background image

6 Piping installation

Installation manual

9

ATXF20~42C5V1B
Daikin room air conditioners
3P519299-11X – 2020.12

a

Remove the pipe port cover here for right side piping

b

Remove the pipe port cover here for right-bottom piping

To connect the piping on left side, left-back, or left-
bottom

INFORMATION

The factory default is right-side piping. For left-side piping,
remove  the  piping  from  the  right  side  and  install  it  on  the
left side.

1

Remove  the  insulation  fixing  screw  on  the  right  side  and
remove the drain hose.

2

Remove the drain plug on the left side and attach it to the right
side.

NOTICE

Do  NOT  apply  lubricating  oil  (refrigerant  oil)  to  the  drain
plug when inserting it. The drain plug may deteriorate and
cause drain leakage from the plug.

3

Insert the drain hose on the left side and do not forget to tighten
it with the fixing screw; otherwise water leakage may occur.

a

b

a

b

a

Insulation fixing screw

b

Drain hose

4

Attach the drain hose to the refrigerant piping bottom side using
adhesive vinyl tape.

A

B

b

a

A

Left-side piping

B

Left-back piping

C

Left-bottom piping

a

Remove the pipe port cover here for left-side piping

b

Remove the pipe port cover here for left-bottom piping

To check for water leaks

1

Remove the air filters.

2

Gradually pour approximately 1 l of water in the drain pan, and
check for water leaks.

6

Piping installation

6.1

Preparing refrigerant piping

6.1.1

Refrigerant piping requirements

NOTICE

The  piping  and  other  pressure-containing  parts  shall  be
suitable  for  refrigerant.  Use  phosphoric  acid  deoxidised
seamless copper for refrigerant.

▪ Foreign materials inside pipes (including oils for fabrication) must

be ≤30 mg/10 m.

Refrigerant piping diameter

Use the same diameters as the connections on the outdoor units:

Class

L1 liquid piping

L1 gas piping

20~42

Ø6.4

Ø9.5

6.1.2

Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:

▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035

and 0.045 kcal/mh°C)

▪ with a heat resistance of at least 120°C

▪ Insulation thickness

Pipe outer diameter

p

)

Insulation inner

diameter (Ø

i

)

Insulation thickness

(t)

6.4 mm (1/4")

8~10 mm

≥10 mm

Ø

i

Ø

i

t

Ø

p

Ø

p

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

6.2

Connecting the refrigerant piping

DANGER: RISK OF BURNING/SCALDING

WARNING

▪ Only  use  R32  as  refrigerant.  Other  substances  may

cause explosions and accidents.

▪ R32  contains  fluorinated  greenhouse  gases.  Its  global

warming  potential  (GWP)  value  is  675.  Do  NOT  vent
these gases into the atmosphere.

▪ When  charging  refrigerant,  ALWAYS  use  protective

gloves and safety glasses.

6.2.1

Guidelines when connecting the
refrigerant piping

Take the following guidelines into account when connecting pipes:

▪ Coat  the  flare  inner  surface  with  ether  oil  or  ester  oil  when

connecting  a  flare  nut.  Tighten  3  or  4  turns  by  hand,  before
tightening firmly.

Summary of Contents for ATXF20C5V1B

Page 1: ...Installation manual Daikin room air conditioners English Installation manual Daikin room air conditioners ATXF20C5V1B ATXF25C5V1B ATXF35C5V1B ATXF42C5V1B ...

Page 2: ...или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemiau nurodytus standartus ir arba kitus norminius dokumentus su sąlyga kad yra naudojami pagal mūsų nurodymus tad ja lietoti atbilstoši ražotāja norādījumiem atbilst sekojošiem standartiem un citiem normatīviem dokumentiem sú v zhode s nasledovnou ými normou ami alebo iným i normatívnym i dokumentom am...

Page 3: ...ning 13 10 2 To perform a test run 13 10 2 1 To perform a test run in winter season 13 11 Disposal 13 12 Technical data 14 12 1 Wiring diagram 14 12 1 1 Unified wiring diagram legend 14 1 About the documentation 1 1 About this document Target audience INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial and household...

Page 4: ...rigerant gas leakage DANGER RISK OF EXPLOSION Do NOT start the unit if it is vacuumed Charging refrigerant see Charging refrigerant WARNING The refrigerant inside the unit is mildly flammable but normally does NOT leak If the refrigerant leaks in the room and comes in contact with fire from a burner a heater or a cooker this may result in fire or the formation of a harmful gas Turn off any combust...

Page 5: ...ff the power supply before servicing Install the switch box cover before turning on the power supply Commissioning see 10 Commissioning 413 DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING SCALDING CAUTION Do NOT perform the test operation while working on the indoor units When performing the test operation NOT only the outdoor unit but the connected indoor unit will operate as well Working on ...

Page 6: ...loor and keep the following requirements in mind for distances from the walls and the ceiling 50 50 30 mm 5 1 2 Additional installation site requirements of the outdoor unit in cold climates Protect the outdoor unit against direct snowfall and take care that the outdoor unit is NEVER snowed up In heavy snowfall areas it is very important to select an installation site where the snow will NOT affec...

Page 7: ...the centres of the drilling points on the wall using a tape measure Position the end of tape measure at symbol 4 Finish the installation by securing the mounting plate on the wall using M4 25L screws field supply INFORMATION The removed pipe port cover can be kept in the mounting plate pocket 337 770 A 285 44 5 170 48 48 44 5 116 5 1 17 337 50 213 237 170 A d e mm a a f h g a a b a c a c a d e A A...

Page 8: ... field supplied hose with inner Ø16 mm Do NOT forget to use a heat insulation tube on the indoor section of the extension hose a a b c Ø16 Ø16 a Drain hose supplied with the indoor unit b Heat insulation tube field supply c Extension drain hose Ridgid polyvinyl chloride pipe When connecting a ridgid polyvinyl chloride pipe nominal Ø13 mm directly to the drain hose as with embedded piping work use ...

Page 9: ...6 1 1 Refrigerant piping requirements NOTICE The piping and other pressure containing parts shall be suitable for refrigerant Use phosphoric acid deoxidised seamless copper for refrigerant Foreign materials inside pipes including oils for fabrication must be 30 mg 10 m Refrigerant piping diameter Use the same diameters as the connections on the outdoor units Class L1 liquid piping L1 gas piping 20...

Page 10: ... caps Soap water may contain salt which absorbs moisture that will freeze when the piping gets cold Soap water contains ammonia which may lead to corrosion of flared joints between the brass flare nut and the copper flare 1 Charge the system with nitrogen gas up to a gauge pressure of at least 200 kPa 2 bar It is recommended to pressurize to 3000 kPa 30 bar in order to detect small leaks 2 Check f...

Page 11: ...apart from each other Transmission wiring and power supply wiring may cross but may NOT run parallel In order to avoid any electrical interference the distance between both wirings should ALWAYS be at least 50 mm WARNING Provide adequate measures to prevent that the unit can be used as a shelter by small animals Small animals that make contact with electrical parts can cause malfunctions smoke or ...

Page 12: ...ing plate using 2 indoor unit fixing screws M4 12L accessory 9 Configuration 9 1 To set a different address In case 2 indoor units are installed in 1 room different addresses for 2 user interfaces can be set 1 Remove the batteries from the user interface 2 Cut the address jumper a a a Address jumper NOTICE Be careful NOT to damage any of the surrounding parts when cutting the address jumper 3 Turn...

Page 13: ...witch box The insulation resistance of the compressor is OK There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units There are NO refrigerant leaks The correct pipe size is installed and the pipes are properly insulated The stop valves gas and liquid on the outdoor unit are fully open 10 2 To perform a test run Prerequisite Power supply MUST be in the specifi...

Page 14: ...r D V D Diode DB Diode bridge DS DIP switch E H Heater FU F U for characteristics refer to PCB inside your unit Fuse FG Connector frame ground H Harness H P LED V L Pilot lamp light emitting diode Symbol Meaning HAP Light emitting diode service monitor green HIGH VOLTAGE High voltage IES Intelligent eye sensor IPM Intelligent power module K R KCR KFR KHuR K M Magnetic relay L Live L Coil L R React...

Page 15: ...ion manual 15 ATXF20 42C5V1B Daikin room air conditioners 3P519299 11X 2020 12 Symbol Meaning X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoid valve coil Z C Ferrite core ZF Z F Noise filter ...

Page 16: ...TANBUL TÜRKİYE Tel 0216 453 27 00 Faks 0216 671 06 00 Çağrı Merkezi 444 999 0 Web www daikin com tr Gülsuyu Mahallesi Fevzi Çakmak Caddesi Burçak Sokak No 20 34848 Maltepe 3P519299 11X 2020 12 Copyright 2020 Daikin Verantwortung für Energie und Umwelt ...

Reviews: