Daikin BRC082A41W Installation Manual Download Page 8

6

English

Example

If the time to clean air filter is set to “Filter Contamination-Heavy”, set Mode No. to “

10

”, First code No. to “

0

”, and Second code No. 

to “

02

”.

Mode

No.

First

code

No.

Description of setting

Second code No.

01

02

03

10

0

Sets operation time until AIR FILTER 
CLEANING TIME INDICATOR lamp 
lights up. (When dirt and dust levels 
are high, change the setting to “Filter 
Contamination-Heavy”.)

Long-life 

filter

Light

±2,500

hrs.

Heavy

±1,250

hrs.

3

Changes AIR FILTER CLEANING TIME 
INDICATOR lamp on/off settings.

On

Off

13

0

Setting air outlet velocity.
This setting is to be changed in function of ceiling 
height (H).

≤8-7/8ft 

 

(≤2.7m)

8-7/8<H≤9-13/16ft

(2.7<H≤3.0m)

9-13/16<H≤11-1/2ft

(3.0<H≤3.5m)

1

Selection of air flow direction.

This setting is to be changed when blocking pad 
optional kit is used.

4-way flow

3-way flow

2-way flow

4

Airflow direction range setting.

This setting is to be changed when range of swing 

flap movement needs to be changed.

Upper

Medium

Lower

NOTE 
Factory settings of the Second code No. are marked in grey backgrounds. 
Do not use any settings not listed in the table. 
For group control with a wireless remote controller, initial settings for all the indoor units of the group are equal. 
(For group control, refer to the installation manual supplied with the indoor unit for group control.)

01_EN_3P444567-1.indd   6

7/5/2016   11:05:30 AM

Summary of Contents for BRC082A41W

Page 1: ...añol WIRELESS REMOTE CONTROLLER KIT INSTALLATION MANUAL Installation manual Manuel dinstallation Manual de instalación MODELS BRC082A41W BRC082A42W BRC082A42S Manuel dinstallation 00_CV_3P444567 1 indd 1 5 11 2016 13 44 03 ...

Page 2: ...BRC082A42W 1 1 3 4 1 1 BRC082A42S 1 1 3 4 1 1 Figure 1 X24A X1A X2A 1 7 2 3 6 2 7 5 3 4 2 Figure 2 MODE TIMER RESERVE CANCEL DOWN UP TEST SWING FAN TIME TEMP ON OFF SETTING A B C 3 2 4 1 5 MODE TIMER RESERVE CANCEL DOWN UP TEST SWING FAN TIME TEMP ON OFF SETTING B D C A 3 2 4 5 1 6 Figure 3 Figure 4 00_CV_3P444567 1_H2 indd 1 6 29 2016 2 25 08 PM ...

Page 3: ...ow to operate the unit and how to perform maintenance Meaning of caution symbols Failure to observe these instructions properly may result in property damage or personal injury Information classified as NOTE contains instructions to ensure proper use of the equipment Refer also to the installation manual supplied with the indoor unit and the installation manual supplied with the decoration panel T...

Page 4: ...eceiver and the wireless remote controller If using both a wired remote controller and a wireless remote controller with one indoor unit change the MAIN SUB switch of the transmitter board Setting procedure Setting the transmitter board Set the wireless address switch SS2 on the transmitter board according to the table below Unit No 1 2 3 Wireless address switch SS2 1 2 3 1 2 3 1 2 3 When using bo...

Page 5: ...he indications on the wireless remote controller are turned off a discrepancy such as described above no longer occurs Affix the unit number label Affix corresponding unit number labels onto both air outlet of the decoration panel and onto back of the wireless remote controller NOTE Set the Unit No of the receiver and the wireless remote controller to be equal If the settings differ the signal fro...

Page 6: ...e decoration panel Then attach the receiver to the decoration panel Lead the wire harness to the electrical wiring box on the indoor unit and connect it to X1A connector on the transmitter board Remove the screw and input the plastic band Then screw it back The wire harness goes through the plastic band Clamp the wire harness from the receiver to other cables with the clamp Installation of the rec...

Page 7: ... setting If optional accessories are mounted on the indoor unit the indoor unit setting may have to be changed Refer to the instruction manual option handbook for each optional accessory See figure 4 A Mode No B Field Set mode C First code No D Second code No Procedure 1 When in normal mode hold down the button for at least 4 seconds to enter the Field Set mode 2 Select the desired Mode No with th...

Page 8: ...nged in function of ceiling height H 8 7 8ft 2 7m 8 7 8 H 9 13 16ft 2 7 H 3 0m 9 13 16 H 11 1 2ft 3 0 H 3 5m 1 Selection of air flow direction This setting is to be changed when blocking pad optional kit is used 4 way flow 3 way flow 2 way flow 4 Airflow direction range setting This setting is to be changed when range of swing flap movement needs to be changed Upper Medium Lower NOTE Factory setti...

Page 9: ...Two dimensional bar code is a manufacturing code 3P444567 1 M15B280 1607 HT 00_CV_3P444567 1 indd 2 5 11 2016 13 44 03 ...

Reviews: