6
■
English
Example
If the time to clean air filter is set to “Filter Contamination-Heavy”, set Mode No. to “
10
”, First code No. to “
0
”, and Second code No.
to “
02
”.
Mode
No.
First
code
No.
Description of setting
Second code No.
01
02
03
10
0
Sets operation time until AIR FILTER
CLEANING TIME INDICATOR lamp
lights up. (When dirt and dust levels
are high, change the setting to “Filter
Contamination-Heavy”.)
Long-life
filter
Light
±2,500
hrs.
Heavy
±1,250
hrs.
—
3
Changes AIR FILTER CLEANING TIME
INDICATOR lamp on/off settings.
On
Off
—
13
0
Setting air outlet velocity.
This setting is to be changed in function of ceiling
height (H).
≤8-7/8ft
(≤2.7m)
8-7/8<H≤9-13/16ft
(2.7<H≤3.0m)
9-13/16<H≤11-1/2ft
(3.0<H≤3.5m)
1
Selection of air flow direction.
This setting is to be changed when blocking pad
optional kit is used.
4-way flow
3-way flow
2-way flow
4
Airflow direction range setting.
This setting is to be changed when range of swing
flap movement needs to be changed.
Upper
Medium
Lower
NOTE
Factory settings of the Second code No. are marked in grey backgrounds.
Do not use any settings not listed in the table.
For group control with a wireless remote controller, initial settings for all the indoor units of the group are equal.
(For group control, refer to the installation manual supplied with the indoor unit for group control.)