5.3.5.4. Digital PCB for external accessories
For accessories mounted externally to the main unit, which require to be controlled, it is mandatory to add
a further digital PCB (ATE00DPUA). The following components require
-
Electric pre and post heating coils
-
Water preheating coil
Digital PCB is also needed when additional filters are mounted and it is required to monitor pressure drop
for each filtration stage, according to VDI6022.
5.4. Accessories only for Smart version
5.4.1. Coils
5.4.1.1. Electrical pre-heating coil
Only coil available for Smart version is pre heating electric coil. In the following table, main info is
summarized:
Size
Material
Name
Max Power
Output (Kw)
Electric
Data
Diameter /
Depth
(mm)
Length
(mm)
Height
(mm)
Weight
(kg)
03
ATD03HEFBU
12
400/3/50
250
325
500
8
04
ATD04HEFBU
15
400/3/50
315
390
630
15
05
ATD05HEFBU
18
400/3/50
355
425
630
17
06
ATD06HEFBU
21
400/3/50
400
485
770
22
07
ATD07HEFBU
24
400/3/50
500
585
785
29
Summary of Contents for ATB03RA
Page 21: ...Databook Modular T October 2022 Rev 00 21...
Page 44: ...Databook Modular T October 2022 Rev 00 44 6 4 Dimensional Drawings Dimension Drawing Size 03...
Page 45: ...Databook Modular T October 2022 Rev 00 45 Dimension Drawing Size 04...
Page 46: ...Databook Modular T October 2022 Rev 00 46 Dimension Drawing Size 05...
Page 47: ...Databook Modular T October 2022 Rev 00 47 Dimension Drawing Size 06...
Page 48: ...Databook Modular T October 2022 Rev 00 48 Dimension Drawing Size 07...