background image

6 Installation

Installer reference guide

13

AZAS71~Y1
Sky Air Active-series
4P486048-1A – 2017.08

3

Insert  a  rubber  sheet  between  the  cables  and  the  outdoor  unit
to prevent the cable from scratching the paint (field supply).

4

Attach the cable’s ends. Tighten those ends.

6.4

Connecting the refrigerant piping

6.4.1

About connecting the refrigerant piping

Before connecting the refrigerant piping

Make sure the outdoor and indoor unit are mounted.

Typical workflow

Connecting the refrigerant piping involves:

▪ Connecting the refrigerant piping to the outdoor unit

▪ Connecting the refrigerant piping to the indoor unit

▪ Installing oil traps

▪ Insulating the refrigerant piping

▪ Keeping in mind the guidelines for:

▪ Pipe bending

▪ Flaring pipe ends

▪ Brazing

▪ Using the stop valves

6.4.2

Precautions when connecting the
refrigerant piping

INFORMATION

Also  read  the  precautions  and  requirements  in  the
following chapters:

▪ General safety precautions

▪ Preparation

DANGER: RISK OF BURNING

CAUTION

▪ Do NOT use mineral oil on flared part.

▪ Do NOT reuse piping from previous installations.

▪ NEVER  install  a  drier  to  this  R32  unit  to  guarantee  its

lifetime. The drying material may dissolve and damage
the system.

NOTICE

Take  the  following  precautions  on  refrigerant  piping  into
account:

▪ Avoid  anything  but  the  designated  refrigerant  to  get

mixed into the refrigerant cycle (e.g. air).

▪ Only use R32 when adding refrigerant.

▪ Only use installation tools (e.g. manifold gauge set) that

are  exclusively  used  for  R32  installations  to  withstand
the  pressure  and  to  prevent  foreign  materials  (e.g.
mineral oils and moisture) from mixing into the system.

▪ Install  the  piping  so  that  the  flare  is  NOT  subjected  to

mechanical stress.

▪ Protect the piping as described in the following table to

prevent dirt, liquid or dust from entering the piping.

▪ Use  caution  when  passing  copper  tubes  through  walls

(see figure below).

Unit

Installation period

Protection method

Outdoor unit

>1 month

Pinch the pipe

<1 month

Pinch or tape the pipe

Indoor unit

Regardless of the
period

INFORMATION

Do  NOT  open  the  refrigerant  stop  valve  before  checking
the refrigerant piping. When you need to charge additional
refrigerant  it  is  recommended  to  open  the  refrigerant  stop
valve after charging.

6.4.3

Guidelines when connecting the
refrigerant piping

Take the following guidelines into account when connecting pipes:

▪ Coat  the  flare  inner  surface  with  ether  oil  or  ester  oil  when

connecting  a  flare  nut.  Tighten  3  or  4  turns  by  hand,  before
tightening firmly.

▪ Always use 2 wrenches together when loosening a flare nut.

▪ Always  use  a  spanner  and  torque  wrench  together  to  tighten  the

flare nut when connecting the piping. This to prevent nut cracking
and leaks.

a

b

c

d

a

Torque wrench

b

Spanner

c

Piping union

d

Flare nut

Summary of Contents for AZAS71M2V1B

Page 1: ...Installer reference guide Sky Air Active series English Installer reference guide Sky Air Active series AZAS71M2V1B AZAS100M7V1B AZAS125M7V1B AZAS140M7V1B AZAS100M7Y1B AZAS125M7Y1B AZAS140M7Y1B...

Page 2: ...refrigerant piping 16 6 5 2 Precautions when checking the refrigerant piping 16 6 5 3 Checking refrigerant piping Setup 16 6 5 4 To check for leaks 16 6 5 5 To perform vacuum drying 17 6 6 Charging r...

Page 3: ...OT touch the refrigerant piping water piping or internal parts during and immediately after operation It could be too hot or too cold Give it time to return to normal temperature If you must touch it...

Page 4: ...d operated and stored must be larger than the minimum floor area defined in table below A m2 This applies to Indoor units without refrigerant leakage sensor in case of indoor units with refrigerant le...

Page 5: ...leakage If refrigerant gas leaks ventilate the area immediately Possible risks Excessive refrigerant concentrations in a closed room can lead to oxygen deficiency Toxic gas may be produced if refriger...

Page 6: ...egory III condition MUST be installed in the fixed wiring WARNING ONLY use copper wires Make sure the field wiring complies with the applicable legislation All field wiring must be performed in accord...

Page 7: ...s Safety instructions that you must read before installing About the documentation What documentation exists for the installer About the box How to unpack the units and remove their accessories About...

Page 8: ...ambient temperature regions For these regions the RZAG model is recommended 5 Preparation 5 1 Overview Preparation This chapter describes what you have to do and know before going on site It contains...

Page 9: ...ght be higher than the sound pressure level mentioned in Sound spectrum in the data book due to environmental noise and sound reflections INFORMATION The sound pressure level is less than 70 dBA In pl...

Page 10: ...1 Minimum total one way piping length Limit L1 5 m 2 Maximum total one way piping length L1 Limit 30 m 50 m a 3 Maximum height between indoor and outdoor H1 Limit 30 m a Parenthesised figure represent...

Page 11: ...2 1 About opening the units At certain times you have to open the unit Example When connecting the refrigerant piping When connecting the electrical wiring When maintaining or servicing the unit DANG...

Page 12: ...unit in order to prevent the invasion of water in the unit and to avoid the drain water dripping see the following illustration INFORMATION If necessary you can use a drain plug kit field supply to p...

Page 13: ...thing but the designated refrigerant to get mixed into the refrigerant cycle e g air Only use R32 when adding refrigerant Only use installation tools e g manifold gauge set that are exclusively used f...

Page 14: ...d film on the inside of the piping This film adversely affects valves and compressors in the refrigerating system and prevents proper operation Set the nitrogen pressure to 20 kPa 0 2 bar just enough...

Page 15: ...tdoor unit Piping length Keep field piping as short as possible Piping protection Protect the field piping against physical damage 1 Do the following Remove the service cover a with screw b Remove the...

Page 16: ...ay have entered the piping first carry out the vacuum drying procedure below until all moisture has been removed 6 5 2 Precautions when checking the refrigerant piping INFORMATION Also read the precau...

Page 17: ...additional refrigerant make sure the outdoor unit s external refrigerant piping is checked leak test vacuum drying INFORMATION Depending on the units and or the installation conditions it might be nec...

Page 18: ...stible heating devices ventilate the room and contact the dealer from which you purchased the unit Do not use the unit until a service person confirms that the portion from which the refrigerant leake...

Page 19: ...it on top of a b Factory refrigerant charge see unit name plate c Additional refrigerant amount charged d Total refrigerant charge e Greenhouse gas emissions of the total refrigerant charge expressed...

Page 20: ...crimp style ring terminals 6 7 5 Specifications of standard wiring components Component V1 Y1 71 100 125 140 100 125 140 Power supply cable MCA a 17 5 A 21 8 A 28 3 A 27 6 A 14 6 A 15 1 A Voltage ran...

Page 21: ...frame Choose one of the 3 possibilities a b a b a b 2 3 1 a Power supply cable b Interconnection cable Connecting to the frame When cables are routed from the unit a protection sleeve for the conduit...

Page 22: ...at up the compressor oil to avoid oil shortage and compressor breakdown during startup NOTICE NEVER operate the unit without thermistors and or pressure sensors switches Burning of the compressor migh...

Page 23: ...ice cover to prevent electric shocks 3 Turn ON power for at least 6 hours before starting operation to protect the compressor 4 On the user interface set the unit to cooling operation mode 2 Start the...

Page 24: ...the unit 9 Maintenance and service NOTICE Maintenance must be done by an authorised installer or service agent We recommend to do maintenance at least once a year However applicable legislation might...

Page 25: ...ly with applicable legislation Units must be treated at a specialised treatment facility for reuse recycling and recovery 11 1 Overview Disposal Typical workflow Disposing of the system typically cons...

Page 26: ...ow of units A E a b c d e eB eD a b c d e eB eD A B C D E B HU HD H B 100 A B C 250 100 100 B E 100 1000 500 A B C E 250 150 150 1000 500 D 500 D E 500 1000 500 B D 100 500 B D E 1 2 1 HB HD HB HU 250...

Page 27: ...e upper unit high enough above the lower unit to prevent ice buildup at the upper unit s bottom plate B1 B2 B1 If there is no danger of drainage dripping and freezing between the upper and lower units...

Page 28: ...ctive devices S1PH S1PLand Q1E 3 Refer to the combination table and the option manual for how to connect the wiring to X6A X28A and X77A 4 Colours BLK black RED red BLU blue WHT white GRN green 4 Lege...

Page 29: ...icable for a certain product or domain Service company Qualified company which can perform or coordinate the required service to the product Installation manual Instruction manual specified for a cert...

Page 30: ......

Page 31: ......

Page 32: ...4P486048 1A 2017 08 Copyright 2017 Daikin...

Reviews: