SiUS341802E
Troubleshooting by Error Code
Service Diagnosis
204
2.25 Remote Controller Thermistor Abnormality
Error Code
CJ
Applicable
Models
All indoor unit models
Method of Error
Detection
Error detection is carried out by temperature detected by the remote controller thermistor.
Error Decision
Conditions
The remote controller thermistor becomes disconnected or shorted while the unit is running.
Supposed
Causes
Defective remote controller thermistor
Defective remote controller PCB
Troubleshooting
Note:
∗
1. How to delete the history of error codes.
Press the ON/OFF button for 4 seconds or more while the error code is displayed in the
inspection mode.
Clear the error code history.
(
∗
1) (While in inspection mode,
press and hold the ON/OFF
button for a period of 4
seconds or more.)
YES
YES
Is
CJ
displayed on the remote
controller?
Is the field
setting 10(20)-2
correct?
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace the remote
controller.
Correct the field setting.
External factor other than
equipment error.
(for example, noise etc.)
NO
NO
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...