background image

5 Unit installation

Installation manual

9

FTXP20~3 ATXP20~35N5V1B
Daikin room air conditioner
3P650253-9H – 2022.10

d

Through-the-wall hole Ø65 mm

e

Drain hose position

f

Position for the tape measure at symbol " "

g

Gas pipe end

h

Liquid pipe end

5.3.2

To drill a wall hole

CAUTION

For walls containing a metal frame or a metal board, use a
wall  embedded  pipe  and  wall  cover  in  the  feed-through
hole to prevent possible heat, electrical shock, or fire.

NOTICE

Be  sure  to  seal  the  gaps  around  the  pipes  with  sealing
material (field supply), in order to prevent water leakage.

1

Bore  a  65  mm  large  feed-through  hole  in  the  wall  with  a
downward slope towards the outside.

2

Insert a wall embedded pipe into the hole.

3

Insert a wall cover into the wall pipe.

Ø65

a b

c

a

Wall embedded pipe

b

Putty

c

Wall hole cover

4

After  completing  wiring,  refrigerant  piping  and  drain  piping,  do
NOT forget to seal the gap with putty.

5.3.3

To remove the pipe port cover

INFORMATION

To  connect  the  piping  on  right-side,  right-bottom,  left-side
or left-bottom, the pipe port cover MUST be removed.

1

Cut  off  the  pipe  port  cover  from  inside  the  front  grille  using  a
coping saw.

2

Remove  any  burrs  along  the  cut  section  using  a  half  round
needle file.

NOTICE

Do NOT use nippers to remove the pipe port cover, as this
would damage the front grille.

5.3.4

To provide drainage

Make  sure  condensation  water  can  be  evacuated  properly.  This
involves:

▪ General guidelines

▪ Connecting the drain piping to the indoor unit

▪ Checking for water leaks

General guidelines

Pipe length.

 Keep drain piping as short as possible.

Pipe  size.

  If  drain  hose  extension  or  embedded  drain  piping  is

required, use appropriate parts that match the hose front end.

Ø16

Ø18

NOTICE

▪ Install the drain hose with a downward slope.

▪ Traps are NOT permitted.

▪ Do NOT put the end of the hose in water.

Drain  hose  extension.

  To  extend  the  drain  hose,  use  a  field

supplied  hose  with  inner  Ø16  mm.  Do  NOT  forget  to  use  a  heat
insulation tube on the indoor section of the extension hose.

a

a

b

c

Ø16

Ø16

a

Drain hose supplied with the indoor unit

b

Heat insulation tube (field supply)

c

Extension drain hose

Ridgid  polyvinyl  chloride  pipe.

  When  connecting  a  ridgid

polyvinyl  chloride  pipe  (nominal  Ø13  mm)  directly  to  the  drain
hose  as  with  embedded  piping  work,  use  a  field  supplied  drain
socket (nominal Ø13 mm).

a

b

c

Ø18

a

Drain hose supplied with the indoor unit

b

Drain socket with nominal Ø13 mm (field supply)

c

Ridgid polyvinyl chloride pipe (field supply)

Condensation.

  Take  measures  against  condensation.  Insulate

the complete drain piping in the building.

1

Insert the drain hose in the drain pipe as shown in the following
figure, so it will NOT be pulled out of the drain pipe.

Summary of Contents for ATXP20N5V1B

Page 1: ...Installation manual Daikin room air conditioner English Installation manual Daikin room air conditioner FTXP20N5V1B FTXP25N5V1B FTXP35N5V1B ATXP20N5V1B ATXP25N5V1B ATXP35N5V1B...

Page 2: ...s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za predpokladu e sa v robk...

Page 3: ...7 1206 Radio Equipment Regulations 2017 following the provisions of BS EN 60335 2 40 2003 A13 2012 BS EN IEC 62311 2020 BS EN IEC 55014 1 2021 BS EN IEC 55014 2 2021 BS EN IEC 61000 3 2 2019 A1 2021 B...

Page 4: ...fferent channel of the indoor unit infrared signal receiver 13 10 Commissioning 14 10 1 Checklist before commissioning 14 10 2 To perform a test run 14 10 2 1 To perform a test run in winter season 14...

Page 5: ...ill be sucked in This will cause abnormal pressure in the refrigeration cycle which may result in equipment damage and even injury CAUTION Incomplete flaring may cause refrigerant gas leakage Do NOT r...

Page 6: ...DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes and measure the voltage at the terminals of main circuit capacitors or electrical components before servicing The vol...

Page 7: ...fety precaution 5 1 1 Installation site requirements of the indoor unit INFORMATION The sound pressure level is less than 70 dBA Air flow Make sure nothing blocks the air flow Drainage Make sure conde...

Page 8: ...then mount the front panel 5 2 5 To remove the electrical wiring box cover 1 Remove the front grille 2 Remove 1 screw from the electrical wiring box 3 Open the electrical wiring box cover by pulling t...

Page 9: ...ppers to remove the pipe port cover as this would damage the front grille 5 3 4 To provide drainage Make sure condensation water can be evacuated properly This involves General guidelines Connecting t...

Page 10: ...left side and do not forget to tighten it with the fixing screw otherwise water leakage may occur a b a b a Insulation fixing screw b Drain hose 4 Attach the drain hose to the refrigerant piping bott...

Page 11: ...it using flare connections 2 Insulate the refrigerant piping interconnection cable and drain hose on the indoor unit as follows c a b f d g e a Gas pipe b Gas pipe insulation c Interconnection cable d...

Page 12: ...cable for 220 240 V Recommended field fuse 20 A Earth leakage circuit breaker Must comply with applicable legislation 7 2 To connect the electrical wiring to the indoor unit WARNING Provide adequate m...

Page 13: ...the bottom frame or the front grille 2 Pass the drain hose and refrigerant piping through the wall hole and seal the gap with a putty 8 3 To fix the unit on the mounting plate 1 Set the indoor unit on...

Page 14: ...e refrigerant pipes gas and liquid are thermally insulated Drainage Make sure drainage flows smoothly Possible consequence Condensate water might drip The system is properly earthed and the earth term...

Page 15: ...operation press INFORMATION Some of the functions CANNOT be used in the test run operation mode If a power failure occurs during operation the system automatically restarts immediately after power is...

Page 16: ...AC CN E HA HE HL HN HR MR _A MR _B S U V W X A K R_ NE Connection connector D V D Diode DB Diode bridge DS DIP switch E H Heater FU F U for characteristics refer to PCB inside your unit Fuse FG Conne...

Page 17: ...FTXP20 35N5V1B ATXP20 35N5V1B Daikin room air conditioner 3P650253 9H 2022 10 Symbol Meaning X Terminal X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoid valve c...

Page 18: ......

Page 19: ......

Page 20: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P650253 9H 2022 10 Copyright 20...

Reviews: