background image

9

12.1 Low Voltage Connections

Several combinations of low voltage schemes are possible, 

depending on the presence of a heat kit and whether the 

heat kit is single-stage or multi-stage, whether the outdoor 

section is an air conditioner or heat pump, and whether 

the outdoor section is single-stage or two stage. The 

24V-control voltage connects the air handle to the room 

thermostat and condenser. Low voltage wiring must be 

copper conductors. A minimum of 18AWG must be used 

for installations. Low voltage wiring must be connected 

through the top of the cabinet or either side.

0.1

0.2

0.3

T1

630

602

576

T2

630

602

576

T3

637

609

586

T4

630

602

576

T5

846

824

800

T1

630

602

576

T2

630

602

576

T3

784

763

742

T4

630

602

576

T5

846

823

800

T1

683

604

525

T2

900

856

803

T3

1079

1025

989

T4

944

897

848

T5

1168

1127

1083

T1

1114

1072

1031

T2

1114

1072

1031

T3

1225

1191

1152

T4

1287

1255

1219

T5

1360

1329

1299

Model

Speed

Tap

CFM @ STATIC PRESSURE (IN W.C.)

AWSF18SU16** AA

AWST18SU14** AA

AWSF24SU16** AA

AWST24SU14** AA

AWSF30LU16** AA

AWST30LU14** AA

AWSF36LU16** AA

AWST36LU14** AA

Table 4 

NOTE:

1. 

Airflow data indicated is at 230V without air filter in 

place.

2.  Select a speed tap that provides a minimum 300 CFM 

per outdoor ton. For satisfactory operation, external 

static pressure must no exceed 0.3" WC (for electric 

heater only).

13 EXPANSION VALVE TROUBLESHOOTING

Before replacing an expansion valve, check the following 

items:

1.  Bulb location: Must be tightly secured to the suction 

line upstream of the equalizer connection.

2.  Insulation:  Bulb must be properly insulated.

3.  Equalizer: Must be connected to the 1/4” SAE 

connection on the suction line.

4.  Charge: Ensure the system is properly charged. There 

MUST be a minimum of 10°F Sub-Cooled liquid at the 

valve inlet.

If the system appears to be “starving” (low suction pressure 

but insufficient cooling):

1.  Check the Superheat (SH) at the evaporator outlet. 

If SH is between 5°F - 12°F, the TXV is controlling 

properly. 

-  Verify that there is proper airflow to the evaporator 

(fan is operating and filter is unrestricted).

2.  If SH is above 12°F, the setting of the TXV may be too 

high. 

-  Adjust the SH by turning counter-clockwise to 

decrease SH. 

-  Wait 20 minutes for the system to balance and adjust 

again, as required. 

-  If adjusting the valve has no effect on the SH, the 

valve may be stuck because of dirt or debris or it may 

have lost the Power Element charge.

3.  After properly reclaiming the refrigerant, remove the 

TXV and check for dirt and debris. Clean, if possible, or 

replace the TXV and filter/drier.

If the system appears to be “flooding” (compressor frosting 

or moisture is condensing at the suction connection):

1.  Check the SH at the evaporator outlet.  If SH is 

between 5°F - 12°F, the TXV is controlling properly.

2.  If SH is less than 5°F, the SH adjustment may be too 

low. 

-  Adjust the SH by turning the adjustment stem clock- 

wise to increase the SH. 

-  Wait 20 minutes for the system to balance and ad- 

just again as required. 

-  If adjusting the valve has no effect on the SH, the 

valve may be stuck open because of dirt or debris or 

moisture in the refrigerant.

3.  After properly reclaiming the refrigerant, remove the 

TXV and check for dirt and debris. Clean, if possible, 

or replace the TXV and filter/drier.  Add a moisture 

indicator to allow checking of moisture if this is believed 

to be a probable cause.

Summary of Contents for AWSF18SU16 Series

Page 1: ...R PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES IF YOU SERVICE THIS UNIT YOU ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY RESULT IN ADDITION IN JURISDICTIONS...

Page 2: ...SERIOUS PROPERTY DAMAGE OR PERSONAL INJURY REDUCED UNIT PERFORMANCE AND OR HAZARDOUS CONDITIONS MAY RESULT FROM THE USE OF DEVICES THAT HAVE NOT BEEN APPROVED OR CERTIFIED BY THE MANUFACTURER CONTENTS...

Page 3: ...of carbon monoxide CO poisoning resulting from the exhaust emissions If a furnace or air handler is installed in an enclosed area such as a garage utility room or parking area and a carbon monoxide p...

Page 4: ...g guidelines If possible allow adequate length of tubing such that the coil may be removed for inspection or cleaning services from the cabinet without disconnecting the tubing Note These air handlers...

Page 5: ...ADIAN ELECTRIC CODE CSA C22 1 FAILURE TO OBSERVE THIS WARNING CAN RESULT IN ELECTRICAL SHOCK THAT CAN CAUSE PERSONAL INJURY OR DEATH WARNING 7 1 Building Electrical Service Inspection This unit is des...

Page 6: ...ped with the unit When these requirements are satisfied the unit achieves the following airflow leakage when tested in accordance with ASHRAE Standard 193 Cabinet air leakage less than 2 at 1 0 inch H...

Page 7: ...ction line Ensure the thermometer makes adequate contact and is insulated for best possible readings Use liquid line temperature to determine subcooling and vapor temperature to determine superheat 3...

Page 8: ...24 VAC 18 Gauge 24 VAC Y R G W C Y Y Note Connect T2 T3 or T4 to the Y terminal to the outdoor unit See Table 5 for correct CFM selec on T1 T5 Figure 3 NOTE Connect appropriate speed tap Pink Purple Y...

Page 9: ...3 Equalizer Must be connected to the 1 4 SAE connection on the suction line 4 Charge Ensure the system is properly charged There MUST be a minimum of 10 F Sub Cooled liquid at the valve inlet If the...

Page 10: ...ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT M ULTIPLE POWER SOURCES MAY BE PRESENT F AILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH Wiring is subject to change Always refer...

Page 11: ...ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT M ULTIPLE POWER SOURCES MAY BE PRESENT F AILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH Wiring is subject to change Always refer...

Page 12: ...ING THIS UNIT M ULTIPLE POWER SOURCES MAY BE PRESENT F AILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH WIRING DIAGRAM AWSF30LU16 AWST30LU14 Wiring is subject to change Always refer...

Page 13: ...ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT M ULTIPLE POWER SOURCES MAY BE PRESENT F AILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH Wiring is subject to change Always refer...

Page 14: ...he unit without first discussing your plans with your dealer or other qualified servicer Restricted airflow could lead to poor operation and or severe equipment damage Likewise it is important to keep...

Page 15: ...WB F DB F WB F Heating Supply Air Temperature DB F Temperature Rise DB F Delta T Difference between Supply and Return Temperatures DB F AirHandler Coil InverterMatched INVERTERAH COILONLY Check EEV an...

Page 16: ...page DAIKIN AMANA BRAND GOODMAN BRAND DAIKIN AMANA BRAND GOODMAN BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty regist...

Reviews: