDUS39 605 8 Controls 18 2AWG ...
Page 70: ...EDUS39 605 Control Devices Controls 69 2 8 7 Electrical Wiring Connection ...
Page 71: ...Control Devices EDUS39 605 70 Controls ...
Page 72: ...EDUS39 605 Control Devices Controls 71 ...
Page 73: ...Control Devices EDUS39 605 72 Controls 1P167242A ...
Page 77: ...Adaptors EDUS39 605 76 Controls C 1PA63164D 2 ...
Page 78: ...EDUS39 605 Adaptors Controls 77 3 3 DTA109A51 DIII NET Expander Adaptor ...
Page 79: ...Adaptors EDUS39 605 78 Controls ...
Page 80: ...EDUS39 605 Adaptors Controls 79 ...
Page 81: ...Adaptors EDUS39 605 80 Controls 3 4 KRP1B71 72 73 Adaptor for wiring ...
Page 82: ...EDUS39 605 Adaptors Controls 81 C 2P164806 ...
Page 83: ...Adaptors EDUS39 605 82 Controls 3 5 KRP4A71 72 73 74 Wiring Adaptor for Electrical Appendices ...
Page 84: ...EDUS39 605 Adaptors Controls 83 1P161220 ...
Page 85: ...Adaptors EDUS39 605 84 Controls ...
Page 86: ...EDUS39 605 Adaptors Controls 85 ...