SiUS341802E
Symptom-based Troubleshooting
Service Diagnosis
152
1.5
Error Codes and Descriptions
k
: ON
h
: OFF
l
: Blink
Error code
Operation
lamp
Error contents
Reference
page
Indoor Unit
A0
l
External protection device abnormality
A1
l
Indoor unit PCB abnormality
A3
l
Drain level control system abnormality
A6
l
Indoor fan motor lock, overload
Indoor fan motor abnormality
Overload/overcurrent/lock of indoor fan motor
Blower motor not running
Indoor fan motor status abnormality
Low indoor airflow
A7 (
∗
1)
k
Swing flap motor abnormality
A8
l
Power supply voltage abnormality
Blower motor stops for over/under voltage
A9
l
Electronic expansion valve coil abnormality, dust clogging
AF (
∗
1)
k
Drain level above limit
AJ
l
Capacity determination device abnormality
C1
l
Transmission abnormality between indoor unit PCB and fan PCB
Blower motor communication error
C4
l
Heat exchanger liquid pipe thermistor abnormality
C5
l
Heat exchanger gas pipe thermistor abnormality
C6
l
Combination error between indoor unit PCB and fan PCB
Blower motor HP mismatch
Indoor blower does not have required parameters to function
C9
(
∗
2)
l
Suction air thermistor abnormality
Remote sensor abnormality
CA
l
Discharge air thermistor abnormality
CC
k
Humidity sensor system abnormality
CE (
∗
1)
k
Infrared presence/floor sensor error
CJ
(
∗
2)
k
Remote controller thermistor abnormality
Outdoor Unit
E1
l
Outdoor unit PCB abnormality
E2
l
Detection of ground leakage by leak detection circuit
Missing of ground leakage detection core
E3
l
Actuation of high pressure switch
E4
l
Actuation of low pressure sensor
E5
l
Inverter compressor motor lock
E6
l
Compressor damage alarm
E7
l
Outdoor fan motor abnormality
E9
l
Electronic expansion valve coil abnormality
F3
l
Discharge pipe temperature abnormality
F4
l
Wet alarm
F6
l
Refrigerant overcharged
Outdoor Unit
H3
l
Harness abnormality (between outdoor unit main PCB and inverter PCB)
H7
l
Outdoor fan motor signal abnormality
Outdoor fan PCB abnormality
H9
l
Outdoor air thermistor (R1T) abnormality
J3
l
Discharge pipe thermistor (R21T) abnormality
Compressor body thermistor (R14T) abnormality
J5
l
Compressor suction thermistor (R12T) abnormality
Suction pipe thermistor (R10T) abnormality
J6
l
Heat exchanger deicer thermistor (R11T) abnormality
Heat exchanger gas pipe thermistor (R8T, R9T) abnormality
J7
l
Receiver inlet thermistor (R3T) abnormality
Subcooling heat exchanger liquid pipe thermistor (R7T) abnormality
Subcooling injection thermistor (R16T) abnormality
J8
l
Heat exchanger liquid pipe thermistor (R4T, R5T) abnormality
Leak detection thermistor (R15T) abnormality
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...