background image

6 Installation

Installer reference guide

14

AZAS71~Y1

Sky Air Active-series

4P486048-1A – 2017.08

Piping size

(mm)

Tightening

torque (N•m)

Flare

dimensions (A)

(mm)

Flare shape

(mm)

Ø9.5

33~39

12.8~13.2

R=0.4~0.8

45° ±2

90°±2

A

Ø15.9

63~75

19.3~19.7

6.4.4

Pipe bending guidelines

Use  a  pipe  bender  for  bending.  All  pipe  bends  should  be  as  gentle
as possible (bending radius should be 30~40 mm or larger).

6.4.5

To flare the pipe end

CAUTION

▪ Incomplete flaring may cause refrigerant gas leakage.

▪ Do  NOT  re-use  flares.  Use  new  flares  to  prevent

refrigerant gas leakage.

▪ Use  flare  nuts  that  are  included  with  the  unit.  Using

different flare nuts may cause refrigerant gas leakage.

1

Cut the pipe end with a pipe cutter.

2

Remove  burrs  with  the  cut  surface  facing  down  so  that  the
chips do not enter the pipe.

a

b

a

Cut exactly at right angles.

b

Remove burrs.

3

Remove  the  flare  nut  from  the  stop  valve  and  put  the  flare  nut
on the pipe.

4

Flare  the  pipe.  Set  exactly  at  the  position  as  shown  in  the
following illustration.

A

Flare tool for R32

(clutch type)

Conventional flare tool

Clutch type

(Ridgid-type)

Wing nut type

(Imperial-type)

A

0~0.5 mm

1.0~1.5 mm

1.5~2.0 mm

5

Check that the flaring is properly made.

a

b

c

a

Flare’s inner surface must be flawless.

b

The pipe end must be evenly flared in a perfect circle.

c

Make sure the flare nut is fitted.

6.4.6

To braze the pipe end

The  indoor  unit  and  outdoor  unit  have  flare  connections.  Connect
both  ends  without  brazing.  If  brazing  should  be  needed,  take  the
following into account:

▪ When  brazing,  blow  through  with  nitrogen  to  prevent  creation  of

large  quantities  of  oxidised  film  on  the  inside  of  the  piping.  This
film adversely affects valves and compressors in the refrigerating
system and prevents proper operation.

▪ Set  the  nitrogen  pressure  to  20  kPa  (0.2  bar)  (just  enough  so  it

can be felt on the skin) with a pressure-reducing valve.

a

b

c

d

e

f

f

a

Refrigerant piping

b

Part to be brazed

c

Taping

d

Manual valve

e

Pressure-reducing valve

f

Nitrogen

▪ Do NOT use anti-oxidants when brazing pipe joints.

Residue can clog pipes and break equipment.

▪ Do  NOT  use  flux  when  brazing  copper-to-copper  refrigerant

piping.  Use  phosphor  copper  brazing  filler  alloy  (BCuP),  which
does not require flux.
Flux  has  an  extremely  harmful  influence  on  refrigerant  piping
systems. For instance, if chlorine based flux is used, it will cause
pipe  corrosion  or,  in  particular,  if  the  flux  contains  fluorine,  it  will
deteriorate the refrigerant oil.

6.4.7

Using the stop valve and service port

To handle the stop valve

Take the following guidelines into account:

▪ The stop valves are factory closed.

▪ The following illustration shows each part required in handling the

valve.

c
d

a

b

a

Service port and service port cap

b

Valve stem

c

Field piping connection

d

Stem cap

▪ Keep both stop valves open during operation.

▪ Do  NOT  apply  excessive  force  to  the  valve  stem.  Doing  so  may

break the valve body.

▪ Always  make  sure  to  secure  the  stop  valve  with  a  spanner,  then

loosen or tighten the flare nut with a torque wrench. Do NOT place
the  spanner  on  the  stem  cap,  as  this  could  cause  a  refrigerant
leak.

a

b

a

Spanner

b

Torque wrench

▪ When  it  is  expected  that  the  operating  pressure  will  be  low  (e.g.

when  cooling  will  be  performed  while  the  outside  air  temperature
is  low),  sufficiently  seal  the  flare  nut  in  the  stop  valve  on  the  gas
line with silicon sealant to prevent freezing.

Silicon sealant, make sure there is no gap.

Summary of Contents for AZAS71M2V1B

Page 1: ...Installer reference guide Sky Air Active series English Installer reference guide Sky Air Active series AZAS71M2V1B AZAS100M7V1B AZAS125M7V1B AZAS140M7V1B AZAS100M7Y1B AZAS125M7Y1B AZAS140M7Y1B...

Page 2: ...refrigerant piping 16 6 5 2 Precautions when checking the refrigerant piping 16 6 5 3 Checking refrigerant piping Setup 16 6 5 4 To check for leaks 16 6 5 5 To perform vacuum drying 17 6 6 Charging r...

Page 3: ...OT touch the refrigerant piping water piping or internal parts during and immediately after operation It could be too hot or too cold Give it time to return to normal temperature If you must touch it...

Page 4: ...d operated and stored must be larger than the minimum floor area defined in table below A m2 This applies to Indoor units without refrigerant leakage sensor in case of indoor units with refrigerant le...

Page 5: ...leakage If refrigerant gas leaks ventilate the area immediately Possible risks Excessive refrigerant concentrations in a closed room can lead to oxygen deficiency Toxic gas may be produced if refriger...

Page 6: ...egory III condition MUST be installed in the fixed wiring WARNING ONLY use copper wires Make sure the field wiring complies with the applicable legislation All field wiring must be performed in accord...

Page 7: ...s Safety instructions that you must read before installing About the documentation What documentation exists for the installer About the box How to unpack the units and remove their accessories About...

Page 8: ...ambient temperature regions For these regions the RZAG model is recommended 5 Preparation 5 1 Overview Preparation This chapter describes what you have to do and know before going on site It contains...

Page 9: ...ght be higher than the sound pressure level mentioned in Sound spectrum in the data book due to environmental noise and sound reflections INFORMATION The sound pressure level is less than 70 dBA In pl...

Page 10: ...1 Minimum total one way piping length Limit L1 5 m 2 Maximum total one way piping length L1 Limit 30 m 50 m a 3 Maximum height between indoor and outdoor H1 Limit 30 m a Parenthesised figure represent...

Page 11: ...2 1 About opening the units At certain times you have to open the unit Example When connecting the refrigerant piping When connecting the electrical wiring When maintaining or servicing the unit DANG...

Page 12: ...unit in order to prevent the invasion of water in the unit and to avoid the drain water dripping see the following illustration INFORMATION If necessary you can use a drain plug kit field supply to p...

Page 13: ...thing but the designated refrigerant to get mixed into the refrigerant cycle e g air Only use R32 when adding refrigerant Only use installation tools e g manifold gauge set that are exclusively used f...

Page 14: ...d film on the inside of the piping This film adversely affects valves and compressors in the refrigerating system and prevents proper operation Set the nitrogen pressure to 20 kPa 0 2 bar just enough...

Page 15: ...tdoor unit Piping length Keep field piping as short as possible Piping protection Protect the field piping against physical damage 1 Do the following Remove the service cover a with screw b Remove the...

Page 16: ...ay have entered the piping first carry out the vacuum drying procedure below until all moisture has been removed 6 5 2 Precautions when checking the refrigerant piping INFORMATION Also read the precau...

Page 17: ...additional refrigerant make sure the outdoor unit s external refrigerant piping is checked leak test vacuum drying INFORMATION Depending on the units and or the installation conditions it might be nec...

Page 18: ...stible heating devices ventilate the room and contact the dealer from which you purchased the unit Do not use the unit until a service person confirms that the portion from which the refrigerant leake...

Page 19: ...it on top of a b Factory refrigerant charge see unit name plate c Additional refrigerant amount charged d Total refrigerant charge e Greenhouse gas emissions of the total refrigerant charge expressed...

Page 20: ...crimp style ring terminals 6 7 5 Specifications of standard wiring components Component V1 Y1 71 100 125 140 100 125 140 Power supply cable MCA a 17 5 A 21 8 A 28 3 A 27 6 A 14 6 A 15 1 A Voltage ran...

Page 21: ...frame Choose one of the 3 possibilities a b a b a b 2 3 1 a Power supply cable b Interconnection cable Connecting to the frame When cables are routed from the unit a protection sleeve for the conduit...

Page 22: ...at up the compressor oil to avoid oil shortage and compressor breakdown during startup NOTICE NEVER operate the unit without thermistors and or pressure sensors switches Burning of the compressor migh...

Page 23: ...ice cover to prevent electric shocks 3 Turn ON power for at least 6 hours before starting operation to protect the compressor 4 On the user interface set the unit to cooling operation mode 2 Start the...

Page 24: ...the unit 9 Maintenance and service NOTICE Maintenance must be done by an authorised installer or service agent We recommend to do maintenance at least once a year However applicable legislation might...

Page 25: ...ly with applicable legislation Units must be treated at a specialised treatment facility for reuse recycling and recovery 11 1 Overview Disposal Typical workflow Disposing of the system typically cons...

Page 26: ...ow of units A E a b c d e eB eD a b c d e eB eD A B C D E B HU HD H B 100 A B C 250 100 100 B E 100 1000 500 A B C E 250 150 150 1000 500 D 500 D E 500 1000 500 B D 100 500 B D E 1 2 1 HB HD HB HU 250...

Page 27: ...e upper unit high enough above the lower unit to prevent ice buildup at the upper unit s bottom plate B1 B2 B1 If there is no danger of drainage dripping and freezing between the upper and lower units...

Page 28: ...ctive devices S1PH S1PLand Q1E 3 Refer to the combination table and the option manual for how to connect the wiring to X6A X28A and X77A 4 Colours BLK black RED red BLU blue WHT white GRN green 4 Lege...

Page 29: ...icable for a certain product or domain Service company Qualified company which can perform or coordinate the required service to the product Installation manual Instruction manual specified for a cert...

Page 30: ......

Page 31: ......

Page 32: ...4P486048 1A 2017 08 Copyright 2017 Daikin...

Reviews: