SiUS341802E
Troubleshooting by Error Code
Service Diagnosis
224
2.38 Harness Abnormality (between Outdoor Unit Main PCB
and Inverter PCB)
Error Code
H3
Applicable
Models
All outdoor unit models
Method of Error
Detection
Check for the transmission conditions of the harnesses between the PCBs using microcomputer.
Error Decision
Conditions
Normal transmission between the PCBs is disabled while the compressor stops running.
Supposed
Causes
Defective connection of jumpers between PCB
Defective outdoor unit main PCB (A1P)
Defective inverter PCB
Troubleshooting
Check for the transmission
conditions of the following
harnesses.
(1) X6A (Inverter PCB)
↔
X28A (A1P)
(2) X63A (Inverter PCB)
↔
X40A (A1P)
Replace the outdoor unit main
PCB (A1P).
Replace the inverter PCB.
RXLQ-TATJU,
RXLQ-TAYDU: A3P
RXLQ-TAYCU,
RXYQ-TAYCU: A4P
YES
NO
YES
Complete countermeasures.
Return the relevant harness to
normal.
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.