INSTALLATION 
MANUAL

R410A Split Series

Models 
ATXS20E2V1B

ATKS20E2V1B

ATXS25E2V1B

ATKS25E2V1B

ATXS35E2V1B

ATKS35E2V1B

ATXS50E2V1B
ATXS20EV1B7
ATXS25EV1B7
ATXS35EV1B7
ATXS50EV1B7

English

Deutsch

Français

Nederlands

Español

Italiano

Ελληνικ

Ü

Portugues

Installation manual

R410A Split series

Installationsanleitung

Split-Baureihe R410A

Manuel d’installation

Série split R410A

Montagehandleiding

R410A Split-systeem

Manual de instalación

Serie Split R410A

Manuale d’installazione

Serie Multiambienti R410A

Εγχειρ

ß

διο

 

εγκατ

Ü

σταση

ò

διαιρο

ýì

ενη

ò 

σειρ

Üò R410A

Manual de Instalação

     Série split R410A

00_CV_3P212421-1.fm  Page 1  Friday, July 20, 2007  2:31 PM

Summary of Contents for ATXS20E2V1B

Page 1: ...an ais Nederlands Espa ol Italiano Portugues Installation manual R410A Split series Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A Split s...

Page 2: ...6 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Dai...

Page 3: ...amping may cause terminal overheating or fire After connecting interconnecting and supply wiring be sure to shape the cables so that they do not put undue force on the electrical covers or panels Inst...

Page 4: ...m electronic ignition type fluorescent lamps inverter or rapid start type as they may shorten the remote control range 8 the unit is at least 1 metre away from any television or radio set unit may cau...

Page 5: ...ter 2 Remove the front grille 3 In front of the mark of the front grille there are 3 upper hooks Lightly pull the front grille toward you with one hand and push down on the hooks with the fingers of y...

Page 6: ...con trollers can be set for different addresses 1 In the same way as when connecting to an HA system remove the metal plate electrical wiring cover 2 Cut the address jumper JA on the printed circuit b...

Page 7: ...finishing tape from bottom to top Cut thermal insulation pipe to an appropriate length and wrap it with tape making sure that no gap is left in the insulation pipe s cut line Caulk pipe hole gap with...

Page 8: ...and Dimensions 80 100 400 135 450 283 47 5 141 5 50 5 46 5 44 5 131 5 87 44 5 110 60 130 220 50 60 110 800 65 65 Use tape measure as shown Position the end of a tape measure at Keep here the piece cu...

Page 9: ...e and refrigerant pipes through the wall hole then set the indoor unit on the mounting plate hooks by using the markings at the top of the indoor unit as a guide 4 Open the front panel then open the s...

Page 10: ...atch indoor unit press the bottom edge of indoor unit with both hands until it is firmly caught by the mounting plate hooks Secure indoor unit to the mounting plate with screws M4 12L 3 3 Wall embedde...

Page 11: ...rds or starburst connections as they may cause overheating electrical shock or fire 2 Do not use locally purchased electrical parts inside the product Do not branch the power for the drain pump etc fr...

Page 12: ...e pipe 5 Check that the flaring is properly made WARNING 1 Do not use mineral oil on flared part 2 Prevent mineral oil from getting into the system as this would reduce the lifetime of the units 3 Nev...

Page 13: ...efrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide in...

Page 14: ...turned off 1 3 Carry out the test operation in accordance with the Operation Manual to ensure that all functions and parts such as louver movement are working properly The air conditioner requires a...

Page 15: ...0710 HT 3P212421 1 M07B075 Two dimensional bar code is a code for manufacturing 00_CV_3P212421 1 fm Page 2 Friday July 20 2007 2 31 PM...