Databook Modular T - October 2022 - Rev. 00
26
5.2. Accessories for Pro & Smart version
5.2.1. Filters
The unit is provided as standard with ePM1 50% (F7) filter on supply side and ePM1 75% (M5) filter on return.
On supply side up to three filtration stages as available. It is not possible to install the third filtration stage
and the water post heating coil at the same time. Other filters available are ePM1 80% (F9) filter and ISO
Coarse 55% (G4).The table below summarizes the material names and the pressure drop for each filter, when
it is clean, at nominal air flow for all the sizes.
Material Name
Main Unit Size
Description
∆P Clean (Pa)
∆P
Mean (Pa)
ATF03G4A
03
ISO Coarse 55%
(G4)
61
101
ATF04G4A
04
82
132
ATF05G4A
05
80
130
ATF06G4A
06
78
128
ATF07G4A
07
85
135
ATF03M5A
03
ePM10 75%
(M5)
81
131
ATF04M5A
04
108
158
ATF05M5A
05
105
155
ATF06M5A
06
103
153
ATF07M5A
07
111
161
ATF03F7A
03
ePM1 50%
(F7)
94
144
ATF04F7A
04
125
175
ATF05F7A
05
122
172
ATF06F7A
06
119
169
ATF07F7A
07
129
179
ATF03F9A
03
ePM1 80%
(F9)
148
198
ATF04F9A
04
198
248
ATF05F9A
05
193
243
ATF06F9A
06
188
238
ATF07F9A
07
204
254
The pressure drop is referring to nominal airflow.
Summary of Contents for ATB03RA
Page 21: ...Databook Modular T October 2022 Rev 00 21...
Page 44: ...Databook Modular T October 2022 Rev 00 44 6 4 Dimensional Drawings Dimension Drawing Size 03...
Page 45: ...Databook Modular T October 2022 Rev 00 45 Dimension Drawing Size 04...
Page 46: ...Databook Modular T October 2022 Rev 00 46 Dimension Drawing Size 05...
Page 47: ...Databook Modular T October 2022 Rev 00 47 Dimension Drawing Size 06...
Page 48: ...Databook Modular T October 2022 Rev 00 48 Dimension Drawing Size 07...