Refrigerant Piping Work
2-2. Selection of Copper and Heat Insulation materials
• When using commercial copper pipes and fittings, observe the
following:
1) Insulation material: Polyethylene foam
Heat transfer rate: 0.041 to 0.052W/mK (0.035 to 0.045kcal/mh
°
C)
Refrigerant gas pipe’s surface temperature reaches 110
°
C max.
Choose heat insulation materials that will withstand this temperature.
2) Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below.
3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
Gas side
Liquid side
25/35 class
50 class
25/35/50 class
O.D. 9.5mm
O.D. 12.7mm
O.D. 6.4mm
Thickness 0.8mm
Thickness 0.8mm
Gas pipe thermal insulation
Liquid pipe thermal insulation
25/35 class
50 class
25/35/50 class
I.D. 12-15mm
I.D. 14-16mm
I.D. 8-10mm
Thickness 10mm Min.
Gas pipe
Liquid pipe
Gas pipe
insulation
Liquid pipe
insulation
Finishing tape
Drain hose
Inter-unit wiring
01_EN_3P166464-1.fm Page 11 Saturday, September 17, 2005 11:08 AM